AF CV4 (Star TCC)

The document appears to be an electrical diagram showing a 1000 kVA transformer and associated protection relays. Lines connect a source labeled H-110-PDC-026 to the transformer labeled H-480-XF-1051 and then to loads. The transformer and two protection relays, labeled RP-1051 and H-110-RP-0261, are depicted with technical specifications including voltage ratings, current transformer ratios, and overload protection settings. Fault current measurements are shown for the transformer and relays.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
37 views

AF CV4 (Star TCC)

The document appears to be an electrical diagram showing a 1000 kVA transformer and associated protection relays. Lines connect a source labeled H-110-PDC-026 to the transformer labeled H-480-XF-1051 and then to loads. The transformer and two protection relays, labeled RP-1051 and H-110-RP-0261, are depicted with technical specifications including voltage ratings, current transformer ratios, and overload protection settings. Fault current measurements are shown for the transformer and relays.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Amps X 10 H-110-PDC-026 (Nom. kV=10, Plot Ref.

kV=10)
.5 1 5 10 50 100 500 1K 5K 10K
10K 10K
H-480-XF-1051
FLA - ONAN 65
5K 5K

1K 1K

500 500

H-480-XF-1051
1000 kVA (Secondary) 5.4 %Z
Delta-Wye Solid Grd

100 100

50 RP-1051 - P 50
ABB
REF 610
CT Ratio 100:5
OC1 H-110-RP-0261 - P
IEC - Extremely Inverse OC1
Pickup = 0.5 (0.3 - 5 xCT Sec) GE Multilin

Seconds
Seconds

Time Dial = 0.27 750/760


10 Inst = 5.3 (0.5 - 35 xCT Sec) CT Ratio 300:5 10
Time Delay = 0.12 s IEC - B
OC2 Pickup = 1.6 (0.05 - 20 xCT Sec)
Inst = 11.6 (0.5 - 35 xCT Sec) Time Dial = 0.5
5 5
Time Delay = 0.04 s Inst = 8 (0.05 - 20 xCT Sec)

H-110-RP-0261

OCR

1 1
RP-1051

R
.5 .5

H-480-XF-1051
1000 kVA

H-110-RP-0261 - 3P
12.929kA @ 10.575kV
(Sym)

.1 .1

H-480-XF-1051
Inrush
.05 .05

RP-1051 - 3P
4.872kA @ 10.575kV
(Sym)

.01 .01
.5 1 5 10 50 100 500 1K 5K 10K

Amps X 10 H-110-PDC-026 (Nom. kV=10, Plot Ref. kV=10) ETAP Star 16.0.0C

AF CV4

Project: Est. de Op. Conc. C1 e Hidro. Date: B


Location: Arequipa-Perú Rev: Base
Contract: MIP16E06 Fault: Phase
Engineer: CELICON INGENIEROS SAC
Filename: C:\Users\user\Desktop\MODELO_HIDRO_2018 - CESAR CASTILLO\MODELO_