This document provides information on sub-feeders for two unit feeders, including motor loads, wire sizes, conduit sizes and circuit breakers. For each sub-feeder, it lists the number of motors or other loads, horsepower rating, voltage, full load amps, required wire and conduit sizes, and recommended circuit breaker sizes. A total of 50 sub-feeders are specified across the two unit feeders.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
186 views4 pages
Unit-1, Feeder-1 Sub-Feeders
This document provides information on sub-feeders for two unit feeders, including motor loads, wire sizes, conduit sizes and circuit breakers. For each sub-feeder, it lists the number of motors or other loads, horsepower rating, voltage, full load amps, required wire and conduit sizes, and recommended circuit breaker sizes. A total of 50 sub-feeders are specified across the two unit feeders.
SUB- MOTOR LOAD WIRES mm2 CONDUIT CIRCUIT BREAKER FEEDER OTHERS RATING VOLTS FLA(3φ) FEEDER NUMBER DRIVES THHN (5KV) (mm φ RSC) (5KV) LIGHT, I 329.3 kV 230 v 826.58 3 – 80 50 900 , 1000 ETC. 3 – 38 II 11 30HP 380 V 40 A 40 125 AT, 225 AF 1 – 22 380 V 40 A 3 – 38 III 9 30 HP 40 125 AT, 225 AF 1 – 22 380 V 40 A 3 – 38 IV 7 30 HP 40 125 AT, 225 AF 1 – 22 380 V 3 – 80 V 5 50 HP 65 A 50 175 AT, 225 AF 1 – 50 380 V 65 A 3 – 80 VI 3 50 HP 50 175 AT, 225 AF 1 – 50 380 V 65 A 3 – 80 VII 1 50 HP 50 175 AT, 225 AF 1 – 50
UNIT-2 MAIN FEEDERS
SUB- MOTOR LOAD WIRES mm2 CONDUIT CIRCUIT BREAKER FEEDER OTHERS RATING VOLTS FLA(3φ) FEEDER NUMBER DRIVES THHN (5KV) (mm φ RSC) (5KV) LIGHT, I 320.7 kV 230 805.02 3 – 80 50 900, 1000 ETC. 3 – 38 II 12 30HP 380 V 40 A 40 125 AT, 225 AF 1 – 22 380 V 40 A 3 – 38 III 10 30 HP 40 125 AT, 225 AF 1 – 22 380 V 40 A 3 – 38 IV 8 30 HP 40 125 AT, 225 AF 1 – 22 380 V 3 – 80 V 6 50 HP 65 A 50 175 AT, 225 AF 1 – 50 380 V 65 A 3 – 80 VI 4 50 HP 50 175 AT, 225 AF 1 – 50 380 V 65 A 3 – 80 VII 2 50 HP 50 175 AT, 225 AF 1 – 50