0% found this document useful (0 votes)
48 views

PCRED398026EN1

Sepam 2000 SX is a device used for incomer and feeder protection, metering, and remote control and monitoring. It provides phase and earth fault protection, measures currents, voltages, power, and energy. With communication options, it can enable remote setting, metering, indication and control. It has advantages like continuous self-testing, disconnectable terminals, and simple setting and testing.

Uploaded by

Yousef
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
48 views

PCRED398026EN1

Sepam 2000 SX is a device used for incomer and feeder protection, metering, and remote control and monitoring. It provides phase and earth fault protection, measures currents, voltages, power, and energy. With communication options, it can enable remote setting, metering, indication and control. It has advantages like continuous self-testing, disconnectable terminals, and simple setting and testing.

Uploaded by

Yousef
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

Protection

and control

Sepam range
Sepam 2000 SX
Presentation

Contents page
presentation 2
selection table 3
metering 4
protection 6
control and monitoring 7
functional and connection schemes 9
other connection schemes 11
examples of connection schemes 13
communication 14
characteristics 15
installation 16
ordering information 20

Sepam 2000 SX is used for incomer and feeder


protection and metering. Combined with the
Advantages
communication option, it can provide remote control, c indication of phase and earth fault values at the time of breaking provides
annunciation and metering. the operator with useful assistance in determining the causes and seriousness
of faults,
c the high level of electromagnetic compatibility (EMC) makes it possible to use
advanced digital technology-based functions in electrical substations,
without the need for any particular precautions,
c Sepam 2000's continuous self-testing sets the device in a predetermined
fail-safe position whenever a failure occurs, thereby preventing random operation,
c terminals that are individually disconnectable while energized allow easy
maintenance,
c The optional communication function may be used for remote setting, remote
metering, remote indication and remote control by means of a two-wire link
with a remote control and monitoring system for centralized operation,
c setting and testing are extremely simple:
v the settings may be made on the front panel (serial link):
- one by one, using the TSM2001 pocket terminal, or the SFT2801 PC software
program,
- all at once using the SFT2821 PC software program (downloading),
v direct readout of primary current and voltage and simple testing of the metering
Sepam 2000 S26 compact.
function by injection guarantee the coherency of all settings.
The wide setting ranges provide for the most widely varied cases.
Installation in the switchboard is simplified:
c just one device to install, the Sepam 2000 S26 (compact),
c cabling is limited to:
v standard 1A or 5A current transformers or linear CSP type sensors
(Rogowski coil principle),
v voltage transformers (SX2 version),
v actuators (trip and closing coils).

Customization (1)
Standard control and monitoring carried out in Sepam 2000's internal PLC
can be customized. Sepam 2000 SX does not allow for extension of the logic
inputs and outputs. For applications which require more logic inputs/outputs,
use Sepam 2000 type S01 or S02.

(1)
Please refer to document Sepam 2000 customized
application.

2 Sepam 2000 SX
Selection table

Sepam 2000 substation


functions ANSI Sepam types
code SX1 SX2
protection
phase overcurrent 50/51 4 4
earth fault (sensitive E/F) 50N/51N(G) 4 4
metering
phase currents (I1, I2, I3) c c
peak demand phase currents (I1, I2, I3) c c
voltage (U21, U32, U13, V1, V2, V3) c
real / reactive power (P, Q) c
peak demand real / reactive power c
power factor c
fréquency c
accumulated real / reactive energy (± Wh, ± VArh) c
tripping currents (I1, I2, I3, Io) c c
true rms current c c
disturbance recording c c
residual current c c
residual voltage c
cumulative breaking current c c
and number of breaks
control and monitoring (1)
open / close c c
lockout relay 86 c c
inhibit closing 69 c c
annunciation 30 c c
logic discrimination 68 c c
trip circuit supervision 74 c c
detection of plugged connectors (DPC) 74 c c
operation counter c c
phase fault trip counter c c
disturbance recording triggering c c
Sepam models
compact S26 LX LT

The figures in the columns represent the number of similar protection devices.
For example, for phase overcurrent protection, “4” means: 4 separate overcurrent protection
devices.
(1)
according to parameter setting.

Sepam 2000 SX 3
Metering

Sepam 2000 is an accurate metering device.


Measurements needed for operation
It gives a direct readout of values,
together with the related units, A, V, W...
Currents
All the values needed for operation and used Measurement of the current for each of the 3 phases of the circuit.
for commissioning are available locally
and in the control room. Peak demand currents
Measurement of the greatest average current value on the 3 phases.
The average current measurement is computed periodically (adjustable period:
5, 10, 15, 30 or 60 minutes).
The “clear” button is pressed for zero reset.

Voltages (4)
Measurement of the circuit phase-to-phase and phase-to-neutral voltages.

Real / reactive power (4)


Measurement of the real and reactive power, with the sign, in balanced
and unbalanced 3-phase networks.

Peak demand real / reactive power (4)


Measurement of the greatest average real power (and reactive power) value,
used to find the power absorbed during peak load periods. The average value
is computed periodically (adjustable period: 5, 10, 15, 30 or 60 minutes).
The “clear” button is pressed for zero reset.

Power factor (p.f.) (4)


Measurement of the p.f., with the sign and type (capacitive or inductive),
Measurements accessed on the front panel of Sepam 2000
(serial link and/or display) and via the communication system. of the power conveyed.

Frequency (4)
Measurement of frequency (based on positive sequence voltage or the U21 voltage
input).

Accumulated real / reactive energy (4)


The alphanumerical display unit shows the 4 accumulated real / reactive energy
values:
c real energy consumed,
c reverse real energy,
c reactive energy consumed,
c reverse reactive energy.
These values are saved in the event of a power failure.

Tripping currents
Measurements of the 3 phase currents and the residual current that were stored
at the time that Sepam 2000 gave the tripping order. Used to find
the fault current (fault analysis) and assess the level of wear of the breaker
(maintenance assistance). The "clear" button is pressed for zero reset.

True rms current


Measurement of the rms value of phase 1 current up to 4 In, taking into account:
c fundamental,
c harmonics up to rank 21st.

Disturbance recording
Recording of electrical signals and logical information before and after
a disturbance recorder triggering order is given.

4 Sepam 2000 SX
Measurements used Characteristics
for commissioning functions ranges accuracy (5)

ammeter (1) 0 to 24 In ±0.5%


and maintenance peak demand current (1) 0 to 24 In ±0.5%
voltmeter (1) 0 to 1.5 Un ±0.5%
Residual current / residual voltage
Used to check the current and voltage sensor wattmeter (1) 0 to 999 MW ±1%
connections by giving the measurement of: varmeter (1) 0 to 999 MVAr ±1%
c the residual current used for the earth fault peak demand real power (1) 0 to 999 MW ±1%
protection function, peak demand reactive power(1) 0 to 999 MVAr ±1%
c the residual voltage used for the neutral voltage
displacement and the directional earth fault protection power factor (1) (3) -1 to +1 0.01
functions. frequency meter (1) 45 to 65 Hz ±0.02 Hz
accumulated real energy (1) 0 to 280 x 106 MWh ±1%
Cumulative breaking current accumulated reactive energy (1) 0 to 280 x 106 MVArh ±1%
Used for breaking device maintenance.
tripping currents (1) phase 0 to 24 In ±5%
earth 0 to 10 Ino ±5%
true rms current 0 to 4 In ±1%
up to harmonic 21
(5)
disturbance recording record 86 periods 12 samples
duration per periods
time before 1 to 85 periods
triggering
event
residual current (7) 0 to 10 Ino ±5%
residual voltage (7) 0 to 1.5 Un ±5%
manque le 5 et 6 cumulative breaking current (7)
0 to 9999 (kA)2 ±10%
(7)
number of breaks 0 to 99999
(1)
measurement accessed on the front panel of Sepam 2000 (display and serial link) and via
the communication system.
(2)
measurement accessed on the front panel of Sepam 2000 (serial link).
(3)
capacitive or inductive
(4)
Sepam SX2.
(5)
typical accuracy with nominal values according to IEC 60255-6.
(6)
transfer of records to the front panel of Sepam 2000 using the SFT 2801 software program
and via Jbus/Modbus communication.
(7)
measurement accessed on the front panel of Sepam 2000 (serial link) and via the
communication system.
Reminder:
Rated current In, rated voltage Un and current Ino are general parameters that are set at the
time of Sepam 2000 commissioning.
In is the current sensor rated current (CT rating).
Ino is the core balance CT current rating.
Un is the phase-to-phase voltage of the voltage sensor primary windings.

Example of the processing of a disturbance recording record


using the PC SFT 2826 software program.

Sepam 2000 SX 5
Protection

Phase overcurrent (ANSI 50/51) F011 to F014*


Three-phase protection against phase-to-phase
Current sensor sizing
faults. The following types of time delay settings are The current sensors used should be such that they will not be saturated by the
available: definite, standard inverse,very inverse, current values which they are required to measure, with accuracy (at least 5 In):
extremely inverse or ultra inverse. c for definite time functions (DT):
1.5 times the setting current,
Earth fault (ANSI 50N/51N or 50G/51G) F081 to c for IDMT functions (SIT, VIT, EIT and UIT):
F084* 1.5 times the greatest working value in the curve.
The following types of time delay can be:
definite, standard inverse, very inverse, extremely
inverse or ultra inverse. Residual current detection
secondary CT. Power wiring resitance
can be provided by:
current and accuracy maximum wiring 2.5 VA power
c the three phase current transformers ;
class resistance increase
in this case, a harmonic 2 restraint is used to do away
with tripping triggered by transformer closing. by step of
c a current transformer (1 or 5 A), combined with a 1A 2.5 VA 5P 20 0.075 Ω 2.5 Ω
CSH 30 interposing ring CT, 5A 7.5 VA 5P 20 0.075 Ω 0.075 Ω
c a CSH 120 or CSH 200 core balance CT, according
to the required diameter,
this method being the most accurate one.
The two ratings available (2 and 30 A), provide a very
wide setting range.
c with another core balance CT, associated with the
ACE 990.

*Fxxx function identification used for protection setting.

Setting ranges
functions Fxxx(1) settings time delays
phase overcurrent F011-F012-F013-F014
definite time DT 0.3 to 24 In t: 0.05 to 655 s
(2)
IDMT 0.3 to 2.4 In t: 0.1 to 12.5 s at 10 Is
earth fault F081-F082-F083-F084 type of sensor
definite time DT 0.05 to 10 In sum of 3 phase currents t: 0.05 to 655 s
0.1 to 20 A CSH core bal. CT, 2 A
1.5 to 300 A CSH core bal. CT, 30 A
0.05 to 10 Ino 1 A or 5 A CT(3)
0.05 to 10 Ino core balance CT (4)
IDMT (2) 0.05 to 1 In sum of 3 phase currents t: 0.1 to 12.5 s at 10 Iso
standard inverse, very inverse, 0.1 to 2 A CSH core bal. CT, 2 A
extremely inverse, ultra inverse 1.5 to 30 A CSH core bal. CT, 30 A
0.05 to 1 Ino 1 A or 5 A CT(3)
0.05 to 1 Ino core balance CT (4)
harmonic 2 restraint taken yes
into account no

Reminder: rated current In, rated voltage Un and current Ino are general parameters that are set at the time of Sepam 2000 commissioning.
In is the current sensor rated current (CT rating).
Un is the phase-to-phase voltage of the voltage sensor primary windings.
Ino is the core balance CT current rating.
(1)
function identification for protection setting.
(2)
IDMT curves:
- inverse: SIT,
- very inverse: VIT,
- extremely inverse: EIT,
- ultra inverse: UIT,
- long time inverse: LTI.
(3)
with CSH30 interposing ring CT.
(4)
core balance CT with ratio 1/n (50 ≤ n ≤ 1500) with ACE 990 interface.

6 Sepam 2000 SX
Control and monitoring (1)

Open / close control Trip circuit supervision and discrepancy (ANSI 74)
Used to control breaking devices equipped Detects tripping (by shunt-trip coil) circuit faults.
with different types of opening and closing coils: Can be used when the Sepam 2000 and the tripping auxiliary power sources have
c circuit breaker with shunt-trip or undervoltage the same voltage rating.
release coil, If the equipment contains an undervoltage release coil only, the tripping circuit
c latching contactor with shunt-trip coil, is not supervised since it is fail-safe. This function can also detect position
Parameter setting via the TSM 2001 pocket terminal, information discrepancies (neither open nor closed or simultaneously open
or PC softwares (SFT 2801 or SFT 2821), allows the and closed) in the different control schemes.
logic to be adapted to suit the equipment being used The connection of inputs I1, I2 and trip output O1 on the ESB board must be done
(by default, the logic is adapted for control of a circuit according to § other connection schemes.
breaker with a shunt-trip coil).
Detection of plugged connectors (ANSI 74)
Lockout relay (ANSI 86) Indication on the display unit that one or more connectors are not plugged
Stores tripping orders (lockout) and requires user in (the detector itself must be connected: see connection schemes).
action to be put back into operation (reset).
Operation counter (2)
Inhibit closing (ANSI 69) Counts the number of closing operations made by the breaking device,
Inhibits the closing of the circuit breaker thereby facilitating equipment maintenance.
or the contactor according to operating conditions.
Phase fault trip counter (2)
Annunciation (ANSI 30) Counts the number of operations for which breaking performances were required,
Keeps the user informed by the display thereby facilitating equipment maintenance.
of messages.
Disturbance recording triggering
Logic discrimination (ANSI 68) Triggers recording of electrical signals and logical states by:
Enables quick, selective tripping of the phase c voluntary local or remote action,
overcurrent and earth fault protection relays, whether c instantaneous overcurrent and earth fault protections,
definite time (DT) or IDMT (standard inverse SIT, c protection tripping order.
very inverse VIT, extremely inverse EIT or ultra
inverse UIT). (1)
according to parameter setting.
(2)
The function triggers the transmission counter reading is via serial link on the front panel of Sepam 2000, and via Jbus/Modbus
of a "blocking input" signal whenever one communication.
of the protection settings is exceeded.
Blocking input signal transmission can be used by the
Sepam 2000 Logic discrimination function for
substation, alternator, transformer and busbar
connection applications.

Sepam 2000 SX 7
Control and monitoring (cont'd) (1)

Parameter setting
functions parameters
open/close control KP1 KP2
circuit breaker with shunt-trip coil 0 0
circuit breaker with undervoltage release coil 1 0
latching contactor with trippy by shunt-trip coil 0 1
inputs
I1 = closed, I2 = open KP3 = 0
I1 = closed, I2 = receipt of blocking input KP3 = 1
outputs
O1 = opening, O2 = closing KP4 = 0
O1 = opening, O2 = transmission of blocking input KP4 = 1
counters
reset to zero of operation counter KP19 = 1
reset to zero of phase fault trip counter KP20 = 1
remote setting
remote setting enable KP38 = 0
remote setting disable KP38 = 1
disturbance recording
inhibition KP50 = 1
automatic triggering KP51 = 1
manual triggering KP52 = 1
other
display of set up control scheme KP17 = 1
BI (blocking input) pilot wire test KP18 = 1

(1)
configuration according.

8 Sepam 2000 SX
Functional and connection schemes

SX1 type L1
L2
L3

CE40 1B
1
2
3
1A 4

4
2B ECM 50 ESB 4A 21
1
51 DPC 20
5 50N
2 51N 19
18
6 17
3 CDG
16
15
6 2A 14
5 DPC 13
CSH
4 12
3 O2
30 A 11
2 2A 10
1 9
8
O1
7
6
5
4
l2
3
2
l1
1

N.B.
Refer to the "other connection schemes"
section regarding other arrangements.
DPC: detection of plugged connectors.
CDG: watchdog.

c Correspondence between primary


and secondary connection (i.e.: P1, S1).
Compact S26LX Sepam 2000.

Sepam 2000 SX 9
Functional and connection schemes (cont'd)

SX2 type L1
L2
L3

3A 3U/Vo CE40 1B
8
7 DPC 1
6 2
5 3
4 1A 4
3
2
1

4
2B ECM 50 ESB 4A 21
1
51 DPC 20
5 50N
2 51N 19
18
6 17
3 CDG
16
15
6 2A 14
5 DPC 13
CSH
4 12
3 O2
30 A 11
2 2A 10
1 9
8
O1
7
6
5
4
l2
3
2
l1
1

N.B.
Refer to the "other connection schemes"
section regarding other arrangements.
DPC: detection of plugged connectors.
CDG: watchdog.

c Correspondance between primary


and secondary connection (i.e.: P1, S1).
Compact S26LT Sepam 2000.

10 Sepam 2000 SX
Other connection schemes

L1 L1
Phase voltage L2 L2
L3 L3

A 3U/Vo 8 A 3U/Vo
8
7 DPC 7 DPC
6 6
5 5
4 4
3 3
2 2
1 1

Connection of a voltage transformer V-connection of 2 voltage transformers


(does not allow residual voltage (does not allow residual voltage
to be measured). to be measured).

Phase and residual voltage L1


L2
L3

8 A 3U/Vo
7 DPC
6
5
4
3
2
1

Broken-delta connection of voltage transformers to measure residual voltage.

Sepam 2000 SX 11
Other connection schemes (cont'd)

Residual current L1 L2 L3
4
2B ECM
with CT 1A or 5A 1
5
A ECM
2 6
6 CSH30 5 DPC
P1 S2
4
3
3 30 A
P2 1
S1 2 2A
6 2A 1 CT + CSH30
CSH30 5 DPC
4 5 turns
3 30 A
2 2A
1 For connection of 1 A transformers make
CT+CSH30
5 turns at the CSH30 primary

with sensors other than CSH 120 and CSH 200. L1 L2 L3 2A ECM
6
5 DPC
ACE 990
* 4
3
1/n 2
1

50 ≤ n ≤ 1500 *
(*) The core balance CT-ACE990 and ACE990-Sepam 2000 connections depend on the
transformer ratio of the core balance CT and the current to be measured.

Phase current L1 L2 L3 L1 L2 L3

4
CCA 601 cable ECA
B ECM
L1
1
2L1 5
2
L2
2L2 6
L3
3
2L3

c Correspondance between primary


and secondary connection (i.e.: P1, S1). Connection of CSP specific sensors. Connection of 2 current transformers.

12 Sepam 2000 SX
Examples of connections (1)

ESB logic input and output boards

ESB A 21 ESB A 21 ESB A 21


DPC 20 DPC 20 DPC 20
19 19 19
18 18 18
17 17 17
CDG 16 CDG 16 CDG 16
15 15 15
14 14 14
13 13 13
12 12 12
O2 11 O2 11 O2 11
10 closing 10 closing 10 closing
9 stop 9 9
8 8 stop 8
O1 7 O1 7 O1 7
6 opening 6 opening 6 opening
5 5 5
4 4 4
l2 3 l2 3 l2 3 BI recept
2 2 2
l1 1 l1 1 l1 1

Tripping of a circuit breaker or latching contactor Tripping of a circuit breaker by an undervoltage Tripping of a circuit breaker or latching contactor
by a shunt-trip coil (2) (3). release coil. by a shunt-trip coil and receipt of a blocking
KP1 = 0 KP3 = 0 KP4 = 0 KP1 = 1 KP3 = 0 KP4 = 0 input.
KP1 = 0 KP3 = 1 KP4 = 0

ESB A 21 ESB A 21 ESB A 21


DPC 20 DPC 20 DPC 20
19 19 19
18 18 18
17 17 17
CDG 16 CDG 16 CDG 16
15 15 15
14 14 14
13 13 13
12 12 12
O2 11 BI transmission O2 11 BI transmission O2 11 BI transmission
10 10 10
9 stop 9 9
8 8 stop 8
O1 7 O1 7 O1 7
6 opening 6 opening 6 opening
5 5 5
4 4 4
l2 3 l2 3 l2 3 BI recept
2 2 2
l1 1 l1 1 l1 1

Tripping of a circuit breaker or latching contactor Tripping of a circuit breaker by an undervoltage Tripping of a circuit breaker or latching contactor
by a shunt-trip coil and transmission of a blocking release coil and transmission of a blocking input. by a shunt-trip coil and receipt of a blocking
input (2). KP1 = 1 KP3 = 0 KP4 = 1 input.
KP1 = 0 KP3 = 0 KP4 = 1 KP1 = 0 KP3 = 1 KP4 = 1

(1)
according to parameter setting.
(2)
with monitoring of trip circuit.
(3)
default parameter setting.
N.B. The inputs are potential-free and there is an external power supply source.
BI: Blocking input.

Sepam 2000 SX 13
Communication

Introduction
Sepam 2000 SX can communicate with a remote monitoring and control system,
equipped with a communication channel.
Several communication options are available:
c Jbus/Modbus master-slave protocol, RS 485 type physical link in 2-wire mode
(rate of 300 to 38400 bauds),
c FIPIO (please consult us),
c FIP ISIS (please consult us).

MERLIN GERIN

Sepam 2000 / remote


Sepam SX
monitoring and control
system communication.
communication table
remote indications address remote reading - remote setting
logic input status protection function curves, set points,
logic output status time delays, angles...

operation counter C1 control logic time delays

phase fault trip counter C2 remote control orders address

control fault: KTS1 “open” KTC33


tripping (or matching) (2) “close” KTC34
remote control open/close fault KTS2 fault acknowledgment (reset) KTC35
position/remote control KTS3 peak demand phase current KTC36
discrepancy zero reset (clear)
Sepam not reset (after fault) KTS5 peak demand W and VAr KTC37
device closed KTS10 zero reset (clear)

phase overcurrent KTS15 tripping current KTC38


zero reset (clear)
earth fault KTS16
inhibition disturbance recording KTC50
(2)
transmit "blocking input" KTS32
automatic disturbance KTC51
inhibited disturbance recording KTS50 recording triggering
remote setting disable KTS51 manual disturbance KTC52
remote measurements recording triggering
phase current The data above is available via the communication link.
peak demand phase currents The measurements available depend on the type of
Sepam 2000.
(1)
phase-to-phase and phase-to-neutral voltage (1)
related to Sepam 2000 SX2.
(2)
frequency (1) according to parameter setting.
(1)
real power
(1)
reactive power
(1)
peak demand real power
(1)
peak demand reactive power
(1)
power factor (P.f.)
(1)
inductive or capactive network
(1)
real energy
(1)
reactive energy
tripping currents
residual current
residual voltage
cumulative breaking current
number of trips

14 Sepam 2000 SX
Characteristics

Electrical characteristics
analog inputs
current transformer 1 A CT < 0.001 VA
10 A to 6250 A ratings 5 A CT < 0.025 VA
voltage transformer 100 to 120 V > 100 kΩ
220 V to 250 kV ratings
logic inputs
voltage 24/30 Vdc 48/127 Vdc 220/250 Vdc
consumption 4 mA 4 mA 3 mA
auxiliary power supply
DC voltage 24/30 Vdc 48/127 Vdc 220/250 Vdc
typical consumption 18 W 19.5 W 21 W
logic outputs (relays)
voltage 24/30 Vdc 48 Vdc 125 Vdc 220/250 Vdc
rated current 8A 8A 8A 8A
400 ms overload 15 A 15 A 15 A 15 A
making capacity 15 A 15 A 15 A 15 A
breaking capacity : DC with resistive load 8A 4A 0,8 A 0,3 A
DC at L/R = 20 ms 6A 2A 0.4 A 0.15 A
DC at L/R = 40 ms 4A 1A 0.2 A 0.1 A
AC with resistive load 8A 8A 8A 8A
AC with p.f. = 0.3 5A 5A 5A 5A

Environmental characteristics
electric insulation
(1)
dielectric withstand IEC 60255-5 2 kV - 1 mn
1.2/50 µs impulse wave withstand IEC 60255-5 5 kV (2)

climatic withstand
operation IEC 60068-2- 1 and 2 - 5 °C to + 55 °C
IEC 60068-2-14 - 5 °C to + 55 °C
storage IEC 60068-2 - 25 °C to + 70 °C
damp heat IEC 60068-2 -3 93% RH at 40 °C
56 days (storage)
10 days (operation)
corrosion influence IEC 60654-4 class I
mechanical robustness
degree of protection IEC 60529 IP 51 front face
vibrations IEC 60255-21-1 class I
shocks / jolts IEC 60255-21-2 class I
earthquakes IEC 60255-21-3 class I
fire resistance IEC 60695-2-1 glow wire
electromagnetic compatibility
radiated fields IEC 60255-22-3 class x 30 V/m
IEC 61000-4-3 class III 10 V/m
electrostatic discharge IEC 60255-22-2 class III
IEC 61000-4-2 class III
damped 1 MHz wave IEC 60255-22-1 class III
5 ns electrical fast transients/burst IEC 60255-22-4 class IV
IEC 61000-4-4 class IV
1.2/50µs - 8/20µs surge immunity IEC 61000-4-5 class III 2 kV differential mode (42 Ω)
1 kV common mode (42 Ω)
conducted disturbance emission EN 55022/CISPR22 class B with auxiliary
(3)
power supply
(4)
radiated field emission EN 55022/CISPR22 class B
“ ” marking on our product guarantees their conformity to European directives.
(1)
except for communication 1.4 kVdc and auxiliary power supply 2.8 kVdc
(2)
except for communication 3 kV common mode, 1 kV differential mode
(3)
EN 50081-1 generic standard
(4)
EN 50081-2 generic standard

Sepam 2000 SX 15
Installation

Dimensions and weights

mounting latches (x2)

222 201

e = 3 mm max

20 300

Compact Sepam (S26) Cut-out

222 202

264 250

Connections
type wiring / accessories type
cabling reference
current transformers screw for i 6 mm2 CCA 660 (1) connector
Ø4 eye lug
CSH core balance CTs, screw i 2.5 mm2 CCA 606 (1)
connector
CSH 30 and ACE 990 adapters
CSP sensors BNC connector CCA 601 cable: (length: 5.5 m)
with two BNC connectors
Sepam 2000 (S26)
rear face with standard voltage transformers screw i 2.5 mm2 CCA 608 (1)
connector
connectors. temperature probes screw i 2.5 mm2 CCA 621 (1)
connector
logic inputs/outputs screw i 2.5 mm2 CCA 621 (1)
connector
power supply screw i 2.5 mm2 CCA 604 (1)
connector
Jbus/Modbus 9-pin sub-D CCA 602 cable (length: 3 m)
communication connector with two 9-pin sub-D
CCA 619 9-pin sub-D
connector box
(1)
accessories supplied with Sepam 2000.

16 Sepam 2000 SX
Notes

Sepam 2000 SX 17
Notes

18 Sepam 2000 SX
Sepam 2000 SX 19
Ordering information

Sepam 2000
(1)
Sepam type ................................................................................................................................................................

quantity .........................................................................................................
(1)
example : SX1

Options
Communication ......................................................... without ...............................
..................................................................................... Jbus/Modbus .....................

Working language ..................................................... French ...............................


..................................................................................... English ..............................
..................................................................................... Spanish .............................
..................................................................................... Italian ................................

Current sensors ......................................................... 1 A/5 A CT .........................

Auxiliary power supply ............................................. 24/30 Vdc ..........................


..................................................................................... 48/127 Vdc ........................
..................................................................................... 220/250 Vdc ......................

Accessories quantity

Pocket terminal ............................................................ TSM 2001 .............


Setting softwares with PC connection kit .................... SFT 2801
+ SFT 2821 ..............

Core balance CTs ........................................................ CSH 120 ................


..................................................................................... CSH 200 ................

Interposing ring CT for residual


current input ................................................................. CSH 30 ..................
Adapter core balance CT ............................................ ACE 990 ................

Jbus/Modbus communication
c 9-pin sub-D connector box ....................................... CCA 619 ................
c Jbus/Modbus network connection box .................... CCA 609 ................
c cable (length: 3 m)
with two 9-pin sub-D connectors ................................. CCA 602 ................
c interfaces box RS485/RS232 ................................... ACE 909 ................

FIP communication (refer to Telemecanique documentation).

Schneider Electric Postal address As standards, specifications and designs change from This document has been
F-38050 Grenoble cedex 9 time to time, please ask for confirmation of the information printed on ecological paper.
Tel: 33 (0)4 76 57 60 60 given in this publication.
Telex: merge 320842 F
http://www.schneiderelectric.com
Publishing: Schneider Electric
Design, production: Idra
Rcs Nanterre B 954 503 439 Printing:
PCRED398026EN /1
ART.88637 12 / 1999

You might also like