PCRED398026EN1
PCRED398026EN1
and control
Sepam range
Sepam 2000 SX
Presentation
Contents page
presentation 2
selection table 3
metering 4
protection 6
control and monitoring 7
functional and connection schemes 9
other connection schemes 11
examples of connection schemes 13
communication 14
characteristics 15
installation 16
ordering information 20
Customization (1)
Standard control and monitoring carried out in Sepam 2000's internal PLC
can be customized. Sepam 2000 SX does not allow for extension of the logic
inputs and outputs. For applications which require more logic inputs/outputs,
use Sepam 2000 type S01 or S02.
(1)
Please refer to document Sepam 2000 customized
application.
2 Sepam 2000 SX
Selection table
The figures in the columns represent the number of similar protection devices.
For example, for phase overcurrent protection, “4” means: 4 separate overcurrent protection
devices.
(1)
according to parameter setting.
Sepam 2000 SX 3
Metering
Voltages (4)
Measurement of the circuit phase-to-phase and phase-to-neutral voltages.
Frequency (4)
Measurement of frequency (based on positive sequence voltage or the U21 voltage
input).
Tripping currents
Measurements of the 3 phase currents and the residual current that were stored
at the time that Sepam 2000 gave the tripping order. Used to find
the fault current (fault analysis) and assess the level of wear of the breaker
(maintenance assistance). The "clear" button is pressed for zero reset.
Disturbance recording
Recording of electrical signals and logical information before and after
a disturbance recorder triggering order is given.
4 Sepam 2000 SX
Measurements used Characteristics
for commissioning functions ranges accuracy (5)
Sepam 2000 SX 5
Protection
Setting ranges
functions Fxxx(1) settings time delays
phase overcurrent F011-F012-F013-F014
definite time DT 0.3 to 24 In t: 0.05 to 655 s
(2)
IDMT 0.3 to 2.4 In t: 0.1 to 12.5 s at 10 Is
earth fault F081-F082-F083-F084 type of sensor
definite time DT 0.05 to 10 In sum of 3 phase currents t: 0.05 to 655 s
0.1 to 20 A CSH core bal. CT, 2 A
1.5 to 300 A CSH core bal. CT, 30 A
0.05 to 10 Ino 1 A or 5 A CT(3)
0.05 to 10 Ino core balance CT (4)
IDMT (2) 0.05 to 1 In sum of 3 phase currents t: 0.1 to 12.5 s at 10 Iso
standard inverse, very inverse, 0.1 to 2 A CSH core bal. CT, 2 A
extremely inverse, ultra inverse 1.5 to 30 A CSH core bal. CT, 30 A
0.05 to 1 Ino 1 A or 5 A CT(3)
0.05 to 1 Ino core balance CT (4)
harmonic 2 restraint taken yes
into account no
Reminder: rated current In, rated voltage Un and current Ino are general parameters that are set at the time of Sepam 2000 commissioning.
In is the current sensor rated current (CT rating).
Un is the phase-to-phase voltage of the voltage sensor primary windings.
Ino is the core balance CT current rating.
(1)
function identification for protection setting.
(2)
IDMT curves:
- inverse: SIT,
- very inverse: VIT,
- extremely inverse: EIT,
- ultra inverse: UIT,
- long time inverse: LTI.
(3)
with CSH30 interposing ring CT.
(4)
core balance CT with ratio 1/n (50 ≤ n ≤ 1500) with ACE 990 interface.
6 Sepam 2000 SX
Control and monitoring (1)
Open / close control Trip circuit supervision and discrepancy (ANSI 74)
Used to control breaking devices equipped Detects tripping (by shunt-trip coil) circuit faults.
with different types of opening and closing coils: Can be used when the Sepam 2000 and the tripping auxiliary power sources have
c circuit breaker with shunt-trip or undervoltage the same voltage rating.
release coil, If the equipment contains an undervoltage release coil only, the tripping circuit
c latching contactor with shunt-trip coil, is not supervised since it is fail-safe. This function can also detect position
Parameter setting via the TSM 2001 pocket terminal, information discrepancies (neither open nor closed or simultaneously open
or PC softwares (SFT 2801 or SFT 2821), allows the and closed) in the different control schemes.
logic to be adapted to suit the equipment being used The connection of inputs I1, I2 and trip output O1 on the ESB board must be done
(by default, the logic is adapted for control of a circuit according to § other connection schemes.
breaker with a shunt-trip coil).
Detection of plugged connectors (ANSI 74)
Lockout relay (ANSI 86) Indication on the display unit that one or more connectors are not plugged
Stores tripping orders (lockout) and requires user in (the detector itself must be connected: see connection schemes).
action to be put back into operation (reset).
Operation counter (2)
Inhibit closing (ANSI 69) Counts the number of closing operations made by the breaking device,
Inhibits the closing of the circuit breaker thereby facilitating equipment maintenance.
or the contactor according to operating conditions.
Phase fault trip counter (2)
Annunciation (ANSI 30) Counts the number of operations for which breaking performances were required,
Keeps the user informed by the display thereby facilitating equipment maintenance.
of messages.
Disturbance recording triggering
Logic discrimination (ANSI 68) Triggers recording of electrical signals and logical states by:
Enables quick, selective tripping of the phase c voluntary local or remote action,
overcurrent and earth fault protection relays, whether c instantaneous overcurrent and earth fault protections,
definite time (DT) or IDMT (standard inverse SIT, c protection tripping order.
very inverse VIT, extremely inverse EIT or ultra
inverse UIT). (1)
according to parameter setting.
(2)
The function triggers the transmission counter reading is via serial link on the front panel of Sepam 2000, and via Jbus/Modbus
of a "blocking input" signal whenever one communication.
of the protection settings is exceeded.
Blocking input signal transmission can be used by the
Sepam 2000 Logic discrimination function for
substation, alternator, transformer and busbar
connection applications.
Sepam 2000 SX 7
Control and monitoring (cont'd) (1)
Parameter setting
functions parameters
open/close control KP1 KP2
circuit breaker with shunt-trip coil 0 0
circuit breaker with undervoltage release coil 1 0
latching contactor with trippy by shunt-trip coil 0 1
inputs
I1 = closed, I2 = open KP3 = 0
I1 = closed, I2 = receipt of blocking input KP3 = 1
outputs
O1 = opening, O2 = closing KP4 = 0
O1 = opening, O2 = transmission of blocking input KP4 = 1
counters
reset to zero of operation counter KP19 = 1
reset to zero of phase fault trip counter KP20 = 1
remote setting
remote setting enable KP38 = 0
remote setting disable KP38 = 1
disturbance recording
inhibition KP50 = 1
automatic triggering KP51 = 1
manual triggering KP52 = 1
other
display of set up control scheme KP17 = 1
BI (blocking input) pilot wire test KP18 = 1
(1)
configuration according.
8 Sepam 2000 SX
Functional and connection schemes
SX1 type L1
L2
L3
CE40 1B
1
2
3
1A 4
4
2B ECM 50 ESB 4A 21
1
51 DPC 20
5 50N
2 51N 19
18
6 17
3 CDG
16
15
6 2A 14
5 DPC 13
CSH
4 12
3 O2
30 A 11
2 2A 10
1 9
8
O1
7
6
5
4
l2
3
2
l1
1
N.B.
Refer to the "other connection schemes"
section regarding other arrangements.
DPC: detection of plugged connectors.
CDG: watchdog.
Sepam 2000 SX 9
Functional and connection schemes (cont'd)
SX2 type L1
L2
L3
3A 3U/Vo CE40 1B
8
7 DPC 1
6 2
5 3
4 1A 4
3
2
1
4
2B ECM 50 ESB 4A 21
1
51 DPC 20
5 50N
2 51N 19
18
6 17
3 CDG
16
15
6 2A 14
5 DPC 13
CSH
4 12
3 O2
30 A 11
2 2A 10
1 9
8
O1
7
6
5
4
l2
3
2
l1
1
N.B.
Refer to the "other connection schemes"
section regarding other arrangements.
DPC: detection of plugged connectors.
CDG: watchdog.
10 Sepam 2000 SX
Other connection schemes
L1 L1
Phase voltage L2 L2
L3 L3
A 3U/Vo 8 A 3U/Vo
8
7 DPC 7 DPC
6 6
5 5
4 4
3 3
2 2
1 1
8 A 3U/Vo
7 DPC
6
5
4
3
2
1
Sepam 2000 SX 11
Other connection schemes (cont'd)
Residual current L1 L2 L3
4
2B ECM
with CT 1A or 5A 1
5
A ECM
2 6
6 CSH30 5 DPC
P1 S2
4
3
3 30 A
P2 1
S1 2 2A
6 2A 1 CT + CSH30
CSH30 5 DPC
4 5 turns
3 30 A
2 2A
1 For connection of 1 A transformers make
CT+CSH30
5 turns at the CSH30 primary
with sensors other than CSH 120 and CSH 200. L1 L2 L3 2A ECM
6
5 DPC
ACE 990
* 4
3
1/n 2
1
50 ≤ n ≤ 1500 *
(*) The core balance CT-ACE990 and ACE990-Sepam 2000 connections depend on the
transformer ratio of the core balance CT and the current to be measured.
Phase current L1 L2 L3 L1 L2 L3
4
CCA 601 cable ECA
B ECM
L1
1
2L1 5
2
L2
2L2 6
L3
3
2L3
12 Sepam 2000 SX
Examples of connections (1)
Tripping of a circuit breaker or latching contactor Tripping of a circuit breaker by an undervoltage Tripping of a circuit breaker or latching contactor
by a shunt-trip coil (2) (3). release coil. by a shunt-trip coil and receipt of a blocking
KP1 = 0 KP3 = 0 KP4 = 0 KP1 = 1 KP3 = 0 KP4 = 0 input.
KP1 = 0 KP3 = 1 KP4 = 0
Tripping of a circuit breaker or latching contactor Tripping of a circuit breaker by an undervoltage Tripping of a circuit breaker or latching contactor
by a shunt-trip coil and transmission of a blocking release coil and transmission of a blocking input. by a shunt-trip coil and receipt of a blocking
input (2). KP1 = 1 KP3 = 0 KP4 = 1 input.
KP1 = 0 KP3 = 0 KP4 = 1 KP1 = 0 KP3 = 1 KP4 = 1
(1)
according to parameter setting.
(2)
with monitoring of trip circuit.
(3)
default parameter setting.
N.B. The inputs are potential-free and there is an external power supply source.
BI: Blocking input.
Sepam 2000 SX 13
Communication
Introduction
Sepam 2000 SX can communicate with a remote monitoring and control system,
equipped with a communication channel.
Several communication options are available:
c Jbus/Modbus master-slave protocol, RS 485 type physical link in 2-wire mode
(rate of 300 to 38400 bauds),
c FIPIO (please consult us),
c FIP ISIS (please consult us).
MERLIN GERIN
14 Sepam 2000 SX
Characteristics
Electrical characteristics
analog inputs
current transformer 1 A CT < 0.001 VA
10 A to 6250 A ratings 5 A CT < 0.025 VA
voltage transformer 100 to 120 V > 100 kΩ
220 V to 250 kV ratings
logic inputs
voltage 24/30 Vdc 48/127 Vdc 220/250 Vdc
consumption 4 mA 4 mA 3 mA
auxiliary power supply
DC voltage 24/30 Vdc 48/127 Vdc 220/250 Vdc
typical consumption 18 W 19.5 W 21 W
logic outputs (relays)
voltage 24/30 Vdc 48 Vdc 125 Vdc 220/250 Vdc
rated current 8A 8A 8A 8A
400 ms overload 15 A 15 A 15 A 15 A
making capacity 15 A 15 A 15 A 15 A
breaking capacity : DC with resistive load 8A 4A 0,8 A 0,3 A
DC at L/R = 20 ms 6A 2A 0.4 A 0.15 A
DC at L/R = 40 ms 4A 1A 0.2 A 0.1 A
AC with resistive load 8A 8A 8A 8A
AC with p.f. = 0.3 5A 5A 5A 5A
Environmental characteristics
electric insulation
(1)
dielectric withstand IEC 60255-5 2 kV - 1 mn
1.2/50 µs impulse wave withstand IEC 60255-5 5 kV (2)
climatic withstand
operation IEC 60068-2- 1 and 2 - 5 °C to + 55 °C
IEC 60068-2-14 - 5 °C to + 55 °C
storage IEC 60068-2 - 25 °C to + 70 °C
damp heat IEC 60068-2 -3 93% RH at 40 °C
56 days (storage)
10 days (operation)
corrosion influence IEC 60654-4 class I
mechanical robustness
degree of protection IEC 60529 IP 51 front face
vibrations IEC 60255-21-1 class I
shocks / jolts IEC 60255-21-2 class I
earthquakes IEC 60255-21-3 class I
fire resistance IEC 60695-2-1 glow wire
electromagnetic compatibility
radiated fields IEC 60255-22-3 class x 30 V/m
IEC 61000-4-3 class III 10 V/m
electrostatic discharge IEC 60255-22-2 class III
IEC 61000-4-2 class III
damped 1 MHz wave IEC 60255-22-1 class III
5 ns electrical fast transients/burst IEC 60255-22-4 class IV
IEC 61000-4-4 class IV
1.2/50µs - 8/20µs surge immunity IEC 61000-4-5 class III 2 kV differential mode (42 Ω)
1 kV common mode (42 Ω)
conducted disturbance emission EN 55022/CISPR22 class B with auxiliary
(3)
power supply
(4)
radiated field emission EN 55022/CISPR22 class B
“ ” marking on our product guarantees their conformity to European directives.
(1)
except for communication 1.4 kVdc and auxiliary power supply 2.8 kVdc
(2)
except for communication 3 kV common mode, 1 kV differential mode
(3)
EN 50081-1 generic standard
(4)
EN 50081-2 generic standard
Sepam 2000 SX 15
Installation
222 201
e = 3 mm max
20 300
222 202
264 250
Connections
type wiring / accessories type
cabling reference
current transformers screw for i 6 mm2 CCA 660 (1) connector
Ø4 eye lug
CSH core balance CTs, screw i 2.5 mm2 CCA 606 (1)
connector
CSH 30 and ACE 990 adapters
CSP sensors BNC connector CCA 601 cable: (length: 5.5 m)
with two BNC connectors
Sepam 2000 (S26)
rear face with standard voltage transformers screw i 2.5 mm2 CCA 608 (1)
connector
connectors. temperature probes screw i 2.5 mm2 CCA 621 (1)
connector
logic inputs/outputs screw i 2.5 mm2 CCA 621 (1)
connector
power supply screw i 2.5 mm2 CCA 604 (1)
connector
Jbus/Modbus 9-pin sub-D CCA 602 cable (length: 3 m)
communication connector with two 9-pin sub-D
CCA 619 9-pin sub-D
connector box
(1)
accessories supplied with Sepam 2000.
16 Sepam 2000 SX
Notes
Sepam 2000 SX 17
Notes
18 Sepam 2000 SX
Sepam 2000 SX 19
Ordering information
Sepam 2000
(1)
Sepam type ................................................................................................................................................................
quantity .........................................................................................................
(1)
example : SX1
Options
Communication ......................................................... without ...............................
..................................................................................... Jbus/Modbus .....................
Accessories quantity
Jbus/Modbus communication
c 9-pin sub-D connector box ....................................... CCA 619 ................
c Jbus/Modbus network connection box .................... CCA 609 ................
c cable (length: 3 m)
with two 9-pin sub-D connectors ................................. CCA 602 ................
c interfaces box RS485/RS232 ................................... ACE 909 ................
Schneider Electric Postal address As standards, specifications and designs change from This document has been
F-38050 Grenoble cedex 9 time to time, please ask for confirmation of the information printed on ecological paper.
Tel: 33 (0)4 76 57 60 60 given in this publication.
Telex: merge 320842 F
http://www.schneiderelectric.com
Publishing: Schneider Electric
Design, production: Idra
Rcs Nanterre B 954 503 439 Printing:
PCRED398026EN /1
ART.88637 12 / 1999