0% found this document useful (0 votes)
41 views6 pages

RCP 1u Spec

This document summarizes a 1000-3000W 1U distributed power system called the RCP-1U rack system. It can provide up to 3000W of power in a 1U rack shelf form factor by utilizing multiple 1000W power supply modules with active current sharing. The system has universal AC input, programmable output voltage, hot swap capability, and a 5 year warranty. It is intended for applications such as industrial automation, distributed power architectures, electric vehicle charging, and more.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
41 views6 pages

RCP 1u Spec

This document summarizes a 1000-3000W 1U distributed power system called the RCP-1U rack system. It can provide up to 3000W of power in a 1U rack shelf form factor by utilizing multiple 1000W power supply modules with active current sharing. The system has universal AC input, programmable output voltage, hot swap capability, and a 5 year warranty. It is intended for applications such as industrial automation, distributed power architectures, electric vehicle charging, and more.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

1000 ~ 3000W 1U Distributed Power System RCP-1U Rack System

Rack Dimension
L * W * H
483.6 * 350.8 * 44 (1U) mm
Bauar t gepruft
Sicherheit
egel ma ge
od o s
be wac g

19 * 13.8 * 1.73 (1U) inch www. tuv.com


ID 2000000000

■ Features ■ Applications
Universal AC input / Full range Industrial automation
1U profile 19” rack shelf, fitting three 1000W modules Distributed power architecture system
up to 3000W with active current sharing Wireless/telecommunication solution
Output voltage programmable Redundant power system
Support hot swap (hot plug) Electric vehicle charger system
5 years warranty Constant current source system

■ Description
RCP-1U rack system is a power distribution solution utilizing the rack configuration with 1U low profile.
Starting with a single unit of 1000W, RCP-1000 is the front end rectifier (or, power supply). With the active
current sharing function, up to 3000W is able to be provided by 1 stack of the 19 ” rack mountable shelf
RCP-1U and 8000W by 3 stacks. The design flexibility for system applications is ideally fulfilled by various
built-in features, such as output programming, remote ON-OFF, auxiliary power, etc.

■ Model Encoding / Order Information


Rack Shelf: Whole System:
RCP-1U I RCP-3K1U I -12 - C
2
C: With I C Interface
I: AC Inlet (IEC320-C14)
- : Without I2C Interface
T: Terminal block
Output voltage
Profile of the system
I: AC Inlet (IEC320-C14)
Series name
T: Terminal block
1U: Profile of the system
3K: Maximum wattage with
fully-populated shelf
Series name
File Name:RCP-1U Rack System-SPEC 2016-07-26
1000 ~ 3000W 1U Distributed Power System RCP-1U Rack System
SPECIFICATION - Power Supply System
MODEL RCP-3K1U□-12 RCP-3K1U□-24 RCP-3K1U□-48
RECTIFIER RCP-1000-12 RCP-1000-24 RCP-1000-48
RACK SHELF RCP-1UI or RCP-1UT
OUTPUT OUTPUT VOLTAGE 12V 24V 48V
MAX. OUTPUT CURRENT 180A 120A 63A
MAX. OUTPUT POWER Note.6 2160W 2880W 3024W
VOLTAGE RANGE Note.5 90 ~ 264VAC 127 ~ 370VDC
FREQUENCY RANGE 47 ~ 63Hz
INPUT
AC CURRENT (Typ.)PER MODULE 8.5A/115VAC 4.5A/230VAC 10.5A/115VAC 5.5A/230VAC 11A/115VAC 5.5A/230VAC
LEAKAGE CURRENT <3.5mA / 230VAC
AUXILIARY POWER 5V @ 0.3A
REMOTE ON-OFF CONTROL By electrical signal or dry contact ON:short OFF:open
REMOTE SENSE Compensate voltage drop on the load wiring up to 0.5V.
FUNCTION OUTPUT VOLTAGE PROGRAMMABLE Adjustment of output voltage is allowable to 90 ~ 110% of nominal output voltage. Please refer to the Function Manual.
DC OK SIGNAL The isolated TTL signal out, Please refer to the Installation Manual
AC OK SIGNAL The isolated TTL signal out, Please refer to the Installation Manual
OVER TEMP WARNING Logic " High" for over temperature warning, Please refer to the Installation Manual, isolated signal
WORKING TEMP. -20 ~ +60℃ (Refer to "Derating Curve")
WORKING HUMIDITY 20 ~ 90% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT ±0.02%/℃ (0 ~ 50℃)
VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY STANDARDS UL60950-1, TUV EN60950-1 approved
WITHSTAND VOLTAGE I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.7KVDC
ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
Parameter Standard Test Level / Note
Conducted EN55022 (CISPR22) / EN55011 (CISPR11) Class B
EMC EMISSION Radiated EN55022 (CISPR22) / EN55011 (CISPR11) Class B
Harmonic Current EN61000-3-2 -----
Voltage Flicker EN61000-3-3 -----
SAFETY & EN55024 , EN61204-3, EN61000-6-2
EMC Parameter Standard Test Level / Note
(Note 4) ESD EN61000-4-2 Level 3, 8KV air ; Level 2, 4KV contact
Radiated EN61000-4-3 Level 3
EFT / Burst EN61000-4-4 Level 3
EMC IMMUNITY
Surge EN61000-4-5 Level 4, 4KV/Line-Earth ; Level 3, 2KV/Line-Line
Conducted EN61000-4-6 Level 3
Magnetic Field EN61000-4-8 Level 4
>95% dip 0.5 periods, 30% dip 25 periods,
Voltage Dips and Interruptions EN61000-4-11
>95% interruptions 250 periods
DIMENSION Rack 483.6*350.8*44(L*W*H)
OTHERS
PACKING 13.2Kg; 1pcs/13.2Kg/2.67CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
NOTE
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. Under parallel
operation of more than one rack connecting together, ripple of the output voltage may be higher than the SPEC at light load condition. It will go back to
normal ripple level once the output load is more than 10%. .
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a 720mm*360mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to
perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com)
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
6. Output of all the RCP-1000 modules are connected in parallel in the rack.

File Name:RCP-1U Rack System-SPEC 2016-07-26


1000 ~ 3000W 1U Distributed Power System RCP-1U Rack System
Function Manual
1. Remote ON/OFF Control
The PSU can be turned ON/OFF together or separately by using the "Remote ON-OFF" function.

1 1
Remote ON-OFF A 8 Remote ON-OFF A 8 Between Remote ON-OFF and -S Output
Remote ON-OFF B 15 Remote ON-OFF B 15
RCP-1U Remote ON-OFF C RCP-1U Remote ON-OFF C
System System Switch Open OFF
-S 21 -S 21 Switch Short ON

2. Voltage Drop Compensation


2.1 Remote Sense
The remote sense compensates voltage drop on the load wiring up to 0.5V.

+V +V
20
+S
RCP-1U System 21 LOAD
-S
-V -V

Sense lines should be twisted in pairs


2.2 Local Sense
Notice : The +S,-S, on CN500 have to be connected to the +V,-V terminals locally in order to get the correct output voltage if the remote sensing is not used.
22
+V
20
+S
RCP-1U System 25
-V
21
-S

3. Output Voltage Programming (or, PV / remote voltage programming / remote adjust / margin programming / dynamic voltage trim)
(1)Output voltage can be trimmed between 90~110% of its rated value by the following method.
(2)+S & +V, -S & -V also need to be connected on CN500.

22
+V
20
+S
4 R1 R1 R1
V-TRIM-A
11
RCP-1U System V-TRIM-B LOAD
18
V-TRIM-C
21 R2 R2 R2
-S
25
-V

3.1 RCP-1000-12
Vout (%) Vout (%)

100 110

98 108

96 106

94 104

92 102

90 100
R1 (Ω) R2 (Ω)
180K 240K 350K 560K 1.2M NC min. 0.1W NC 300K 120K 62K 31K 13K min. 0.1W

File Name:RCP-1U Rack System-SPEC 2016-07-26


1000 ~ 3000W 1U Distributed Power System RCP-1U Rack System
3.2 RCP-1000-24
Vout (%) Vout (%)

100 110

98 108

96 106

94 104

92 102

90 100
R1 (Ω) R2 (Ω)
560K 750K 1M 1.6M 3.3M NC min. 0.1W NC 330K 130K 62K 30K 10K min. 0.1W

3.3 RCP-1000-48
Vout (%) Vout (%)

100 110

98 108

96 106

94 104

92 102

90 100
R1 (Ω) R2 (Ω)
1.3M 1.7M 2.4M 3.6M 7.6M NC min. 0.1W NC 345K 140K 70K 36K 15K min. 0.1W

2
4. I C Bus Interface Option
2
※ For the details of I C option, please refer to the Installation Manual.

File Name:RCP-1U Rack System-SPEC 2016-07-26


1000 ~ 3000W 1U Distributed Power System RCP-1U Rack System
Mechanical Specification (Rack System) Case No. 959A Unit:mm

Fig1

14 25

1 13

ADDRESS
SWITCH CN500
- + 14 25
LC NC LB NB LA NA
RCP-1UT 1 13 Mounting Bracket

10 8

ADDRESS
SWITCH CN500
C B A - + 14 25

RCP-1UI 1 13

440

1 1

125
125

350.8

1 1

125
125

1 1
3-M5 L=6mm

3-M5 L=6mm

50
50

24

22 22

Air flow
direction

Module C Module B Module A


31.8
44

10.6
7.1

DC OK AC OK DC OK AC OK DC OK AC OK
6.1

466.2
483.6

Chassis of RCP-1U RACK


※ Mounting Instruction Mounting Surface
Hole No. Recommended Screw Size MAX. Penetration Depth L Recommended mounting torque
1 M5 6mm 10Kgf-cm

Mounting Screw
L

File Name:RCP-1U Rack System-SPEC 2016-07-26


1000 ~ 3000W 1U Distributed Power System RCP-1U Rack System
※ IN/OUT Connector Pin No. Assignment( CN500 ) : D-Type Right Angle 25 positions(female type)

14 25

1 13

Pin No. Function Description


1,8,15 RemoteON-OFF Each unit can separately turn the output on and off by electrical or dry contact between Remote ON-OFF A,B,C(pin 1,8,15) and -S(pin 21). Short: ON, Open:OFF.
Low : When input voltage is ≧82Vrms +/-4V.
2,9,16 AC-OK
High : When input voltage in≦82Vrms +/-4V.
High : When Vout≦80%+/-5%.
3,10,17 DC-OK
Low : When Vout ≧80%+/-5%
4,11,18 V-TRIM Connection for output voltage programming.
High : When the internal temperature is within safe limit.
5,12,19 T-ALARM
Low : 10℃ below the thermal shut down limit.

6 +5V-AUX Auxiliary voltage output, 4.3~5.3V, referenced to GND-AUX(pin 7).


The maximum load current is 0.3A. This output has the built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
Auxiliary voltage output GND.
7 GND-AUX
The signal return is isolated from the output terminals (+V & -V).

14 CS Current sharing signal.


When units are connected in parallel, the CS pins of the units should be connected to allow current balance between units.
20 +S Positive sensing for Remote Sense.
21 -S Negative sensing for Remote Sense.
22 +V Positive output voltage.
2
23 SCL Serial clock used in the I C interface option. Refer to the Instruction Manual.
2
24 SDA Serial data used in the I C interface option. Refer to the Instruction Manual.
25 -V Negative output voltage.

Installation Manual
Please refer to the manual of RCP-1U system.

File Name:RCP-1U Rack System-SPEC 2016-07-26