The document provides specifications for 25kVA and 50kVA distribution transformers used in Ethiopia's power engineering industry. It lists over 40 technical requirements and parameters for pole mounted transformers including ratings, winding materials, cooling methods, efficiency levels, temperature limits, losses, bushings specifications, and testing procedures. Manufacturers must meet standards from the IEC and provide detailed drawings and test results to qualify for use on Ethiopia's 33kV distribution network.

Uploaded by

G/eyesus 27/16
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
152 views

33kv Transformer PDF

The document provides specifications for 25kVA and 50kVA distribution transformers used in Ethiopia's power engineering industry. It lists over 40 technical requirements and parameters for pole mounted transformers including ratings, winding materials, cooling methods, efficiency levels, temperature limits, losses, bushings specifications, and testing procedures. Manufacturers must meet standards from the IEC and provide detailed drawings and test results to qualify for use on Ethiopia's 33kV distribution network.

Uploaded by

G/eyesus 27/16
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 37

ETHIOPIA POWER ENGINEERING INDUSTRY

Pole mount transformer


New specification for 33KV transformer
Operation ppc
7/11/2019
1. Guaranteed Technical Particulars for 25KVA (33/0.4) KV
Distribution Transformer.
No Item Unit Requirement Bid Offer

General
1 Manufacturer

2 Country of manufacture

3 Kind of installation Out-door


Pole mounted
4 Equipment Standard IEC 60076
5 No. of phases three-phase
6 Type of tank Bolted Cover
7 No. of windings Two
8 Vector group symbol Dyn5
9 Tapping range 2.5
10 Number of steps ± steps
11 Maximum Height above sea level at meters 3000
which tests are performed,
12 Cooling method ONAN
13 Specification of oil) IEC 60296
13.1 Ratings
14 Rated power kVA 25
15 Nominal system voltage
15.1 primary UNI 33
15.2 secondary UN2 0.4
16 Frequency 50
17 Principal tapping 33
18.1 Maximum Continuous System kV 36
withstand Voltage
18.2 Rated Voltage of the equipment kv 52
19 Impedance voltage at rated power 4
No Item Unit Requirement Bid Offer

20 HV Windings
20.1 Material, wire or strip Copper wire/strip

20.2 Insulation
20.3 Power frequency withstand voltage kV(rms) 70
20.4 Rated lightning, impulse withstand kV(peak) 170
voltage
21 LV Windings
21.1 Material, wire or strip Copper wire/strip

21.2 Insulation
21.3 Power frequency withstand voltage kV(rms) 3

21.4 Rated lightning, impulse withstand kV(peak)


voltage
21.5 Magnetic flux density (at rated Tesla 1.7
voltage and frequency)
22 Core Material CRGO
22.1 Core Loss figure, Watt/kg
22.2 Ill. Operation Details
23 Ambient temperature (max.) 45
24 Ambient temperature (average) 30
25 Temperature rise limit (at 3000 m )
25.1 oil / top 55
25.2 windings / average 60
25.3 windings hot spot 68
26 No-load loss at rated voltage and kW <0.0805
frequency
27 Full load loss ,W kW <0.99
28 Rated voltage at full load (P.F=0.95)
29 Efficiency referred to 75 0C at rated
voltage and frequency
No ltem Unit Requurement Bid Offer

29.1 100% rated output and P.F= 1 (0/0)


29.2 100% rated output and P.F= 0.95 (0/0)
30 No load current as percent of rated
current
30.1 at 90% voltage (0/0)
30.2 at 100% voltage (0/0)
Bushings
31 Primary
31.1 Manufacturer
31.2 rated current 630
31.3 power frequency test level 95
31.4 lightning impulse level 250
31.5 clearance across insulator (at 3000m) mm 480
31.6 adjustable arcing horns yes/no Yes
31.7 creep age distance >1080

31.8 Specification for creepage distance IEC 60815-2/2008

32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 rated current
32.4 power frequency test level kV ,min 3
32.5 lightning impulse test
32.6 clearance across insulator 60
32.7 creep age distance
Tests
33 Routine tests: IEC 60076 and on each unit
Specifications
34 Separate source over-voltage on each unit
withstand test
No Item Requirement BidOffer

35 Induced over voltage withstand test, on each unit


36 test voltage / primary (tap 1) (IEC Yes
test standard)
37 test voltage / secondary (IEC test Yes
standard)
38 Type tests: IEC 60076 and on one unit
Specifications
39 test voltage / full wave (IEC test Yes
standard)
40 test voltage / chopped wave (IEC test Yes
standard)
41 Heat-run test on one unit
42 Noise level at a measuring distance dB (A)
of 0.3meter
VI. Materials, Masses, Measures and
Drawings
43 Transformer tank, material Steel
43.1 Transformer total mass kg
43.2 Overall dimensions including
bushings:
43.3 Height mm
43.4 Depth mm
43.5 Width mm
43.6 Thickness of tank plate
43.7 Top mm
43.8 Bottom
43.9 Sides
43.1 Colour of transformer Grey
43.1 Thickness of surface treatment 140
44 Drawing of dimensions No.
45 Pamphlet No.
2. GUARANTEED TECHNICAL PARTICULARS FOR 50KVA (33/0.4)
KV DISTRIBUTIONTRANSFORMER.

No Item Unit Requirement Bid


Offer
General
1 Manufacturer

2 Country of manufacture

3 Kind of installation Out-door


Pole mounted
4 Equipment Standard IEC 60076
5 No. of phases three-phase
6 Type of tank Bolted Cover
7 No. of windings Two
8 Vector group symbol Dyn5
9 Tapping range 2.5
10 Number of steps ± steps
11 height above sea level the tests are 3000
performed , in meter
12 Cooling method ONAN
13 Specification of oil IEC 60296
11. Ratings
14 Rated power kVA 50
15 Rated system voltage
15.1 primary UN 1 33
15.2 secondary UN2 0.4
16 Frequency 50
17 Principal tapping 33
18.1 Maximum Continuous System 36
withstand Voltage
18.2 Rated Voltage of the equipment 52
19 Impedance voltage at rated power 4
No Item Unit Requirement Bid Offer

20 HV Windings
20.1 Material, wire or strip Copper wire/strip

20.2 Insulation
20.3 Power frequency withstand voltage kV(rms) 70
20.4 Rated lightning, impulse withstand kV(peak) 170
voltage
21 LV Windings
21.1 Material, wire or strip Copper wire/strip

21.2 Insulation
21.3 Power frequency withstand voltage kV(rms) 3

21.4 Rated lightning, impulse withstand kV(peak)


voltage
21.5 Magnetic flux density (at rated Tesla 1.7
voltage and frequency)
22 Core Material CRGO
22.1 Core Loss figure, Watt/kg
Ill. Operation Details
23 Ambient temperature (max.) 45
24 Ambient temperature (average) 30
25 Temperature rise limit (at 3000 m )
25.1 oil / top 55
25.2 windings / average 60
25.3 windings hot spot 68
26 No-load loss at rated voltage and kW <1.035
frequency
27 Full load loss ,W kW <1.21
28 Rated voltage at full load (P.F=0.95)
29 Efficiency referred to 75 0C at rated
voltage and frequency
Item, Unit Requirement Bid Offer

29.1 100% rated output and P.F= 1 (0/0)


29.2 100% rated output and P.F= 0.95 (0/0)
30 No load current as percent of rated
current

30.1 at 90% voltage (0/0)


30.2 at 100% voltage (0/0)
Bushings
31 Primary
31.1 Manufacturer
31.2 rated current 630
31.3 power frequency test level 95
31.4 lightning impulse level 250
31.5 clearance across insulator mm 480
31.6 adjustable arcing horns yes/no Yes
creep age distance >1080

31.8 Specification of creepage distance IEC 60815-2/2008

32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 rated current
power frequency test min. 3
32.5 lightning impulse level (at 3000 m)
32.6 clearance across insulator 60
32.7 Min. creep age distance mm

V. Tests
33 Routine tests: IEC 60076 and on each unit
Specifications
34 Separate source over-voltage on each unit
Item Unit Requirement Bid Offer

withstand test
35 Induced over voltage withstand test, on each unit
36 test voltage / primary (tap 1) (IEC Yes
test standard)
37 test voltage / secondary (IEC test Yes
standard)
38 Type tests: IEC 60076 and on one unit
Specifications
39 test voltage / full wave (IEC test Yes
standard)
40 test voltage / chopped wave (IEC test Yes
standard)
41 Heat-run test on one unit
42 Noise level at a measuring distance dB(A)
of 0.3 meter
VI. Materials, Masses, Measures
and Drawings
43 Transformer tank, material Steel
43.1 Transformer total mass kg
43.2 Overall dimensions including
bushings:
43.3 Height mm
43.4 Depth mm
43.5 Width
43.6 Thickness of tank plate
43.7 Top mm
43.8 Bottom mm
43.9 Sides mm
43.1 Colour of transformer Grey
43.1 Thickness of surface treatment 140
44 Drawing of dimensions No.
45 Pamphlet No.
3. GUARANTEED TECHNICAL PARTICULARS FOR 100KVA(33/0.4)
KV DISTRIBUTION TRANSFORMER
No Item Unit Requirement Bid Offer

1. General
1 Manufacturer

2 Country of manufacture

3 Kind of installation Out door


Pole mounted
4 Equipment Standard IEC 60076
5 No. of phases three-phase
6 Type of tank Bolted Cover
7 No. of windings Two
8 Vector group symbol Dyn5
9 Tapping range 2.5
10 Number of steps ± steps
11 (maximum),height above sea level 3000
Meter
12 Cooling method ONAN
13 Specification of oil) IEC 60296
11. Ratings
14 Rated power kVA 100
15 Rated system voltage
15.1 primary UNI kv 33
15.2 secondary UN2 kV 0.4
16 Frequency 50
17 Principal tapping kV 33
18.1 Maximum Continuous System 36
withstand Voltage
18.2 Rated Voltage of the equipment 52
No Item Requirement Bid Offer

19 Impedance voltage at rated power 4


20 HV Windings
20.1 Material, wire or strip Copper wire/strip

20.2 Insulation
20.3 Power frequency withstand voltage kV(rms) 70
20.4 Rated lightning, impulse withstand kV(peak) 170
voltage
21 LV Windings
21.1 Material, wire or strip Copper wire/strip

21.2 Insulation
21.3 Power frequency withstand voltage kV(rms) 3

21.4 Rated lightning, impulse withstand kV(peak)


voltage
21.5 Magnetic flux density (at rated Tesla 1.7
voltage and frequency)
22 Core Material CRGO
22.1 Core Loss figure, Watt/kg
Ill. Operation Details
23 Ambient temperature (max.) 45
24 Ambient temperature (average) 30
25 Temperature rise limit (at 3000 m )
25.1 oil / top 55
25.2 windings / average 60
25.3 windings hot spot 68
26 No-load loss at rated voltage and kW <0.16675
frequency
27 Full load loss ,W kW <1.925
28 Rated voltage at full load (P.F=0.95)
Item Unit Requirement Bid Offer
0
29
Efficiency referred to 75 C at rated
voltage and frequency
29.1 100% rated output and P.F= 1 (0/0)
29.2 100% rated output and P.F= 0.95
(0/0)
30 No load current as percent of rated
current
30.1 at 90% voltage (0/0)
30.2 at 100% voltage (0/0)
Bushings
31 Primary
31.1 Manufacturer
31.2 rated current 630
31.3 power frequency test 95
lightning impulse test 250
31.5 clearance across insulator (at 3000m) Mm 480
31.6 adjustable arcing horns yes/no Yes
creep age distance Mm >1080

31.8 Specification of creepage distance IEC 60815-2/2008

32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 rated current
32.4 power frequency test min. 3
32.5 lightning impulse test
32.6 clearance across insulator 60
32.7 Min. creep age distance

v. Tests
No Item Unit Requirement Bid Offer

33 Routine tests: IEC 60076 and on each unit


Specifications
34 Separate source over-voltage on each unit
withstand test
35 Induced over voltage withstand test, on each unit
36 test voltage / primary (tap 1) (IEC Yes
test standard)
37 test voltage / secondary (IEC test kV Yes
standard)
38 Type tests: IEC 60076 and on one unit
Specifications
39 test voltage / full wave (IEC test kV Yes
standard)
40 test voltage / chopped wave (IEC test Yes
standard)
41 Heat-run test on one unit
42 Noise level at a measuring distance dB(A)
of 0.3meter
VI. Materials, Masses, Measures
and Drawings
43 Transformer tank, material Steel
43.1 Transformer total mass kg
43.2 Overall dimensions including
bushings:
43.3 Height
43.4 Depth
43.5 Width mm
43.6 Thickness of tank plate
43.7 Top mm
43.8 Bottom mm
Sides mm
43.1 Colour of transformer Grey
43.1 Thickness of surface treatment um 140
44 Drawing of dimensions No.
45 Pamphlet No.
4. GUARANTEED TECHNICAL PARTICULARS FOR 200KVA
(33/0.4) KV DISTRIBUTIONTRANSFORMER.

No Item Unit Requirement Bid Offer

1. General
1 Manufacturer

2 Country of manufacture

3 Kind of installation Out door


Pole mounted
4 Equipment Standard IEC 60076
5 No. of phases three-phase
6 Type of tank Bolted Cover
7 No. of windings Two
8 Vector group symbol Dyn5
9 Tapping range 2.5
10 Number of steps ± steps
11 height above sea level the tests are 3000
performed in meter

12 Cooling method ONAN


13 Specification of oil) IEC 60296
11. Ratings
14 Rated power kVA 200
15 Nominal system voltage
15.1 primary UN 1 33
15.2 secondary UN2 0.4
16 Frequency 50
17 Principal tapping 33
18.1 Maximum Continuous System 36
withstand Voltage
18.2 Rated Voltage of the equipment 52
No Item Unit Requirement Bid Offer

19 Impedance voltage at rated power 4


20 HV Windings
20.1 Material, wire or strip Copper wire/strip

20.2 Insulation
20.3 Power frequency withstand voltage kV (rms) 70
20.4 Rated lightning, impulse withstand kV (peak) 170
voltage
21 LV Windings
21.1 Material, wire or strip Copper wire/strip

21.2 Insulation
21.3 Power frequency withstand voltage kV(rms) 3

21.4 Rated lightning, impulse withstand kV(peak)


voltage
21.5 Magnetic flux density (at rated Tesla 1.7
voltage and frequency)
22 Core Material CRGO
22.1 Core Loss figure, Watt/kg
Ill. Operation Details
23 Ambient temperature (max.) 45
Ambient temperature (average) 30
25 Temperature rise limit (at 3000 m )
25.1 oil / top 55
25.2 windings / average 60
25.3 windings hot spot 68
26 No-load loss at rated voltage and kW <0.2875
frequency
27 Full load loss ,W kW <3.08
28 Rated voltage at full load (P.F=0.95)
No Item Unit Requirement Bid Offer

29 Efficiency referred to 75 0C at rated


voltage and frequency
29.1 100% rated output and P.F= 1 (0/0)
29.2 100% rated output and P.F= 0.95
(0/0)
30 No load current as percent of rated
current
30.1 at 90% voltage (0/0)
30.2 at 100% voltage (0/0)
Bushings
31 Primary
31.1 Manufacturer
31.2 rated current 630
31.3 power frequency test level 95
31.4 lightning impulse level kV 250
31.5 clearance across insulator (at 1000m) mm 480
31.6 adjustable arcing horns yes/no Yes
31.7 creep age distance >1080

31.8 Specification of creepage distance IEC 60815-2/2008


32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 rated current
32.4 power frequency test min. 3
32.5 lightning impulse test
32.6 clearance across insulator 60
32.7 Minimum creep age distance
V. Tests
33 Routine tests: IEC 60076 and on each unit
Specifications
No Item Unit Requirement Bid Offer

34 Separate source over-voltage on each unit


withstand test
35 Induced over voltage withstand test, on each unit
36 test voltage / primary (tap 1) (IEC kV Yes
test standard)
37 test voltage / secondary (IEC test Yes
standard)
38 Type tests: IEC 60076 and on one unit
Specifications
39 test voltage / full wave (IEC test kV Yes
standard)
40 test voltage / chopped wave (IEC test kV Yes
standard)
41 Heat-run test on one unit
42 Noise level at a measuring distance dB (A)
of 0.3 meter
VI. Materials, Masses, Measures
and Drawings
43 Transformer tank, material Steel
43.1 Transformer total mass kg
43.2 Overall dimensions including
bushings:
43.3 Height
43.4 Depth mm
43.5 Width
43.6 Thickness of tank plate
43.7 Top
43.8 Bottom
43.9 Sides
43.1 Colour of transformer Grey
43.1 Thickness of surface treatment 140
44 Drawing of dimensions No.
45 Pamphlet No.
5. GUARANTEED TECHNICAL PARTICULARS FOR 315KVA
(33/0.4) KV DISTRIBUTIONTRANSFORMER.

No Item Unit Requirement Bid Offer

1. General
1 Manufacturer

2 Country of manufacture

3 Kind of installation Out door


Pole mounted
4 Equipment Standard IEC 60076
5 No. of phases three-phase
6 Type of tank Bolted Cover
7 No. of windings Two
8 Vector group symbol Dyn5
9 Tapping range 2.5
10 Number of steps ± steps
11 height above sea level the tests are 3000
performed in meter

12 Cooling method ONAN


13 Specification of oil) IEC 60296
11. Ratings
14 Rated power kVA 315
15 Rated system voltage
15.1 primary UNI 33
15.2 secondary UN2 0.4
16 Frequency Hz 50
17 Principal tapping 33
18.1 Maximum Continuous System 36
withstand Voltage
18.2 Rated Voltage of the equipment kV 52
Item Unit Requirement 'Bid Offer

19 Impedance voltage at rated power 4


20 HV Windings
20.1 Material, wire or strip Copper wire/strip

20.2 Insulation
20.3 Power frequency withstand voltage kV(rms) 70
20.4 Rated lightning, impulse withstand kV(peak) 170
voltage
21 LV Windings
21.1 Material, wire or strip Copper wire/strip

21.2 Insulation
21.3 Power frequency withstand voltage kV(rms) 3

21.4 Rated lightning, impulse withstand kV(peak)


voltage
21.5 Magnetic flux density (at rated Tesla 1.7
voltage and frequency)
22 Core Material CRGO
22.1 Core Loss figure, Watt/kg
Ill. Operation Details
23 Ambient temperature (max.) 45
24 Ambient temperature (average) 30
25 Temperature rise limit (at 3000 m )
25.1 oil / top 55
25.2 windings / average 60
25.3 windings hot spot 68
26 No-load loss at rated voltage and kW <0.414
frequency
27 Full load loss ,W kW <4.29
28 Rated voltage at full load (P.F=0.95)
No Item Unit Requirement Bid Offers
29 Efficiency referred to 75 0C at rated
voltage and frequency
29.1 100% rated output and P.F= 1 (0/0)
29.2 100% rated output and P.F= 0.95 (0/0)
30 No load current as percent of rated
current
30.1 at 90% voltage (0/0)
30.2 at 100% voltage (0/0)
Bushings
31 Primary
31.1 Manufacturer
31.2 rated current 630
31.3 power frequency test level 95
31.4 lightning impulse level 250
31.5 clearance across insulator (at 1000m) mm 480
31.6 adjustable arcing horns yes/no Yes
creep age distance >1080

31.8 Specification for creepage distance IEC 60815-2/2008

32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 rated current
32.4 power frequency test I min. 3
32.5 lightning impulse test
32.6 clearance across insulator 60
32.7 Min. creep age distance
V. Tests
33 Routine tests: IEC 60076 and on each unit
No Item Unit Requirement Bid Offer

Specifications
34 Separate source over-voltage on each unit
withstand test
35 Induced over voltage withstand test, on each unit
36 test voltage / primary (tap 1) (IEC test Yes
standard)
37 test voltage / secondary (IEC test kV Yes
standard)
38 Type tests: IEC 60076 and on one unit
Specifications
39 test voltage / full wave (IEC test kV Yes
standard)
40 test voltage / chopped wave (IEC test Yes
standard)
41 Heat-run test on one unit
42 Noise level at a measuring distance of dB(A)
0.3meter
VI. Materials, Masses, Measures
and Drawings
43 Transformer tank, material Steel
43.1 Transformer total mass kg
43.2 Overall dimensions including
bushings:
43.3 Height
43.4 Depth
43.5 Width
43.6 Thickness of tank plate
43.7 Top
43.8 Bottom mm
43.9 Sides
43.1 Colour of transformer Grey
43.1 Thickness of surface treatment 140
44 Drawing of dimensions No.
45 Pamphlet No.
6. GUARANTEED TECHNICAL PARTICULARS FOR 400KVA
(33/0.4) KV DISTRIBUTIONTRANSFORMER.

No Item Unit Requirement Bid Offer

1. General
1 Manufacturer

2 Country of manufacture

3 Kind of installation Indoor, Ground


Mounted
4 Equipment Standard IEC 60076
5 No. of phases three-phase
6 Type of tank Bolted Cover
7 No. of windings Two
8 Vector group symbol Dyn5
9 Tapping range 2.5
10 Number of steps ± steps
11 Maximum height above sea level in Meters 3000
which the tests are performed
12 Cooling method ONAN
13 Specification of oil) IEC 60296
11. Ratings
14 Rated power kVA 400
15 Nominal system voltage
15.1 primary UNI 33
15.2 secondary UN2 0.4
16 Frequency 50
17 Principal tapping kV 33
18.1 Maximum Continuous System 36
withstand Voltage
18.2 Rated Voltage of the equipment kV 52
19 Impedance voltage at rated power 4
Item Unit Rèquirement Bid Offer

20 HV Windings
20.1 Material, wire or strip Copper wire/strip

20.2 Insulation
20.3 Power frequency withstand voltage kV(rms) 70
20.4 Rated lightning, impulse withstand kV(peak) 170
voltage
21 LV Windings
21.1 Material, wire or strip Copper wire/strip

21.2 Insulation
21.3 Power frequency withstand voltage kV(rms) 3

21.4 Rated lightning, impulse withstand kV(peak)


voltage
21.5 Magnetic flux density (at rated Tesla 1.7
voltage and frequency)
22 Core Material CRGO
22.1 Core Loss figure, Watt/kg
Ill. Operation Details
23 Ambient temperature (max.) 45
24 Ambient temperature (average) 30
25 Temperature rise limit (at 3000 m )
25.1 oil / top 55
25.2 windings / average 60
25.3 windings hot spot 68
26 No-load loss at rated voltage and kW <0.4945
frequency
27 Full load loss ,W kW <5.06
28 Rated voltage at full load (P.F=0.95)
29 Efficiency referred to 75 0C at rated
voltage and frequency
No Item Unit Requirement Bid Offer

29.1 100% rated output and P.F= 1 (0/0)


29.2 100% rated output and P.F= 0.95
(0/0)
30 No load current as percent of rated
current
30.1 at 90% voltage (0/0)
30.2 at 100% voltage (0/0)
Bushings
31 Primary
31.1 Manufacturer
31.2 rated current 630
31.3 power frequency test kV 95
31.4 lightning impulse test kV 250
31.5 clearance across insulator (at 3000m) mm 480
31.6 adjustable arcing horns yes/no Yes
31.7 creep age distance mm >1080

31.8 Specification of creepage distance IEC 60815-2/2008


32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 rated current
32.4 power frequency test kV min. 3
32.5 lightning impulse test
32.6 clearance across insulator 60
32.7 Min. creep age distance
V. Tests
33 Routine tests: IEC 60076 and on each unit
Specifications
34 Separate source over-voltage on each unit
withstand test
No Item Unit Requirement Bid Offer

35 Induced over voltage withstand test, on each unit


36 test voltage / primary (tap 1) (IEC Yes
test standard)
37 test voltage / secondary (IEC test Yes
standard)
38 Type tests: IEC 60076 and on one unit
Specifications
39 test voltage / full wave (IEC test kV Yes
standard)
40 test voltage / chopped wave (IEC test kV Yes
standard)
41 Heat-run test on one unit
42 Noise level at a measuring distance dB(A)
of 0.3meter
VI. Materials, Masses, Measures
and Drawings
43 Transformer tank, material Steel
43.1 Transformer total mass kg
43.2 Overall dimensions including
bushings:
43.3 Height
43.4 Depth
43.5 Width mm
43.6 Thickness of tank plate
43.7 Top
43.8 Bottom
43.9 Sides
43.1 Colour of transformer Grey
43.1 Thickness of surface treatment 140
44 Drawing of dimensions No.
45 Pamphlet No.
7. GUARANTEED TECHNICAL PARTICULARS FOR 500KVA
(33/0.4) KV DISTRIBUTIONTRANSFORMER.

No Item Unit Requirement Bid Offer

1. General
1 Manufacturer

2 Country of manufacture

3 Kind of installation
Indoor, Ground Mounted
4 Equipment Standard IEC 60076
5 No. of phases three-phase
6 Type of tank Bolted Cover
7 No. of windings Two
8 Vector group symbol Dyn5
9 Tapping range 2.5
10 Number of steps ± steps
11 Maximum height above sea level at meters 3000
which the tests are performed
12 Cooling method ONAN
13 Specification of oil) IEC 60296
11. Ratings
14 Rated power kVA 500
15 Rated system voltage
15.1 primary UNI kV 33
15.2 secondary UN2 kV 0.4
16 Frequency 50
17 Principal tapping kV 33
18.1 Maximum Continuous System 36
withstand Voltage
18.2 Rated Voltage of the equipment kV 52
19 Impedance voltage at rated power 4
No Unit Requirement id Offer

20 HV Windings
20.1 Material, wire or strip Copper wire/strip

20.2 Insulation
20.3 Power frequency withstand voltage kV(rms) 70
20.4 Rated lightning, impulse withstand kV(peak) 170
voltage
21 LV Windings
21.1 Material, wire or strip Copper wire/strip

21.2 Insulation
21.3 Power frequency withstand voltage kV(rms) 3

21.4 Rated lightning, impulse withstand kV(peak)


voltage
21.5 Magnetic flux density (at rated Tesla 1.7
voltage and frequency)
22 Core Material CRGO
22.1 Core Loss figure, Watt/kg
Ill. Operation Details
23 Ambient temperature (max.) 45
24 Ambient temperature (average) 30
25 Temperature rise limit (at 3000 m )
25.1 oil / top 55
25.2 windings / average 60
25.3 windings hot spot 68
26 No-load loss at rated voltage and kW <0.5865
frequency
27 Full load loss ,W kW <6.05
28 Rated voltage at full load (P.F=0.95) kV
29 Efficiency referred to 75 0C at rated
voltage and frequency
No Item Unit Requirement Bid Offer

29.1 100% rated output and P.F= 1 (0/0)


29.2 100% rated output and P.F= 0.95
(0/0)
30 No load current as percent of rated
current
30.1 at 90% voltage (0/0)
30.2 at 100% voltage (0/0)
Bushings
31 Primary
31.1 Manufacturer
31.2 rated current
31.3 power frequency test level kV 95
31.4 lightning impulse level 250
31.5 clearance across insulator Mm 480
31.6 adjustable arcing horns yes/no Yes
creep age distance Mm >1080

31.8 Specification of creepage distance IEC 60815-2/2008

32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 rated current
32.4 power frequency test kV min. 3
32.5 lightning impulse test
32.6 clearance across insulator Mm 60
32.7 Min. creep age distance Mm
V. Tests
33 Routine tests: IEC 60076 and on each unit
Specifications
34 Separate source over-voltage on each unit
withstand test
No Item Unit Requirement Bid Offer

35 Induced over voltage withstand test, on each unit


36 test voltage / primary (tap 1) (IEC kV Yes
test standard)
37 test voltage / secondary (IEC test kV Yes
standard)
38 Type tests: IEC 60076 and on one unit
S ecifications
39 test voltage / full wave (IEC test Yes
standard)
40 test voltage / chopped wave (IEC test Yes
standard)
41 Heat-run test on one unit
42 Noise level at a measuring distance dB(A)
of 0.3meter
VI. Materials, Masses, Measures
and Drawings
43 Transformer tank, material Steel
43.1 Transformer total mass Kg
43.2 Overall dimensions including
bushings:
43.3 Height Mm
43.4 Depth Mm
43.5 Width Mm
43.6 Thickness of tank plate
43.7 Top Mm
43.8 Bottom Mm
43.9 Sides Mm
43.1 Colour of transformer Grey
43.1 Thickness of surface treatment 140
44 Drawing of dimensions No.
45 Pamphlet No.
8. GUARANTEED TECHNICAL PARTICULARS FOR 630KVA
(33/0.4) KV DISTRIBUTIONTRANSFORMER.

No Item Unit Requirement Bid Offer

1. General
1 Manufacturer

2 Country of manufacture

3 Kind of installation Indoor, Ground


Mounted
4 Equipment Standard IEC 60076
5 No. of phases three-phase
6 Type of tank Bolted Cover
7 No. of windings Two
8 Vector group symbol Dyn5
9 Tapping range 2.5
10 Number of steps ± steps
11 Maximum height above sea level at meters 3000
which the tests are performed
12 Cooling method ONAN
13 Specification of oil) IEC 60296
11. Ratings
14 Rated power kVA 630
15 Rated system voltage
15.1 primary UNI 33
15.2 secondary UN2 0.4
16 Frequency 50
17 Principal tapping 33
18.1 Maximum Continuous System 36
withstand Voltage
18.2 Rated Voltage of the equipment kV 52
19 Impedance voltage at rated power 4
No Item Unit Requirement Bid Offer

20 HV Windings
20.1 Material, wire or strip Copper wire/strip

20.2 Insulation
20.3 Power frequency withstand voltage kV(rms) 70
20.4 Rated lightning, impulse withstand kV(peak) 170
voltage
21 LV Windings
21.1 Material, wire or strip
Copper wire/strip
21.2 Insulation
21.3 Power frequency withstand voltage kV(rms) 3

21.4 Rated lightning, impulse withstand kV(peak)


voltage
21.5 Magnetic flux density (at rated Tesla 1.7
voltage and frequency)
22 Core Material CRGO
22.1 Core Loss figure, Watt/kg
Ill. Operation Details
23 Ambient temperature (max.) 45
24 Ambient temperature (average) 30
25 Temperature rise limit (at 3000 m )
25.1 oil / top 55
25.2 windings / average 60
25.3 windings hot spot 68
26 No-load loss at rated voltage and kW <0.69
frequency
27 Full load loss ,W kW <7.15
28 Rated voltage at full load (P.F=0.95)
29 Efficiency referred to 75 0C at rated
voltage and frequency
No Item Unit Requirement Bid Offer

29.1 100% rated output and P.F= 1 (0/0)


29.2 100% rated output and P.F= 0.95
(0/0)
30 No load current as percent of rated
current
30.1 at 90% voltage (0/0)
30.2 at 100% voltage (0/0)
Bushings
31 Primary
31.1 Manufacturer
31.2 rated current 630
31.3 power frequency test level 95
31.4 lightning impulse level 250
31.5 clearance across insulator 480
31.6 adjustable arcing horns yes/no Yes
creep age distance >1080

32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 rated current
32.4 power frequency test level (at 1000 min. 3
m)
32.5 lightning impulse level (at 1000 m) kV
32.6 clearance across insulator
32.7 Min. creep age distance 60
V. Tests
33 Routine tests: IEC 60076 and on each unit
Specifications
34 Separate source over-voltage on each unit
No Item Unit Requirement Bid Offer

withstand test
35 Induced over voltage withstand test, on each unit
36 test voltage / primary (tap 1) (IEC kV Yes
test standard)
37 test voltage / secondary (IEC test Yes
standard)
38 Type tests: IEC 60076 and on one unit
Specifications
39 test voltage / full wave (IEC test Yes
standard)
40 test voltage / chopped wave (IEC test Yes
standard)
41 Heat-run test on one unit
42 Noise level at a measuring distance dB (A)
of 0.3meter
VI. Materials, Masses, Measures
and Drawings
43 Transformer tank, material Steel
43.1 Transformer total mass kg
43.2 Overall dimensions including
bushings:
43.3 Height
43.4 Depth
43.5 Width mm
43.6 Thickness of tank plate
43.7 Top
43.8 Bottom mm
43.9 Sides mm
43.1 Colour of transformer Grey
43.1 Thickness of surface treatment 140
44 Drawing of dimensions No.
45 Pamphlet No.
9. GUARANTEED TECHNICAL PARTICULARS FOR 800KVA
(33/0.4)KV DISTRIBUTION TRANSFORMER.

No Item Unit Requirement Bid Offer

1. General
1 Manufacturer

2 Country of manufacture

3 Kind of installation Indoor, Ground


Mounted
4 Equipment Standard IEC 60076
5 No. of phases three-phase
6 Type of tank Bolted Cover
7 No. of windings Two
8 Vector group symbol Dyn5
9 Tapping range 2.5
10 Number of steps ± steps
11 Maximum height above sea level at meters 3000
which the tests are performed
12 Cooling method ONAN
13 Specification of oil) IEC 60296
11. Ratings
14 Rated power kVA 800
15 Rated system voltage
15.1 primary UN 1 33
15.2 secondary UN2 0.4
16 Frequency Hz 50
17 Principal tapping 33
18 Maximum Continuous System 36
withstand Voltage
19 Impedance voltage at rated power 5
N0 Item Unit Requirement Bid Offer

20 HV Windings
20.1 Material, wire or strip Copper wire/strip

20.2 Insulation
20.3 Power frequency withstand voltage kV(rms) 70
20.4 Rated lightning, impulse withstand kV(peak) 170
voltage
21 LV Windings
21.1 Material, wire or strip Copper wire/strip

21.2 Insulation
21.3 Power frequency withstand voltage kV(rms) 3

21.4 Rated lightning, impulse withstand kV(peak) 6


voltage
21.5 Magnetic flux density (at rated Tesla 1.7
voltage and frequency)
22 Core Material CRGO
22.1 Core Loss figure, Watt/kg
Ill. Operation Details
23 Ambient temperature (max.) 45
24 Ambient temperature (average) 30
25 Temperature rise limit (at 3000 m )
25.1 oil / top 55
25.2 windings / average 60
25.3 windings hot spot 68
26 No-load loss at rated voltage and kW <0.7475
frequency
27 Full load loss ,W kW 0.24
28 Rated voltage at full load (P.F=0.95)
29 Efficiency referred to 75 0C at rated
voltage and frequency
No Item Unit Requirement BidOffer

29.1 100% rated output and P.F= 1 (0/0)


29.2 100% rated output and P.F= 0.95
(0/0)
30 No load current as percent of rated
current
30.1 at 90% voltage (0/0)
30.2 at 100% voltage (0/0)
Bushings
31 Primary
31.1 Manufacturer
31.2 rated current 630
31.3 power frequency test level 95
31.4 lightning impulse level 250
31.5 clearance across insulator 480
31.6 adjustable arcing horns yes/no Yes
31.7 creep age distance mm >1080

32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 rated current
32.4 power frequency test level (at 1000 min. 3
m)
32.5 lightning impulse level (at 1000 m)
32.6 clearance across insulator Mm
32.7 Minimum creep age distance Mm 60
V. Tests
33 Routine tests: IEC 60076 and on each unit
Specifications
34 Separate source over-voltage on each unit
withstand test
No Item Unit Requirement: Offer

35 Induced over voltage withstand test, on each unit


36 test voltage / primary (tap 1) (IEC kV Yes
test standard)
37 test voltage / secondary (IEC test Yes
standard)
38 Type tests: IEC 60076 and on one unit
Specifications
39 test voltage / full wave (IEC test Yes
standard)
40 test voltage / chopped wave (IEC test Yes
standard)
41 Heat-run test on one unit
42 Noise level at a measuring distance dB (A)
of 0.3meter
VI. Materials, Masses, Measures
and Drawings
43 Transformer tank, material Steel
43.1 Transformer total mass kg
43.2 Overall dimensions including
bushings:
43.3 Height
43.4 Depth
43.5 Width mm
43.6 Thickness of tank plate
43.7 Top
43.8 Bottom mm
43.9 Sides mm
43.1 Colour of transformer Grey
43.1 Thickness of surface treatment 140
44 Drawing of dimensions No.
45 Pamphlet No.