1 Dir OC + EF Protn - APPS
1 Dir OC + EF Protn - APPS
Imagination at work
Directional Protection
Need for Directional Control
A B
A B
• Both load and fault current may flow in either direction along
feeder circuits
51 67 67 67
Load Load
51 67 67 67
Load
Ring Main Circuit
Procedure :
1. Open ring at A
Grade : A' - E' - D' - C' - B'
2. Open ring at A'
Grade : A - B - C - D - E
Typical operating times shown.
Note : Relays B, C, D’, E’ may be non-directional.
A B' B C' C
1.7
0.1 1.3 0.5 0.9
0.9 D'
0.5 D
A' E E'
1.7
0.1 1.3
Ring System with Two Sources
Discrimination between all relays is not possible due to different requirements under
different ring operating conditions.
For F1 :- B’ must operate before A’ Not
For F2 :- B’ must operate after A’ Compatible
F1
A B' B C' C
A'
F2 D D'
Ring System with Two Sources
Option 1
Trip least important source instantaneously then treat as normal ring main.
Option 2
Fit pilot wire protection to circuit A - B and consider as common source busbar.
A 50
Option 1 Option 1 Option 1
PW PW
Option 2 Option 2
Parallel Feeders
Non-Directional Relays :-
51 A 51 C Load
51 B 51 D
F
“Conventional Grading” :- A&B
Operating Time
Grade ‘A’ with ‘C’
C&D
and Grade ‘B’ with ‘D’
51 A C 51
I2 LOAD
51 B D 51
Relays ‘C’ and ‘D’ see the same fault current (I2). As
‘C’ and ‘D’ have similar settings both feeders will be
tripped.
Parallel Feeders
C
51 A I2 67 LOAD
51 B D 67
E
51 A C 67 Load
51
51 B D 67
B D
Grade B with D at If3 A C Load
Load B D If1
(upper feeder open at P)
If2
Grid supply
P1 67 67
S1
51
S2
P2
S2 S1
P2 P1
51
51 51
S S 2
2 S 2
S 2 S 2
S 2 S 2
Directional Decision by Phase Comparison (2)
S1
S2 S2
S2 S2
S2 S2
S2
Polarising Voltage for ‘A’ Phase Overcurrent Relay
OPERATE SIGNAL = IA
Applied Voltage : VA
Applied Current : IA
VA
IA
Operate
IAF
VAF
Restrain
Question :
- is this comparison suitable for a typical power system ?
Polarising Voltage
Applied Voltage : VBC
Applied Current : IA
VA
IA
IAF
IVBC
IA
VA
90
VBC
VC VB
The 90 connection is now used for all overcurrent relays. 30 and 60°
connections were also used in the past, but are no longer used, as the 90
connection gives better performance.
Relay Characteristic Angle (R.C.A.)
for Electronic Relays
The angle by which the current applied to the relay must be displaced from the
voltage applied to the relay to produce maximum operational sensitivity
e.g. 45°
OPERATE
RCA
45
VBC
90° Connection - 45° R.C.A.
MAX SENSITIVITY
OPERATE LINE
IA
V VA IA FOR MAX
RESTRAIN SENSITIVITY
A 45
90 45
VBC VBC
135
VC VB
OPERATE
MAX
SENSITIVITY
IA RESTRAIN LINE
VA VA IA FOR MAX
30
SENSITIVITY
90 30
V BC V BC
150
VC VB
Tripping
Direction
Selection of the R.C.A.
Plain feeder - zero sequence source behind relay
Selection of the R.C.A.
Plain or a Transformer feeder – only zero sequence source
in front of the relay
45° RCA (lead)
Tripping
Transformer Feeder Direction
Tripping
Direction
Selection of the R.C.A.
Plain Feeder – zero sequence source in front
Selection of the R.C.A.
Transformer feeder
Directional Earth Fault
Protection
Directional Earth Fault
Requirements are similar to directional overcurrent
i.e. need operating signal
and polarising signal
Operating Signal
obtained from residual connection of line CT's
i.e. Iop = 3Io
Polarising Signal
The use of either phase-neutral or phase-phase voltage as the reference
becomes inappropriate for the comparison with residual current.
Most appropriate polarising signal is the residual voltage.
Residual Voltage (1)
May be obtained from ‘broken’ delta V.T. secondary.
A
B
C
A-G
VA
VA
VC VB VC VB VC VB
VA VRES
VA VRES
VB VB VB
VC VC VC
Residual Voltage at R (relaying point) is dependant upon Z S / ZL ratio.
ZS0
VRES = x 3E
2Z S1 + ZS0 + 2Z L1 + ZL0
Residual Voltage (3)
Resistance Earthed System
E S R F
ZS ZL
N
ZE
A-G
G
ZS0 + 3Z E
VRES = x 3E
2Z S1 + ZS0 + 2Z L1 + ZL0 + 3Z E
V A-G V A-G
G.F G.F G.F
VRES
VC VB
Residual Voltage Polarisation
3R V0
(Relay Point)
V0 = 0 - I0 (ZS0 + 3R)
Virtual Current Polarisation
❑The faulted phase voltage is not considered in the residual
voltage calculation.
Transmission Systems
Directional earth fault used as back-up protection
Can form part of a directional scheme
VRES might be unreliable due to mutual coupling
Unsuitable VT for V RES measurement (i.e. open delta, 3-limb)
Negative Sequence
Z
Network :- ZL2
S2 I2
ZS1=ZS2
V2 ZL1=ZL2
(Relay Point)
V2 = 0 – I2 (ZS2)
Load Encroachment
Load Encroachment
LV Network Embedded
generation
LV Load
Application (2/11)
Directional Protection
DOC protection without embedded generation :-
▪Dir. Protection is naturally insensitive to load current (IA-LOAD), by virtue of its
direction
▪Since load current resides in the restraining region, a setting of 0.5In is often
selected
Normal Load
F1(A-B)
Direction
(IA-LOAD) 45° VBC
IAF (VPOL)
67
VC VB
IA-LOAD
CB3 CB4
Application (3/11)
Impact of Embedded Generation
45° VBC
Embedded
Normal Load
Direction
IA-EXP Generation (VPOL)
(IA-LOAD) VC VB
67 IA-LOAD
CB3 CB4
Application (4/11) Problem….
CB3 CB4
IF2
Application (5/11)
Solution – DOC with Load Blinding
Load blinding originates from distance protection relays:
❑Relay determines the difference between fault and load conditions by
the change in system impedance
❑DOC protection is:
▪ Inhibited during load conditions, thus permitting export of excess generation
▪ Allowed to operate for faults providing the correct direction
IF1
Z in front jX Fault Impedance
CB1 CB2 VS (F)
of relay
IF1+ IF2 Gen
IF1 Potential
Blind Spot Load Locus
F IS > (IF1+ IF2) (lagging VARs)
R
Load Locus
Embedded (leading VARs)
Generation Z behind
relay
67
CB3 CB4 Load Blinder
VS
Application (6/11)
Load Blinder Characteristic
jX
❑How to set?
Z MIN2 Z MIN1
33 10 3
ZMIN (primary) = = 31.7
3 600
❑ZMIN2 Import – Not required as imported load is naturally in the restraining
region of the DOC relay
Application (8/11)
Load Blinder Setting
1 = 2 = COS-1(0.85 ) + 15 = 47
Application (9/11)
Load Blinder Setting
❑ V< Undervoltage threshold
▪ Designed to disable the load blinder during fault conditions
▪ Must disable load blinder for faults with minimum embedded generation (VFAULT
0.5VN)
▪ Disabling load blinder for faults with maximum embedded generation less
important due to increase in fault current
▪ Recommended setting = 0.7VN
▪ Hence :-
jX Fault Impedance
(HV fault)
▪ Example: For 33kV system: Import region
ZMIN =
naturally 31.7Ω
33 10 3 blocked by Restraining
V = 0.7 = 13 .3kV DOC blinder region
3 characteristic. 47°
R
47°
Restraining
i.e. Operates if any ph-n region
voltage falls below 13.3kV
Application (10/11)
Load Blinder Characteristic – Setting Criteria (I2>)
I 2 = 0.38ISetting
▪ Example: Assuming IS = 0.5 IFLC
132kV
0.5 524
I 2 = 0.38 = 0.166 A sec
600
30MVA
▪ i.e. Load blinder turns off if
I2 component is above 0.166A (secondary)
600/1 Full load current (IFLC) =
67
524A at 33kV
33kV
Application (11/11) Hybrid Load Blinder / DOC
Characteristic (A-Phase Element)
Import / Export Load
Conditions Fault Condition
Insulated Systems
Insulated Systems (1)
a b c Where Ica is the capacitive
current for Phase A
Ica
Icb
R
Ic
Ica
Source Icb
R
Ic
Ica
Icb
R
3Ic 2Ic
Location CT's
Insulated Systems (2)
Faulty Feeder VRES VRES
Healthy Feeders
Va Vb Va Vb
Ic Ic
0V -3Ic 0V
Icb I Icb I
ca Pre-fault ca Pre-fault
Vc Vc
VRES VRES
Ic = Ica + Icb
-2Ic
RCA RCA
R
Ic
Ica
Source Icb
R
Ic
IL
Ica
Icb
IL 3Ic
R
Ic
2Ic
Location of CT's
IL
Peterson Coil Earthed Systems (2)
Faulty Feeder VRES VRES
Healthy Feeders
Va Vb Va Vb
N N
Pre-fault Pre-fault
Vc Vc
Ic Icb Ica
Ic
IL -3Ic
Ica Icb
Operate Operate
VPOL
VPOL
Peterson Coil Earthed Systems (3)
Faulty Feeders VRES VRES
Healthy Feeders
Va Vb Va Vb
N N
Pre-fault Pre-fault
Vc Vc
Ic Icb Ic Ica
IL -3Ic
Ica Icb
Operate Operate
VPOL
VPOL
Current Polarisation
Current Polarising
A solidly earthed, high fault level (low source impedance) system may result
in a small value of residual voltage at the relaying point. If residual voltage is
too low to provide a reliable polarising signal then a current polarising signal
may be used as an alternative.
OP
POL
DEF Relay
Current Polarising (1)
OP
POL
DEF RELAY
OP
POL
DEF RELAY
OP
POL
DEF RELAY
OP
CORRECT
POL DEF RELAY
Auto Transformers (1)
ZT
ZH ZL
SOURCE
ZS SOURCE
DEF
RELAY
IH H L IL
IN = 3 (IL0 – IH0)
For HV Faults
IH H L IL
IN = 3 (IH0 – IL0)
Auto-Transformer Example
ZS
H L
IN = 3 (IH0 – IL0)
I0
ZT0
Auto-Transformer Example
ΙH0 = Ι 0 in p.u.
MVAbase
= Ι0 x in kA
3 x kVH
Z T0
ΙL0 = . Ι 0 in p.u.
Z T0 + Z S0 + ZL0
Z T0 MVAbase
= . Ι0 x in kA
Z T0 + Z S0 + ZL0 3 x kVL
Auto-Transformer Example
3 Ι 0 .MVA base 1 1 Z T0
ΙN = -
3 kVH kVL Z T0 + Z S0 + ZL0
1 1 Z T0
ΙN is + ve if
kVH kVL Z T0 + Z S0 + ZL0
kVH Z T0
or Z + Z + Z 1
kVL T0 S0 L0
Auto-Transformer Example
ZS
H L
IN = 3 (IL0 – IH0)
I0
ZT0
❑ IH0 = 0
❑ IN = 3IL0 which is +ve.
Directional Control
51 I
67 I
VT supervision
selectively block operation