03 CB - Routine Tests-New
03 CB - Routine Tests-New
—
ABB PowerTEC
—
Type of testing & its importance
TYPE TEST – This test is done on a product for the certification of the design parameters. (According
to clause 6 of IEC 62271-100)
ROUTINE TEST – This test is done on each product produce at manufacture end. (According to clause 7
of IEC 62271-100)
1
6/17/2019
TEST CHAMBER
TEST CHAMBER
2
6/17/2019
—
Routine test procedure for circuit breaker
SCOPE
CONTENT
– Over pressure test (ABB specification)
– Mechanical operating tests (Cl. No. 7.101)
– Timing & velocity measurement (Cl. No. 7.101)
– Measurement of the resistance of the main circuit (Cl. No. 7.3)
– Dynamic contact resistance measurement (ABB specification)
– Tightness test (Cl. No. 7.4)
– Design and visual checks (Cl. No. 7.5)
– Dielectric test on the main circuit (Cl. No. 7.1)
– Dielectric test on auxiliary and control circuits (Cl. No. 7.2)
– Before the starting the above tests, the following points are to be taken care off:
i) Proper electrical connections are made as per the schematic.
ii) Gas is filled up to 7.0 bar absolute pressure.
—
Routine test procedure for circuit breaker
TEST : 01
3
6/17/2019
—
Routine test procedure for circuit breaker
TEST : 02
—
Routine test procedure for circuit breaker
TEST : 03
üThis test determines Operating Time & velocity of the breaker. The
main contacts are monitored to obtain instant of contact
separation or contact make through a suitable Breaker analyzer.
The closing and tripping signals are given to the respective coils at
the terminals provided on the operating mechanism.
4
6/17/2019
—
Routine test procedure for circuit breaker
—
Test Definitions for circuit breaker
5
6/17/2019
—
Routine test procedure for circuit breaker
—
Routine test procedure for circuit breaker
140 140
A
120 120 A
T1
a a
b b
100 100
80 80
mm
mm
60 60
40 40
20 20
T1
0
0
2
2
A
Ic
A
Ic 0
0
0 20 40 60 80 100 120 140 160 180
0 20 40 60 80 100 120 140 160 180 ms
ms
6
6/17/2019
—
Routine test procedure for circuit breaker
TEST : 04
7
6/17/2019
—
Routine test procedure for circuit breaker
—
Routine test procedure for circuit breaker
8
6/17/2019
—
Routine test procedure for circuit breaker
TEST : 05
Dynamic contact resistance measurement in open operation (DCRM)
üInstrument Requirement: DCRM kit (Provided in Elcon)
üClose the circuit breaker.
üConnection same as in contact resistance test.
üGive open command to circuit breaker & record the signature of dynamically contact open operation.
—
Routine test procedure for circuit breaker
TEST : 06
Tightness test
üThis same sniffing test is carried out on the Gas pipe and the Distribution
Block for tightness ,wherever applicable.
9
6/17/2019
—
Routine test procedure for circuit breaker
TEST : 07
—
Routine test procedure for circuit breaker
TEST : 08
Dielectric test on the main circuit
üInstrument Requirement: HV Transformer & control panel
üThis test is conducted at blocking pressure
üAs per the testing standard , all Circuit Breakers have to pass the
Power frequency dry voltage withstand test for one minute.
üConnection from the Transformer is taken to the top flange of pole
column with a GI wire and bottom is earthed.
üWith circuit breaker in close position, the support insulator of pole
column of the breaker is tested for its dielectric strength
üSimilarly with circuit breaker in open position, if middle flange is
earthed then arc chamber of pole column gets tested.
10
6/17/2019
—
Routine test procedure for circuit breaker
Breaker in Close Breaker in Open
position position
—
Routine test procedure for circuit breaker
TEST : 09
Dielectric test on auxiliary and control circuits
11
6/17/2019
—
Routine test procedure– LTBE1 245 kV breaker
LIMITING VALUES
CO Time : Max. 30 ms
Stroke : 160 ± 3 mm
Motor Current : 10 Amp(220 V)
20 Amp(110 V)
Spring Charging Time :15 Sec Max.
Contact Resistance : 49 mW (At 20 º C)
CO Time :
Max. 70 ms
Stroke 160 ± 3 mm
:
Motor Current : 10 Amp(220 V)
20 Amp(110 V)
Spring Charging Time :20 Sec Max.
Contact Resistance : 102 mW (At 20 º C)
12
6/17/2019
—
Routine test procedure– 800 kV LTBE4 breaker
LIMITING VALUES
Close Time : Max. 60 ms Close velocity : 4.2 to 4.7 m/s
Open Time : Max. 25 ms Open velocity : 7.2 to 7.5 m/s
CO Time : Max. 70 ms
Stroke : 160 ± 3 mm
Motor Current : 15 Amp(220 V dc)
30 Amp(110 V dc)
Spring Charging Time :30 Sec Max.
Contact Resistance : 260 mW (At 20 º C)
—
Routine test – 245 kV ELF SL 4-1 breaker
LIMITING VALUES
Close Time : Max. 130 ms
Open Time : 16 – 30 ms
CO Time : 35 – 45 ms
Contact Resistance : Max. 45 mW (At 20 º C)
Close velocity : 4 - 6 m/s
Trip velocity : 7.5 to 9.5 m/s
Stroke length : 200 ± 2 mm
13
6/17/2019
LIMITING VALUES
CO Time : Max. 60 ms
—
Equipments used at test plants
14
6/17/2019
—
ABB PowerTEC™ scheduled courses Y2019
Sr. Course
Course Name Days Jan Feb March April May June July August Sep Oct Nov Dec
No. No.
INTCV566
16 HVDC and FACTS 2 19-20
& 567 Manisha Shukla
17 Microgrids, renewables & BESS * INTCV570 3 21-23 [email protected]
18 Asset Performance management * INTCV569 2 17-18
ABB reserves all rights for the content provided in this presentation. Reproduction, use by or
disclosures to third parties without ABB’s written permission is strictly forbidden
15