Trans Series, M

This document provides the register addresses for user-defined and technician parameters in the MODBUS ASCII protocol for a trans-AMF system. It lists parameters such as voltage and frequency trip points for the mains and generator, breaker settings, display settings, and more. The parameters are organized into categories like Operator Parameters, System, Mains, Generator, and each parameter is associated with a unique register address.

Uploaded by

Apocalypse
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
58 views

Trans Series, M

This document provides the register addresses for user-defined and technician parameters in the MODBUS ASCII protocol for a trans-AMF system. It lists parameters such as voltage and frequency trip points for the mains and generator, breaker settings, display settings, and more. The parameters are organized into categories like Operator Parameters, System, Mains, Generator, and each parameter is associated with a unique register address.

Uploaded by

Apocalypse
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 29

TRANS-AMF REGISTER ADDRESS FOR MODBUS ASCII

User Defined Parameters


1. Operator Parameters
1.1 Mains

Parameter Parameter Description Address

MAINS VOLT LEVEL (Mains->Volt level)


Under volt trip Mains Under Voltage 40066
Under volt reset Mains Under Voltage Reset 40067
Over volt trip Mains Over Voltage 40068
Over volt reset Mains Over Voltage Reset 40069

MAINS FREQ. LEVEL (Mains->Frequency level)


Under freq trip Mains Under Frequency 40073
Under freq reset Mains Under Frequency Reset 40074
Over freq trip Mains Over Frequency 40075
Over freq reset Mains Over Frequency Reset 40076

1.2 Generator

GENERATOR VOLT LEVEL (Generator->Volt level)


Under volt shutdown Generator Under Voltage Shutdown 40085
Under volt prealarm Generator Under Voltage Pre-Alarm 40086
Under volt reset Generator Under Voltage Pre-Alarm Reset 40087
Over volt shutdown Generator Over Voltage Shutdown 40088
Over volt prealarm Generator Over Voltage Pre-Alarm 40089
Over volt reset Generator Over Voltage Pre-Alarm Reset 40090
Shutdown delay time Generator Voltage Shutdown Delay Time 40091

GENERATOR FREQ LEVEL (Generator->Frequency level)


Nominal frequency Nominal Alternator Frequency 40095
Under freq shutdown Generator Under Frequency Shutdown 40096
Under freq prealarm Generator Under Frequency Pre-Alarm 40097
Under freq reset Generator Under Frequency Pre-Alarm Reset 40098
Over freq shutdown Generator Over Frequency Shutdown 40099
Over freq prealarm Generator Over Frequency Pre-Alarm 40100
Over freq reset Generator Over Frequency Pre-Alarm Reset 40101
Shutdown delay time Generator Frequency Shutdown Delay Time 40102

GENERATOR CUR LEVEL (Generator->Current level)


Under cur. set Generator Under Current Set 40106
Under cur. prealarm Generator Under Current Pre-Alarm 40107
Under cur. reset Generator Under Current Pre-Alarm Reset 40108
Over cur. set Generator Over Current Set 40111
Over cur. prealarm Generator Over Current Pre-Alarm 40112
Over cur. reset Generator Over Current Pre-Alarm Reset 40113

1
GEN POWER LEVEL (Generator->Power level)
Under power shutdown Generator Under Power Shutdown 40123
Under power prealarm Generator Under Power Pre-Alarm 40124
Under power reset Generator Under Power Pre-Alarm Reset 40125
Over power shutdown Generator Over Power Shutdown 40126
Over power prealarm Generator Over Power Pre-Alarm 40127
Over power reset Generator Over Power Pre-Alarm Reset 40128
Shutdown delay time Generator Power Shutdown Delay Time 40129
Reverse power set Reverse Power Set 40130

GEN WORKING CALENDAR (Generator->Working calendar)


Disable/enable select Working Calendar Disable or Enable 40133
Start time on monday Working Calendar Work Start Time on Monday 40134
Stop time on monday Working Calendar Work Stop Time on Monday 40135
Start time on tues. Working Calendar Work Start Time on Tuesday 40136
Stop time on tuesday Working Calendar Work Stop Time on Tuesday 40137
Start time on wednes. Working Calendar Work Start Time on Wednesday 40138
Stop time on wednes. Working Calendar Work Stop Time on Wednesday 40139
Start time on thurs. Working Calendar Work Start Time on Thursday 40140
Stop time on thursday Working Calendar Work Stop Time on Thursday 40141
Start time on friday Working Calendar Work Start Time on Friday 40142
Stop time on friday Working Calendar Work Stop Time on Friday 40143
Start time on satur. Working Calendar Work Start Time on Saturday 40144
Stop time on saturday Working Calendar Work Stop Time on Saturday 40145
Start time on sunday Working Calendar Work Start Time on Sunday 40146
Stop time on sunday Working Calendar Work Stop Time on Sunday 40147

2. Technician Parameters
2.1 System

SYSTEM NETWORK (System->Network)


CT ratio Current Transformer Ratio 40001
Earth fault CT ratio Earth Fault Current Transformer Ratio 40002
PT ratio Voltage Transformer Ratio 40003
Type of AC system Select AC system; 0- 1 Phase 2 Wire 40004
1- 3 Phase 4 Wire
2- 1 Phase 3 Wire

Phase sequence Generator Phase Sequence (dis, L123 or L321) 40005

Generator kVA rating Generator kVA rating set 40006

2
BREAKERS (System->Breakers)
Type of Breaker Hardware Breaker Selection 40011
Gen.brk.cls.contact Gen Close Breaker Contact Type 40012
Gen.brk.cls.relay Gen Close Breaker Relay Type 40013
Gen.brk.cls.time Gen Close Timer 40014
Gen.brk.open relay Gen Open Breaker Relay Type 40015
Gen.brk.open time Gen Open Timer 40016
Mains.brk.cls.contact Mains Close Breaker Contact Type 40017
Mains.brk.cls.relay Mains Close Breaker Relay Type 40018
Mains.brk.cls.time Mains Close Timer 40019
Mains.brk.open relay Mains Open Breaker Relay Type 40020
Mains.brk.open time Mains Open Timer 40021
Break.close puls.time Breaker Close Pulse Time 40022
Break.open pulse time Breaker Open Pulse Time 40023
Transfer time Transfer Time 40024
Spring loading time Spring Loading Time 40025
Retry number Retry Number 40026

LCD DISPLAY (System->LCD display)


Language Laguage Selection 40031
Contrast Digital Contrast 40032
Auto backlight off Auto Backlight Off 40033
Auto scroll time Auto Scroll Time 40034
Auto scroll number Auto Scroll Number 40035
Err. mesg scroll time Scroll Time For Error Messages 40036

COMMUNICATION (System->Communication)
Slave address Slave Address 40040
Baud Rate 40041
0 - 1200 baud
Baud rate 1 - 2400 baud
2 - 4800 baud
3 - 9600 baud
4 - 19200 baud
5 - 38400 baud
Parity Parity 40042
0 - NONE
1 - ODD
2 - EVEN
Stop bit Stop Bit (0-> 1 stop bit,1-> 2 stop bit) 40043

DATE & TIME SET (System->Date & time set)


Year Year 40048
Month Month 40049
Day Date 40050
Week Day of week 40051
Hour Hour 40052
Minute Minute 40053
Second Second 40054

3
DEFAULT SETTINGS (System->Default settings)
Save setting to def. Save setting to default 40055
Reset default sets Reset default sets 40056
Reset factory sets Reset factory sets 40057

PASSWORD SETTINGS (System->Password settings)


Operator password Operator Password 40061
Technician password Technician Password 40062

2.2 Mains
MAINS VOLT LEVEL (Mains->Volt level)
Under volt trip Mains Under Voltage 40066
Under volt reset Mains Under Voltage Reset 40067
Over volt trip Mains Over Voltage 40068
Over volt reset Mains Over Voltage Reset 40069

MAINS FREQ. LEVEL (Mains->Frequency level)


Under freq trip Mains Under Frequency 40073
Under freq reset Mains Under Frequency Reset 40074
Over freq trip Mains Over Frequency 40075
Over freq reset Mains Over Frequency Reset 40076

MAINS ACTIONS (Mains->Actions)


Mains failure detect Mains Failure Detection En/Dis 40080
Mains fail.stop mode Look Mains Failure at Stop Mode En/Dis 40081
Always return delay Always Look Mains Return Delay 40082

2.3 Generator

GENERATOR VOLT LEVEL (Generator->Volt level)


Under volt shutdown Generator Under Voltage Shutdown 40085
Under volt prealarm Generator Under Voltage Pre-Alarm 40086
Under volt reset Generator Under Voltage Pre-Alarm Reset 40087
Over volt shutdown Generator Over Voltage Shutdown 40088
Over volt prealarm Generator Over Voltage Pre-Alarm 40089
Over volt reset Generator Over Voltage Pre-Alarm Reset 40090
Shutdown delay time Generator Voltage Shutdown Delay Time 40091

GENERATOR FREQ LEVEL (Generator->Frequency level)


Nominal frequency Nominal Alternator Frequency 40095
Under freq shutdown Generator Under Frequency Shutdown 40096
Under freq prealarm Generator Under Frequency Pre-Alarm 40097
Under freq reset Generator Under Frequency Pre-Alarm Reset 40098
Over freq shutdown Generator Over Frequency Shutdown 40099
Over freq prealarm Generator Over Frequency Pre-Alarm 40100
Over freq reset Generator Over Frequency Pre-Alarm Reset 40101
Shutdown delay time Generator Frequency Shutdown Delay Time 40102

4
GEN CUR LEVEL & ACT (Generator->Current level & act.)
Under cur. set Generator Under Current Set 40106
Under cur. prealarm Generator Under Current Pre-Alarm 40107
Under cur. reset Generator Under Current Pre-Alarm Reset 40108
Under cur. act. Generator Under Current Actions 40109
0 - Disable
1 - Warning (Alarm Only, No Shutdown)
2 - Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
3 - Shutdown (Alarm And Shutdown)
Under act. delay time Generator Under Current Actions Delay Time 40110
Over cur. set Generator Over Current Set 40111
Over cur. prealarm Generator Over Current Pre-Alarm 40112
Over cur. reset Generator Over Current Pre-Alarm Reset 40113
Over cur. act. Generator Over Current Actions 40114
0 - Disable
1 - Warning (Alarm Only, No Shutdown)
2 - Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
3 - Shutdown (Alarm And Shutdown)
Over act. delay time Generator Over Current Actions Delay Time 40115
Short circuit cur. Generator Short Circuit Current Set 40116
Earth fault cur. Generator Earth Fault Current Set 40117
Earth fault cur. act. Generator Earth Fault Current Actions 40118
0 - Disable
1 - Warning (Alarm Only, No Shutdown)
2 - Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
3 - Shutdown (Alarm And Shutdown)
E.F. act. delay time Generator Earth Fault Current Actions Delay Time 40119

GEN POWER LEVEL (Generator->Power level)


Under power shutdown Generator Under Power Shutdown 40123
Under power prealarm Generator Under Power Pre-Alarm 40124
Under power reset Generator Under Power Pre-Alarm Reset 40125
Over power shutdown Generator Over Power Shutdown 40126
Over power prealarm Generator Over Power Pre-Alarm 40127
Over power reset Generator Over Power Pre-Alarm Reset 40128
Shutdown delay time Generator Power Shutdown Delay Time 40129
Reverse power set Reverse Power Set 40130
Reverse power act. Reverse Power Actions 40131
0 - Disable
1 - Warning (Alarm Only, No Shutdown)
2 - Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
3 - Shutdown (Alarm And Shutdown)
Rv.pow.act.delay time Reverse Power Action Delay Time 40132

5
GEN WORKING CALENDAR (Generator->Working calendar)
Disable/enable select Working Calendar Disable or Enable 40133
Start time on monday Working Calendar Work Start Time on Monday 40134
Stop time on monday Working Calendar Work Stop Time on Monday 40135
Start time on tues. Working Calendar Work Start Time on Tuesday 40136
Stop time on tuesday Working Calendar Work Stop Time on Tuesday 40137
Start time on wednes. Working Calendar Work Start Time on Wednesday 40138
Stop time on wednes. Working Calendar Work Stop Time on Wednesday 40139
Start time on thurs. Working Calendar Work Start Time on Thursday 40140
Stop time on thursday Working Calendar Work Stop Time on Thursday 40141
Start time on friday Working Calendar Work Start Time on Friday 40142
Stop time on friday Working Calendar Work Stop Time on Friday 40143
Start time on satur. Working Calendar Work Start Time on Saturday 40144
Stop time on saturday Working Calendar Work Stop Time on Saturday 40145
Start time on sunday Working Calendar Work Start Time on Sunday 40146
Stop time on sunday Working Calendar Work Stop Time on Sunday 40147

GENERATOR GENERAL (Generator->General)


Sens.option gen.freq Sensing Options Generator Frq En/Dis 40151
Sens.opt.pickup&flywh Sensing Opt Pickup En/Dis & Flywheel 40152
All warning are latch All Warnings Are Latched En/Dis 40153

2.4 Engine

ENGINE START OPTIONS (Engine->Starting options)


Horn prior start Audible Alarm Prior To Starting En/Dis 40158
No. of start attemp Number Of Start Attempts 40159
Cranking time Cranking Time 40160
Crank rest time Crank Rest Time 40161
Pickup fail delay Pickup Sensor Fail Delay 40162

ENG. CRANK DISCONNECT (Engine->Crank disconnect)


Generator frequency Crank Disconnect On Gen. Frequency 40167
Engine speed Crank Disconnect On Engine RPM 40168
Generator volt Crank Disconnect On Gen. Voltage 40169
Alt. Charge volt Crank Disconnect On Charge Alt. Voltage 40170
Oil pressure Crank Disconnect On Oil Pressure 40171

ENGINE SPEED SETS (Engine->Speed settings)


Nominal speed Nominal Speed 40175
Under speed shutdown Engine Under Speed Shutdown 40176
Under speed prealarm Engine Under Speed Prealarm 40177
Under speed reset Engine Under Speed Prealarm Reset 40178
Over speed shutdown Engine Over Speed Shutdown 40179
Over speed prealarm Engine Over Speed Prealarm 40180
Over speed reset Engine Over Speed Prealarm Reset 40181
Shutdown delay time Engine Speed Shutdown Delay Time 40182

6
ENGINE PLANT BATTERY (Engine->Plant battery)
Under volt Battery Undervolts Warning 40186
Under volt reset Battery Undervolts Warning Reset 40187
Under volt delay Battery Undervolts Volts Delay 40188
Over volt Battery Overvolts Warning 40189
Over volt reset Battery Overvolts Warning Reset 40190
Over volt delay Battery Overvolts Delay 40191
Alt. chg. warning Charge Alternator Warning 40192

CANBUS ECU (Engine->CanBus ECU)


Baud rate Baud Rate: 40196
0 - 20
1 - 50
2 - 100
3 - 125
4 - 250
5 - 500
6 - 800
7 - 1.000
J1939 ECU type J1939 ECU Type Selection: 40197
0 - Disable
1 - Standard
2 - Volvo EMS2
3 - Volvo EDC4
4 - Perkins
Device address Device Address 40198
Engine cont. address Engine Control Address 40199
ECU remote control ECU Remote Control via J1939 40200
Speed control enable Speed Control via J1939 40201
Oil pres cont. enab Oil Pressure Control via J1939 40202
Temp. control enable Coolant Temperature Control via J1939 40203
Speed set point Speed Set Point Selection 40204
Speed correction Speed Correction Value 40205

7
CANBUS ERROR SET (Engine->CanBus error set)
CAN fault actions Can Fault Actions: 40208
0- Disable
1- Warning Non-Latching
2- Warning (Alarm Only, No Shutdown)
3- Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
4- Shutdown (Alarm And Shutdown)

CAN fault activation Can Fault Activation: 40209


0- Active From Starting
1- Active From Safety On
2- Always Active

CAN fault delay Can Fault Delay 40210


Amber warn.actions J1939 Amber Warning Lamp Actions: 40211
0- Disable
1- Warning Non-Latching
2- Warning (Alarm Only, No Shutdown)
3- Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
4- Shutdown (Alarm And Shutdown)

Amber warn.activation J1939 Amber Warning Lamp Activation: 40212


0- Active From Starting
1- Active From Safety On
2- Always Active

Amber warn.delay J1939 Amber Warning Lamp Delay 40213


Red stop actions J1939 Red Stop Lamp Actions: 40214
0- Disable
1- Warning Non-Latching
2- Warning (Alarm Only, No Shutdown)
3- Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
4- Shutdown (Alarm And Shutdown)

Red stop activation J1939 Red Stop Lamp Activation: 40215


0- Active From Starting
1- Active From Safety On
2- Always Active

Red stop delay J1939 Red Stop Lamp Delay 40216

8
ENGINE MAINTENANCE (Engine->Maintenance)
Running hour interval Running Hours Interval 40219
Maint.date interval Maintenance Date Interval 40220
Eng. stop when maint Force Engine Shutdown When Maintenance Is Due 40221
Eng.running hour(lsb) Engine Running Hour (Lsb) 40222
Eng.running hour Engine Running Hour 40223
Eng.running hour(msb) Engine Running Hour(Msb) 40224
Maintenance okay Maintenance Okay 40225

LOAD TEST (Engine->Load test)


Disable/enable select Disable, No Load or On Load Selection 40228

EXERCISE (Engine->Exercise)
Time of period Generator exercise working period on related day 40231
Week Generator exercise working day of week 40232
Start time Generator exercise work start time on related day 40233

ENGINE GENERAL (Engine->General)


Fuel selection Engine Fuel Selection 40236
Stop solenoid time Stop Solenoid Time 40237
Ignition delay Ignition Delay 40238
Gas valve delay Gas Valve Delay 40239
Min.of ignition speed Min Ignition Speed 40240
Choke time Choke Time 40241

9
2.5 Inputs

SENDER INPUTS (Inputs->Sender inputs)


Oil pressure unit Oil Pressure Unit 40244
Oil press. input type Oil Pressure Input Type 40245
Oil pressure prealarm Oil Pressure Pre-Alarm 40246
Oil pressure reset Oil Pressure Pre-Alarm Reset 40247
Oil pressure shutdown Oil Pressure Shutdown 40248
Temperature unit Coolant Temperature Unit 40249
Temp. input type Coolant Temperature Input Type 40250
High temp. prealarm High Temperature Pre-Alarm 40251
High temp. reset High Temp. Pre-Alarm Reset 40252
High temp. shutdown High Temperature Shutdown 40253
Low temp. warning Low Temperature Warning 40254
Heater control ON Coolant Heater Control On 40275
Heater control OFF Coolant Heater Control Off 40276
Conf. AI1 unit Configurable Analogue Input-1 Unit 40255
Conf. AI1 type Configurable Analogue Input-1 Type 40256
Conf. AI1 low prealrm Configurable Analogue Input-1 Low Pre-Alarm 40257
Conf. AI1 low reset Configurable Analogue Input-1 Low Reset 40258
Conf. AI1 low shutdwn Configurable Analogue Input-1 Low Shutdown 40259
Conf. AI1 high prealrm Configurable Analogue Input-1 High Pre-Alarm 40260
Conf. AI1 high reset Configurable Analogue Input-1 High Reset 40261
Conf. AI1 high shutdwn Configurable Analogue Input-1 High Shutdown 40262
Conf. AI1 control ON Configurable Analogue Input-1 Control On 40263
Conf. AI1 control OFF Configurable Analogue Input-1 Control Off 40264
Conf. AI2 unit Configurable Analogue Input-2 Unit 40265
Conf. AI2 type Configurable Analogue Input-2 Type 40266
Conf. AI2 low prealrm Configurable Analogue Input-2 Low Pre-Alarm 40267
Conf. AI2 low reset Configurable Analogue Input-2 Low Reset 40268
Conf. AI2 low shutdwn Configurable Analogue Input-2 Low Shutdown 40269
Conf. AI2 high prealrm Configurable Analogue Input-2 High Pre-Alarm 40270
Conf. AI2 high reset Configurable Analogue Input-2 High Reset 40271
Conf. AI2 high shutdwn Configurable Analogue Input-2 High Shutdown 40272
Conf. AI2 control ON Configurable Analogue Input-2 Control On 40273
Conf. AI2 control OFF Configurable Analogue Input-2 Control Off 40274

10
SENDER LINEARISATION (Inputs->Sender linearisation)
Oil pressure sender 1 Oil Pressure Sender Point-1 40279
Oil pressure 1 Oil Pressure Point-1 40280
Oil pressure sender 2 Oil Pressure Sender Point-2 40281
Oil pressure 2 Oil Pressure Point-2 40282
Oil pressure sender 3 Oil Pressure Sender Point-3 40283
Oil pressure 3 Oil Pressure Point-3 40284
Oil pressure sender 4 Oil Pressure Sender Point-4 40285
Oil pressure 4 Oil Pressure Point-4 40286
Oil pressure sender 5 Oil Pressure Sender Point-5 40287
Oil pressure 5 Oil Pressure Point-5 40288
Oil pressure sender 6 Oil Pressure Sender Point-6 40289
Oil pressure 6 Oil Pressure Point-6 40290
Oil pressure sender 7 Oil Pressure Sender Point-7 40291
Oil pressure 7 Oil Pressure Point-7 40292
Oil pressure sender 8 Oil Pressure Sender Point-8 40293
Oil pressure 8 Oil Pressure Point-8 40294
Oil pressure sender 9 Oil Pressure Sender Point-9 40295
Oil pressure 9 Oil Pressure Point-9 40296
Oil pressure sender 10 Oil Pressure Sender Point-10 40297
Oil pressure 10 Oil Pressure Point-10 40298
Temperature sender 1 Temperature Sender Point-1 40299
Temperature 1 Temperature Point-1 40300
Temperature sender 2 Temperature Sender Point-2 40301
Temperature 2 Temperature Point-2 40302
Temperature sender 3 Temperature Sender Point-3 40303
Temperature 3 Temperature Point-3 40304
Temperature sender 4 Temperature Sender Point-4 40305
Temperature 4 Temperature Point-4 40306
Temperature sender 5 Temperature Sender Point-5 40307
Temperature 5 Temperature Point-5 40308
Temperature sender 6 Temperature Sender Point-6 40309
Temperature 6 Temperature Point-6 40310
Temperature sender 7 Temperature Sender Point-7 40311
Temperature 7 Temperature Point-7 40312
Temperature sender 8 Temperature Sender Point-8 40313
Temperature 8 Temperature Point-8 40314
Temperature sender 9 Temperature Sender Point-9 40315
Temperature 9 Temperature Point-9 40316
Temperature sender 10 Temperature Sender Point-10 40317
Temperature 10 Temperature Point-10 40318
Conf. AI1 sender 1 Configurable Analogue Input-1 Sender Point-1 40319
Conf. AI1 value 1 Configurable Analogue Input-1 Point-1 40320
Conf. AI1 sender 2 Configurable Analogue Input-1 Sender Point-2 40321
Conf. AI1 value 2 Configurable Analogue Input-1 Point-2 40322
Conf. AI1 sender 3 Configurable Analogue Input-1 Sender Point-3 40323
Conf. AI1 value 3 Configurable Analogue Input-1 Point-3 40324
Conf. AI1 sender 4 Configurable Analogue Input-1 Sender Point-4 40325
Conf. AI1 value 4 Configurable Analogue Input-1 Point-4 40326
Conf. AI1 sender 5 Configurable Analogue Input-1 Sender Point-5 40327
Conf. AI1 value 5 Configurable Analogue Input-1 Point-5 40328

11
Conf. AI1 sender 6 Configurable Analogue Input-1 Sender Point-6 40329
Conf. AI1 value 6 Configurable Analogue Input-1 Point-6 40330
Conf. AI1 sender 7 Configurable Analogue Input-1 Sender Point-7 40331
Conf. AI1 value 7 Configurable Analogue Input-1 Point-7 40332
Conf. AI1 sender 8 Configurable Analogue Input-1 Sender Point-8 40333
Conf. AI1 value 8 Configurable Analogue Input-1 Point-8 40334
Conf. AI1 sender 9 Configurable Analogue Input-1 Sender Point-9 40335
Conf. AI1 value 9 Configurable Analogue Input-1 Point-9 40336
Conf. AI1 sender 10 Configurable Analogue Input-1 Sender Point-10 40337
Conf. AI1 value 10 Configurable Analogue Input-1 Point-10 40338
Conf. AI2 sender 1 Configurable Analogue Input-2 Sender Point-1 40339
Conf. AI2 value 1 Configurable Analogue Input-2 Point-1 40340
Conf. AI2 sender 2 Configurable Analogue Input-2 Sender Point-2 40341
Conf. AI2 value 2 Configurable Analogue Input-2 Point-2 40342
Conf. AI2 sender 3 Configurable Analogue Input-2 Sender Point-3 40343
Conf. AI2 value 3 Configurable Analogue Input-2 Point-3 40344
Conf. AI2 sender 4 Configurable Analogue Input-2 Sender Point-4 40345
Conf. AI2 value 4 Configurable Analogue Input-2 Point-4 40346
Conf. AI2 sender 5 Configurable Analogue Input-2 Sender Point-5 40347
Conf. AI2 value 5 Configurable Analogue Input-2 Point-5 40348
Conf. AI2 sender 6 Configurable Analogue Input-2 Sender Point-6 40349
Conf. AI2 value 6 Configurable Analogue Input-2 Point-6 40350
Conf. AI2 sender 7 Configurable Analogue Input-2 Sender Point-7 40351
Conf. AI2 value 7 Configurable Analogue Input-2 Point-7 40352
Conf. AI2 sender 8 Configurable Analogue Input-2 Sender Point-8 40353
Conf. AI2 value 8 Configurable Analogue Input-2 Point-8 40354
Conf. AI2 sender 9 Configurable Analogue Input-2 Sender Point-9 40355
Conf. AI2 value 9 Configurable Analogue Input-2 Point-9 40356
Conf. AI2 sender 10 Configurable Analogue Input-2 Sender Point-10 40357
Conf. AI2 value 10 Configurable Analogue Input-2 Point-10 40358

12
CONF. INPUT-1 (Inputs->Conf. input-1)
Dis,user conf.or list 0- Disable 40363
1- User Configured
2- Select From List
Polarity 0- Normally Open (Close To Activate) 40364
1- Normally Close (Open To Activate)
Indication If User Configured 40365
0- Status
1- Warning Non-Latching
2- Warning Latching
3- Electrical Trip
4- Shutdown
Activation If User Configured 40366
0- Active From Starting
1- Active From Safety On
2- Always Active
Select from list If Select From List 40367
0-Remote Start On Load
1-Remote Start Off Load
2-Auxiliary Mains Fail
3-Simulate Lamp Test Button
4-Simulate Horn Reset Button
5-Simulate Alarm Reset Button
6-Simulate Auto Button
7-Simulate Test Button
8-Simulate Manual Button
9-Simulate Start Button
10-Simulate Stop Button
11-Generator Closed Auxiliary
12-Generator Load Inhibit
13-Mains Closed Auxiliary
14-Mains Load Inhibit
15-Auto Restore Inhibit
16-Auto Start Inhibit
17-Panel Lock
18-Scheduled Runs Inhibited
19-Priority Select
20-Transfer To Generator/Open Mains
21-Transfer To Mains/Open Generator
22-Remote Inhibit
23-Being Found Alive
24-Generator is Loaded in STOP Mode
25-Emergency Stop (only conf. input-1)
25-Low Oil Pressure (only conf. input-4)
25-High Temperature (only conf. input-5)
26-Low Oil Level (only conf. input-4)

Active delay Input active delay 40368

CONF. INPUT-2 (Inputs->Conf. input-2)


Dis,user conf.or list The same as Config. Input-1 options 40371
Polarity The same as Config. Input-1 options 40372
Indication The same as Config. Input-1 options 40373
Activation The same as Config. Input-1 options 40374
Select from list The same as Config. Input-1 options 40375
Active delay The same as Config. Input-1 options 40376

13
CONF. INPUT-3 (Inputs->Conf. input-3)
Dis,user conf.or list The same as Config. Input-1 options 40379
Polarity The same as Config. Input-1 options 40380
Indication The same as Config. Input-1 options 40381
Activation The same as Config. Input-1 options 40382
Select from list The same as Config. Input-1 options 40383
Active delay The same as Config. Input-1 options 40384

CONF. INPUT-4 (Inputs->Conf. input-4)


Dis,user conf.or list The same as Config. Input-1 options 40387
Polarity The same as Config. Input-1 options 40388
Indication The same as Config. Input-1 options 40389
Activation The same as Config. Input-1 options 40390
Select from list The same as Config. Input-1 options 40391
Active delay The same as Config. Input-1 options 40392

CONF. INPUT-5 (Inputs->Conf. input-5)


Dis,user conf.or list The same as Config. Input-1 options 40395
Polarity The same as Config. Input-1 options 40396
Indication The same as Config. Input-1 options 40397
Activation The same as Config. Input-1 options 40398
Select from list The same as Config. Input-1 options 40399
Active delay The same as Config. Input-1 options 40400

CONF. INPUT-6 (Inputs->Conf. input-6)


Dis,user conf.or list The same as Config. Input-1 options 40403
Polarity The same as Config. Input-1 options 40404
Indication The same as Config. Input-1 options 40405
Activation The same as Config. Input-1 options 40406
Select from list The same as Config. Input-1 options 40407
Active delay The same as Config. Input-1 options 40408

14
CONF. INPUT-7 (Inputs->Conf. input-7)
Input type 0- Disable 40411
1- User Configured (Digital)
2- Select From List (Digital)
3- Cabin Temperature (Anolog)
Polarity If Input Type is Digital 40412
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
Indication If Input Type is User Configured 40413
0- Status
1- Warning Non-Latching
2- Warning Latching
3- Electrical Trip
4- Shutdown
Activation If Input Type is User Configured 40414
0- Active From Starting
1- Active From Safety On
2- Always Active
Select from list If Input Type is Select From List 40415
0-Remote Start On Load
1-Remote Start Off Load
2-Auxiliary Mains Fail
3-Simulate Lamp Test Button
4-Simulate Horn Reset Button
5-Simulate Alarm Reset Button
6-Simulate Auto Button
7-Simulate Test Button
8-Simulate Manual Button
9-Simulate Start Button
10-Simulate Stop Button
11-Generator Closed Auxiliary
12-Generator Load Inhibit
13-Mains Closed Auxiliary
14-Mains Load Inhibit
15-Auto Restore Inhibit
16-Auto Start Inhibit
17-Panel Lock
18-Scheduled Runs(Exercise) Inhibited
19-Priority Select
20-Transfer To Generator/Open Mains
21-Transfer To Mains/Open Generator
22-Remote Inhibit
23-Being Found Alive
24-Generator is loaded in stop mode

Active delay Input active delay (If Input Type is Digital) 40416
Cabin temp.low prealr Cabin temperature low prealarm 40417
Cabin temp.low reset Cabin temperature low prealarm reset 40418
Cabin temp.low shutd. Cabin temperature low shutdown 40427
Cabin temp.high preal Cabin temperature high prealarm reset 40436
Cabin temp.high reset Cabin temperature high prealarm 40445
Cabin temp.high shutd Cabin temperature high shutdown 40454

15
CONF. EXP. INPUT-1 (Inputs->Conf. exp. input-1)
Dis,user conf.or list 0- Disable 40419
1- User Configured
2- Select From List
Hardware type 0-> -Ve (Switched To Battery -) 40420
1-> +Ve (Switched To Battery +)
Polarity 0- Normally Open (Close To Activate) 40421
1- Normally Close (Open To Activate)
Indication If User Configured 40422
0- Status
1- Warning Non-Latching
2- Warning Latching
3- Electrical Trip
4- Shutdown
Activation If User Configured 40423
0- Active From Starting
1- Active From Safety On
2- Always Active
Select from list If Select From List 40424
2-Auxiliary Mains Fail
3-Simulate Lamp Test Button
4-Simulate Horn Reset Button
5-Simulate Alarm Reset Button
6-Simulate Auto Button
7-Simulate Test Button
8-Simulate Manual Button
9-Simulate Start Button
10-Simulate Stop Button
11-Generator Closed Auxiliary
12-Generator Load Inhibit
13-Mains Closed Auxiliary
14-Mains Load Inhibit
15-Auto Restore Inhibit
16-Auto Start Inhibit
17-Panel Lock
18-Scheduled Runs Inhibited
19-Reserved
20-Transfer To Generator/Open Mains
21-Transfer To Mains/Open Generator
Active delay Input active delay 40425

CONF. EXP. INPUT-2 (Inputs->Conf. exp. input-2)


Dis,user conf.or list The same as Expansion Config. Input-1 options 40428
Hardware type The same as Expansion Config. Input-1 options 40429
Polarity The same as Expansion Config. Input-1 options 40430
Indication The same as Expansion Config. Input-1 options 40431
Activation The same as Expansion Config. Input-1 options 40432
Select from list The same as Expansion Config. Input-1 options 40433
Active delay The same as Expansion Config. Input-1 options 40434

16
CONF. EXP. INPUT-3 (Inputs->Conf. exp. input-3)
Dis,user conf.or list The same as Expansion Config. Input-1 options 40437
Hardware type The same as Expansion Config. Input-1 options 40438
Polarity The same as Expansion Config. Input-1 options 40439
Indication The same as Expansion Config. Input-1 options 40440
Activation The same as Expansion Config. Input-1 options 40441
Select from list The same as Expansion Config. Input-1 options 40442
Active delay The same as Expansion Config. Input-1 options 40443

CONF. EXP. INPUT-4 (Inputs->Conf. exp. input-4)


Dis,user conf.or list The same as Expansion Config. Input-1 options 40446
Hardware type The same as Expansion Config. Input-1 options 40447
Polarity The same as Expansion Config. Input-1 options 40448
Indication The same as Expansion Config. Input-1 options 40449
Activation The same as Expansion Config. Input-1 options 40450
Select from list The same as Expansion Config. Input-1 options 40451
Active delay The same as Expansion Config. Input-1 options 40452

CONF. EXP. INPUT-5 (Inputs->Conf. exp. input-5)


Dis,user conf.or list The same as Expansion Config. Input-1 options 40455
Hardware type The same as Expansion Config. Input-1 options 40456
Polarity The same as Expansion Config. Input-1 options 40457
Indication The same as Expansion Config. Input-1 options 40458
Activation The same as Expansion Config. Input-1 options 40459
Select from list The same as Expansion Config. Input-1 options 40460
Active delay The same as Expansion Config. Input-1 options 40461

CONF. EXP. INPUT-6 (Inputs->Conf. exp. input-6)


Dis,user conf.or list The same as Expansion Config. Input-1 options 40464
Hardware type The same as Expansion Config. Input-1 options 40465
Polarity The same as Expansion Config. Input-1 options 40466
Indication The same as Expansion Config. Input-1 options 40467
Activation The same as Expansion Config. Input-1 options 40468
Select from list The same as Expansion Config. Input-1 options 40469
Active delay The same as Expansion Config. Input-1 options 40470

CONF. EXP. INPUT-7 (Inputs->Conf. exp. input-7)


Dis,user conf.or list The same as Expansion Config. Input-1 options 40473
Hardware type The same as Expansion Config. Input-1 options 40474
Polarity The same as Expansion Config. Input-1 options 40475
Indication The same as Expansion Config. Input-1 options 40476
Activation The same as Expansion Config. Input-1 options 40477
Select from list The same as Expansion Config. Input-1 options 40478
Active delay The same as Expansion Config. Input-1 options 40479

CONF. EXP. INPUT-8 (Inputs->Conf. exp. input-8)


Dis,user conf.or list The same as Expansion Config. Input-1 options 40482
Hardware type The same as Expansion Config. Input-1 options 40483
Polarity The same as Expansion Config. Input-1 options 40484
Indication The same as Expansion Config. Input-1 options 40485
Activation The same as Expansion Config. Input-1 options 40486
Select from list The same as Expansion Config. Input-1 options 40487
Active delay The same as Expansion Config. Input-1 options 40488
17
2.6 Outputs
CONF. OUTPUT-1 (Outputs->Conf. output-1)
Polarity 0- Normally Open (Close To Activate) 40491
1- Normally Close (Open To Activate)
0-NOT USED
Function 1-AIR FLAP CONTROL
2-ALARM RESET
40492
3-AUDIBLE ALARM
4-AUTO START INHIBIT
5-AUXILIARY MAINS FAILURE
6-BATTERY HIGH VOLTAGE
7-BATTERY LOW VOLTAGE
8-CALLING FOR SCHEDULED RUN
9-CAN ECU POWER
10-CAN ECU STOP
11-CHARGE ALTERNATOR FAILURE
12-COMMON ALARM
13-COMMON ELECTRICAL TRIP ALARM
14-COMMON SHUTDOWN ALARM
15-COMMON WARNING ALARM
16-COOLING FAN AFTER START
17-COOLING FAN AFTER STOP
18-COOLANT TEMPERATURE HIGH PRE-ALARM
19-COOLANT TEMPERATURE HIGH SHUTDOWN
20-COOLING DOWN TIMER IN PROGRESS
21-CRANK RELAY ENERGISED
22-DELAYED ALARMS ACTIVE
23-DIGITAL INPUT1 ALARM
24-DIGITAL INPUT2 ALARM
25-DIGITAL INPUT3 ALARM
26-DIGITAL INPUT4 ALARM
27-DIGITAL INPUT5 ALARM
28-DIGITAL INPUT6 ALARM
29-DIGITAL INPUT7 ALARM
30-EXPANSION INPUT1 ALARM
31-EXPANSION INPUT2 ALARM
32-EXPANSION INPUT3 ALARM
33-EXPANSION INPUT4 ALARM
34-EXPANSION INPUT5 ALARM
35-EXPANSION INPUT6 ALARM
36-EXPANSION INPUT7 ALARM
37-EXPANSION INPUT8 ALARM
38-EARTH FAULT
39-EMERGENCY STOP
40-FAIL TO START ALARM
41-FAIL TO STOP ALARM
42-CONF. AI1 CONTROL
43-FUEL RELAY ENERGISED
44-GAS ENGINE IGNITION OUTPUT
45-GENERATOR AT REST
46-GENERATOR AVAILABLE
47-GENERATOR CLOSED AUXILIARY
48-GENERATOR FAILED TO CLOSE
49-GENERATOR FAILED TO OPEN
50-GENERATOR HIGH FREQUENCY PRE-ALARM
51-GENERATOR HIGH FREQUENCY SHUTDOWN
52-GENERATOR HIGH VOLTAGE PRE-ALARM
53-GENERATOR HIGH VOLTAGE SHUTDOWN
54-GENERATOR LOAD INHIBIT
55-GENERATOR LOW FREQUENCY PRE-ALARM
56-GENERATOR LOW FREQUENCY SHUTDOWN
57-GENERATOR LOW VOLTAGE PRE-ALARM
58-GENERATOR LOW VOLTAGE SHUTDOWN
59-GENERATOR STOPPING
60-GENERATOR OPEN BREAKER
61-HORN OUTPUT LATCHED
62-HORN OUTPUT PULSED
63-LAMP TEST
64-CONF. AI2 CONTROL
65-LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
66-LOW TEMPERATURE
67-MAINTENANCE DUE ALARM
68-MAINS CLOSED AUXILIARY
69-MAINS FAILED TO CLOSE
70-MAINS FAILED TO OPEN
71-MAINS FAILURE
72-MAINS HIGH FREQUENCY
73-MAINS HIGH VOLTAGE
74-MAINS LOAD INHIBIT
75-MAINS LOW FREQUENCY
76-MAINS LOW VOLTAGE
77-MAINS OPEN BREAKER
78-NO LOADING COMMAND
79-OIL PRESSURE LOW PRE-ALARM
80-OIL PRESSURE LOW SHUTDOWN
81-CONF.AI1.HIGH PREA
82-CONF.AI1.HIGH SHUT
83-OVER CURRENT PRE-ALARM
84-OVER CURRENT
85-OVER POWER PRE-ALARM
86-OVER POWER SHUTDOWN
87-OVERSPEED PRE-ALARM
88-OVERSPEED SHUTDOWN
89-PANEL LOCK
90-PRE-HEAT(during preheat timer)
91-PRE-HEAT(until end of cranking)
92-PRE-HEAT(until end of warming)
93-PRE-HEAT(until end safety on)
94-REMOTE START PRESENT
95-REMOTE STOP DELAY IN PROGRESS
96-SHORT CIRCUIT
97-SMOKE LIMITING
98-STARTING ALARM
99-STARTING ALARMS ARMED
100-STOP RELAY ENERGISED
101-SYSTEM IN AUTO MODE
102-SYSTEM IN MANUAL MODE
103-SYSTEM IN STOP MODE
104-SYSTEM IN TEST MODE
105-UNDER CURRENT PRE-ALARM
106-UNDER CURRENT
107-UNDER POWER PRE-ALARM
108-UNDER POWER SHUTDOWN
109-UNDERSPEED PRE-ALARM
110-UNDERSPEED SHUTDOWN
111-WAITING FOR GENERATOR
112-DUAL COMMUNICATION ERROR
113-LOAD SUPPLY FROM GENERATOR
114-LOAD SUPPLY FROM MAINS
115-CONFIGURABLE ANALOG INPUT 1 LOW PRE-ALARM
116-CONFIGURABLE ANALOG INPUT 1 LOW SHUTDOWN
117-CONFIGURABLE ANALOG INPUT 2 LOW PRE-ALARM
118-CONFIGURABLE ANALOG INPUT 2 LOW SHUTDOWN
119-CONFIGURABLE ANALOG INPUT 2 HIGH PRE-ALARM
120-CONFIGURABLE ANALOG INPUT 2 HIGH SHUTDOWN
121-CHOKE ACTIVE
122-REMOTE CONTROL ACTIVE
123-REVERSE POWER
124-CABIN TEMPERATURE LOW PRE-ALARM
125-CABIN TEMPERATURE LOW SHUTDOWN
126-CABIN TEMPERATURE HIGH PRE-ALARM
127-CABIN TEMPERATURE HIGH SHUTDOWN
128-HEATER CONTROL
129-REMOTE OUTPUT

18
CONF. OUTPUT-2 (Outputs->Conf. output-2)
Polarity 0- Normally Open (Close To Activate) 40495
1- Normally Close (Open To Activate)

Function The same as Configurable Output-1 options 40496

CONF. OUTPUT-3 (Outputs->Conf. output-3)


Polarity 0- Normally Open (Close To Activate) 40499
1- Normally Close (Open To Activate)

Function The same as Configurable Output-1 options 40500

CONF. OUTPUT-4 (Outputs->Conf. output-4)


Polarity 0- Normally Open (Close To Activate) 40503
1- Normally Close (Open To Activate)

Function The same as Configurable Output-1 options 40504

CONF. OUTPUT-5 (Outputs->Conf. output-5)


Polarity 0- Normally Open (Close To Activate) 40507
1- Normally Close (Open To Activate)

Function The same as Configurable Output-1 options 40508

CONF. OUTPUT-6 (Outputs->Conf. output-6)


Polarity 0- Normally Open (Close To Activate) 40511
1- Normally Close (Open To Activate)

Function The same as Configurable Output-1 options 40512

CONF. EXP. OUTPUT-1 (Outputs->Conf. exp. output-1)


Polarity 0- Normally Open (Close To Activate) 40515
1- Normally Close (Open To Activate)

Function The same as Configurable Output-1 options 40516

CONF. EXP. OUTPUT-2 (Outputs->Conf. exp. output-2)


Polarity 0- Normally Open (Close To Activate) 40519
1- Normally Close (Open To Activate)

Function The same as Configurable Output-1 options 40520

CONF. EXP. OUTPUT-3 (Outputs->Conf. exp. output-3)


Polarity 0- Normally Open (Close To Activate) 40523
1- Normally Close (Open To Activate)

Function The same as Configurable Output-1 options 40524

CONF. EXP. OUTPUT-4 (Outputs->Conf. exp. output-4)


Polarity 0- Normally Open (Close To Activate) 40527
1- Normally Close (Open To Activate)

Function The same as Configurable Output-1 options 40528

CONF. EXP. OUTPUT-5 (Outputs->Conf. exp. output-5)


Polarity 0- Normally Open (Close To Activate) 40531
1- Normally Close (Open To Activate)

Function The same as Configurable Output-1 options 40532

CONF. EXP. OUTPUT-6 (Outputs->Conf. exp. output-6)


Polarity 0- Normally Open (Close To Activate) 40535
1- Normally Close (Open To Activate)

Function The same as Configurable Output-1 options 40536

19
CONF. EXP. OUTPUT-7 (Outputs->Conf. exp. output-7)
Polarity 0- Normally Open (Close To Activate) 40539
1- Normally Close (Open To Activate)

Function The same as Configurable Output-1 options 40540

CONF. EXP. OUTPUT-8 (Outputs->Conf. exp. output-8)


Polarity 0- Normally Open (Close To Activate) 40543
1- Normally Close (Open To Activate)

Function The same as Configurable Output-1 options 40544

2.7 Timers
START TIMERS (Timers->Start timers)
Mains transient delay Mains Transient Delay 40547
Mains fail start dely Mains Fail Start Delay 40548
Remote start delay Remote Start Delay 40549
Pre-heat Pre-Heat 40550
Pre-heat bypass Pre-Heat Bypass 40551
Safety on delay Safety On Delay 40552
Warming up time Warmup Time 40553
Horn duration Horn Duration 40554
Chg. excitation time Charge Excitation Time 40555
Cooling fan time Cooling Fan Time 40556
Idle mode time Idle Mode Time (Smoke Limiting) 40557
Idle mode time off Idle Mode Time Off (Smoke Limiting Off) 40558

STOPPING TIMERS (Timers->Stopping timers)


Mains return delay Mains Return Delay 40563
Remote stop delay Remote Stop Delay 40564
Cooling time Cooling Time 40565
Fail to stop delay Fail To Stop Time 40566

2.8 Expansion Modules


IO (1-8) MODULE (Expansion modules->IO (1-8))
Disable/enable select Expansion I/O Module Selection 40571

DIAL-UP & ETHERNET (Expansion modules->Dial-up & Ethernet)


Disable/enable select Expansion Dal-up&Ethernet Module Selection 40576
Call back selection Call Back Selection 40577

GSM MODULE (Expansion modules->GSM)


Disable/enable select Expansion GSM Module Selection 40582
Call back selection Call Back Selection 40583
SMS SMS Feature Enable or Disable 40584

GPRS MODULE (Expansion modules->GPRS)


Disable/enable select Expansion GPRS Module Selection 40589
Call back selection Call Back Selection 40590

20
DUAL SET MODULE (Expansion modules->Dual set)
Disable/enable select Expansion Dual Set Module Selection 40595
Node ID Device Address 40596
Working period Dual Working Period 40597
Early start time Early Start Time 40598
Remote priority selct Remote Priority Selection: 40599
0- Pasive, 1- High Priority, 2- Low Priority

WEB SERVER MODULE (Expansion modules->Web server)


Disable/enable select Expansion Web Server Module Selection 40605

2.9 User Adjustment


MAINS VOLTAGE OFFSET (User adjustment->Mains volt offset)
Mains V1 offset Mains V1 Offset 40612
Mains V2 offset Mains V2 Offset 40613
Mains V3 offset Mains V3 Offset 40614

GEN. VOLTAGE OFFSET (User adjustment->Gen. volt offset)


Gen. V1 offset Generator V1 Offset 40621
Gen. V2 offset Generator V2 Offset 40622
Gen. V3 offset Generator V3 Offset 40623

CURRENT OFFSET (User adjustment->Current offset)


Current I1 offset Current I1 Offset 40630
Current I2 offset Current I2 Offset 40631
Current I3 offset Current I3 Offset 40632
E/F. Current offset Earth current I3 Offset 40633

BATTERY&CHRG GEN.VOL (User adjustment->Bat.&gen.chg.V.offset)


Batt.volt offset Battery Voltage Offset 40640
Gen.chg.volt offset Charge Generator Voltage Offset 40641

SENDER INPUTS OFFSET (User adjustment->Sender inputs offset)


Oil Pressure offset Oil Pressure Offset 40648
Temperature offset Coolant Temperature Offset 40649
Conf. AI1 offset Configurable Analogue Input-1 Offset 40650
Conf. AI2 offset Configurable Analogue Input-2 Offset 40651

21
Example-1: To read the "Nominal Alternator Frequency" parameter's value;
Slave ID: 1
Command: 3 (Read Holding Register)
Register Address: 95 (Nominal Alternator Frequency)
Register Count: 1
ASCII DECIMAL HEX
Start Character : 58 0x3A Start Character
Slave ID high nibble 0 48 0x30
Device Slave ID
Slave ID low nibble 1 49 0x31
Command high nibble 0 48 0x30
03 = Read Holding Register Command
Command low nibble 3 52 0x34
Register Address MSB high nibble 0 48 0x30
Register Address MSB low nibble 0 48 0x30 Nominal Alternator Frequency Register Address
(00095 – 1 = 94 / 256 = 0 = 00 MSB)
Register Address LSB high nibble 5 53 0x35 (94 < 256 = 94 = 5E LSB)
Register Address LSB low nibble E 69 0x45
Register Count MSB high nibble 0 48 0x30
1 / 256 = 0 = 00
Register Count MSB low nibble 0 48 0x30
Register Count LSB high nibble 0 48 0x30
1 < 256 = 1 = 01
Register Count LSB low nibble 1 49 0x31
LRC MSB 9 57 0x39 1 + 3 + 5E + 1 =1+3+94+1 = 99
99 < 256 = 99
LRC LSB D 68 0x44 (99 ^ 255)+1= 157 = 9D
13 CR 13 0xD
Stop Characters
10 LF 10 0xA
ASCII :0103005E00019DCRLF

Example-2: To change the "CT Ratio" parameter's value;


Slave ID: 1
Command: 6 (Preset Single Register)
Register Address: 1 (CT Ratio)
Data: 300

ASCII DECIMAL HEX


Start Character : 58 0x3A Start Character
Slave ID high nibble 0 48 0x30
Device Slave ID
Slave ID low nibble 1 49 0x31
Command high nibble 0 48 0x30
06 = Preset Single Register Command
Command low nibble 6 54 0x36
Register Address MSB high nibble 0 48 0x30
Register Address MSB low nibble 0 48 0x30 CT Ratio Register Address
(00001 – 1 = 0 / 256 = 0 = 00 MSB)
Register Address LSB high nibble 0 48 0x30 (0 < 256 = 0 = 00 LSB)
Register Address LSB low nibble 0 48 0x30
Data MSB high nibble 0 48 0x30
300 / 256 = 1 = 01
Data MSB low nibble 1 49 0x31
Data LSB high nibble 2 50 0x32
300 - 256 = 44 = 2C
Data LSB low nibble C 67 0x43
LRC MSB C 67 0x43 1 + 6 + 1 + 2C =1+6+1+44 = 52
52 < 256 = 52
LRC LSB C 67 0x43 (52^255)+1= 204 = CC
13 CR 13 0xD
Stop Characters
10 LF 10 0xA
ASCII :01060000012CCCCRLF

22
Device Type and Revision Number Bits
Description Address--Bit
Device Type 30053--(9-15 bits). If the value of these bits is 64,
the unit is "TRANS-AMF".
Device Revision 30053--(0-7 bits).

Observation Values
Description Unit Address

Generator frequency Hz 30001


Mains frequency Hz 30002
Engine speed RPM 30003
Conf. AI2 sender ºC 30004
Number of engine runs - 30005
Number of engine starts - 30006
Oil pressure sender Bar 30007
Coolant temperature sender ºC 30008
Conf. AI1 sender % 30009
Battery voltage Vdc 30010
Charge alternator voltage Vdc 30011
Year - 30012
Month, day - Month:Day = 30013(MSB): 30013(LSB)
Hour, minute - Hour:Min = 30014(MSB): 30014(LSB)
Engine working hour Hour 30015-30016
Load current IL1 A 30017
Load current IL2 A 30018
Load current IL3 A 30019
Earth current A 30020
Mains voltage L1N Vac 30021
Mains voltage L2N Vac 30022
Mains voltage L3N Vac 30023
Mains voltage L12 Vac 30024
Mains voltage L23 Vac 30025
Mains voltage L31 Vac 30026
Generator voltage L1N Vac 30027
Generator voltage L2N Vac 30028
Generator voltage L3N Vac 30029
Generator voltage L12 Vac 30030
Generator voltage L23 Vac 30031
Generator voltage L31 Vac 30032
Generator power factor PF1 - 30042-30043
Generator power factor PF2 - 30044-30045
Generator power factor PF3 - 30046-30047
Engine working minute Min. 30049
Next maintenance hour - 30051
Next maintenance month - 30052
Generator apparent power S1 kVA 30054-30055
Generator apparent power S2 kVA 30056-30057
Generator apparent power S3 kVA 30058-30059
Generator total apparent power kVA 30060-30061
23
Description Unit Address

Generator active power P1 kW 30062-30063


Generator active power P2 kW 30064-30065
Generator active power P3 kW 30066-30067
Generator total active power kW 30068-30069
Generator reactive power Q1 kVAr 30070-30071
Generator reactive power Q2 kVAr 30072-30073
Generator reactive power Q3 kVAr 30074-30075
Generator total reactive power kVAr 30076-30077
Generator active energy kWh 30078-30079-30080-30081
Generator reactive energy kVArh 30082-30083-30084-30085
Engine speed (J1939) RPM 30087
Oil pressure (J1939) Bar 30088
Coolant temperature (J1939) ºC 30089
Fuel rate (J1939) L/h 30090-30091
Fuel total used (J1939) L 30092-30093
Oil level (J1939) % 30094
Coolant level (J1939) % 30095
Load at current speed (J1939) % 30096
Fuel temperature (J1939) ºC 30097
Oil temperature (J1939) ºC 30098-30099
Actual engine torque (J1939) % 300100
Boost pressure (J1939) Bar 300101
Intake manifold temperature (J1939) ºC 300102
Accelerat. Pedal position (J1939) % 300103
Engine working hour (J1939) - 300104-30105
Engine working minute (J1939) - 300106
DM1 faults SPN1 (J1939) - 30107-30108
DM1 faults SPN2 (J1939) - 30109-30110
DM1 faults SPN3 (J1939) - 30111-30112
DM1 faults SPN4 (J1939) - 30113-30114
DM1 faults SPN5 (J1939) - 30115-30116
DM1 faults SPN6 (J1939) - 30117-30118
DM1 faults SPN7 (J1939) - 30119-30120
DM1 faults SPN8 (J1939) - 30121-30122
DM1 faults SPN9 (J1939) - 30123-30124
DM1 faults SPN10 (J1939) - 30125-30126
DM1 faults FMI1 (J1939) - 30127
DM1 faults FMI2 (J1939) - 30128
DM1 faults FMI3 (J1939) - 30129
DM1 faults FMI4 (J1939) - 30130
DM1 faults FMI5 (J1939) - 30131
DM1 faults FMI6 (J1939) - 30132
DM1 faults FMI7 (J1939) - 30133
DM1 faults FMI8 (J1939) - 30134
DM1 faults FMI9 (J1939) - 30135
DM1 faults FMI10 (J1939) - 30136
DM1 faults OC1 (J1939) - 30137
DM1 faults OC2 (J1939) - 30138
DM1 faults OC3 (J1939) - 30139
DM1 faults OC4 (J1939) - 30140
24
Description Unit Address

DM1 faults OC5 (J1939) - 30141


DM1 faults OC6 (J1939) - 30142
DM1 faults OC7 (J1939) - 30143
DM1 faults OC8 (J1939) - 30144
DM1 faults OC9 (J1939) - 30145
DM1 faults OC10 (J1939) - 30146
Cabin temperature ºC 30235

Example-3: To read the "Mains Voltage L1N" analogue measurement value;


Slave ID: 1
Command: 4 (Read Input Register)
Register Address: 21 (Mains Voltage L1N)
Register Count: 1
ASCII DECIMAL HEX
Start Character : 58 0x3A Start Character
Slave ID high nibble 0 48 0x30
Device Slave ID
Slave ID low nibble 1 49 0x31
Command high nibble 0 48 0x30
04 = Read Input Register Command
Command low nibble 4 52 0x34
Register Address MSB high nibble 0 48 0x30
Register Address MSB low nibble 0 48 0x30 Mains Voltage L1N Register Address
(00021 – 1 = 20 / 256 = 0 = 00 MSB)
Register Address LSB high nibble 1 49 0x31 (20 < 256 = 20 = 14 LSB)
Register Address LSB low nibble 4 52 0x34
Register Count MSB high nibble 0 48 0x30
1 / 256 = 0 = 00
Register Count MSB low nibble 0 48 0x30
Register Count LSB high nibble 0 48 0x30
1 < 256 = 1 = 01
Register Count LSB low nibble 1 49 0x31
LRC MSB E 69 0x45 1 + 4 + 14 + 1 =1+4+20+1 = 26
26 < 256 = 26
LRC LSB 6 54 0x36 (26^255)+1= 230 = E6
13 CR 13 0xD
Stop Characters
10 LF 10 0xA
ASCII :010400140001E6CRLF

25
Warning and Alarm Bits

Bit Description Address--Bit

Charge alternator failure 30033--0


Generator under frequency error 30033--1
Generator over frequency error 30033--2
High coolant temperature 30033--3
Generator under voltage error 30033--4
Generator over voltage error 30033--5
Low oil pressure 30033--6
Failed to start 30033--7
Conf. AI2 high error 30033--8
Generator phase sequence fail 30033--9
Under power error 30033--10
Over power error 30033--11
Oil pressure sensor error 30033--12
Temperature sensor error 30033--13
Conf. AI1 sensor error 30033--14
Conf. AI2 sensor error 30033--15

Over current electrical trip 30034--0


Reverse power electrical trip 30034--1
Earth current electrical trip 30034--2
Under current electrical trip 30034--3
Generator breaker not opened alarm 30034--4
Generator breaker not closed alarm 30034--5
Mains breaker not opened alarm 30034--6
Mains breaker not closed alarm 30034--7

High coolant temperature prealarm 30035--0


Low oil pressure prealarm 30035--1
Conf. AI1 low prealarm 30035--2
Generator under voltage prealarm 30035--3
Generator over voltage prealarm 30035--4
Generator under frequency prealarm 30035--5
Generator over frequency prealarm 30035--6
Under speed prealarm 30035--7
Over speed prealarm 30035--8
Battery voltage high prealarm 30035--9
Battery voltage low prealarm 30035--10
Over current warning 30035--11
Conf. AI1 high prealarm 30035--12
Earth current warning 30035--13
Low coolant temperature warning 30035--14
Maintenance warning 30035--15

26
Bit Description Address--Bit

Emergency stop error 30036--0


Generator stop error 30036--1
Reverse power error 30036--2
Cabin temperature low error 30036--3
Cabin temperature high error 30036--4
Pickup signal loss error 30036--5
Conf. AI1 low error 30036--6
Over speed error 30036--7
Under speed error 30036--8
Conf. AI2 low error 30036--9
Conf. AI1 high error 30036--10
Over current error 30036--11
Short circuit error 30036--12
Earth fault error 30036--13
Under current error 30036--14
Maintenance error 30036--15

Service alarm led-1 30038--5


Yellow alarm led-1 30038--6
Red alarm led-1 30038--7
Exp. I/O module spare-1 error 30038--8
Exp. I/O module spare-2 error 30038--9
Exp. I/O module spare-3 error 30038--10
Exp. I/O module spare-4 error 30038--11
Exp. I/O module spare-5 error 30038--12
Exp. I/O module spare-6 error 30038--13
Exp. I/O module spare-7 error 30038--14
Exp. I/O module spare-8 error 30038--15

Service alarm led-2 30039--5


Yellow alarm led-2 30039--6
Red alarm led-2 30039--7

Spare-1 error 30040--0


Spare-2 error 30040--1
Spare-3 error 30040--2
Spare-7 error 30040--3
Spare-6 error 30040--4
Spare-4 error 30040--6
Spare-5 error 30040--7
Service alarm led-3 30040--13
Yellow alarm led-3 30040--14
Red alarm led-3 30040--15

Canbus communication error 30041--0


J1939 amber warning lamp 30041--1
J1939 red stop lamp 30041--2

27
Bit Description Address--Bit

Conf. Ai2 high prealarm 30048--0


Under current prealarm 30048--1
Under current alarm 30048--2
Over current prealarm 30048--3
Under power prealarm 30048--4
Over power prealarm 30048--5
Dual communication error 30048--6
Conf. Ai2 low prealarm 30048--7
Reverse power alarm 30048--8
Cabin temperature low prealarm 30048--9
Cabin temperature high prealarm 30048--10

Outputs Status Bits


Bit Description Address--Bit
Generator contactor output 30037--0
Mains contactor output 30037--1
Configurable output-1 30037--2
Configurable output-2 30037--3
Configurable output-3 30037--4
Configurable output-4 30037--5
Configurable output-5 30037--6
Configurable output-6 30037--7

Exp. I/O module configurable output-1 30039--8


Exp. I/O module configurable output-2 30039--9
Exp. I/O module configurable output-3 30039--10
Exp. I/O module configurable output-4 30039--11
Exp. I/O module configurable output-5 30039--12
Exp. I/O module configurable output-6 30039--13
Exp. I/O module configurable output-7 30039--14
Exp. I/O module configurable output-8 30039--15

Operation Mode, Generator, Mains and Load Status Bits


Bit Description Address--Bit
Stop mode 30038--1
Manual mode 30038--2
Automatic mode 30039--3
Test mode 30040--11

Generator start 30039--1


Generator running 30040--10
Generator can take load 30039--2

Mains okay 30040--12

Load supply from mains 30038--4


Load supply from generator 30039--4

28
Optional Expansion Modules Status Bits
Bit Description Address--Bit
Ethernet module plugged 30041--8
GSM module plugged 30041--9
GPRS module plugged 30041--10
Dual set module plugged 30041--12
Web server module plugged 30041--13

Generator Control, Load Control and Changing Operation Mode Bits


Bit Description Address--Bit
Start button 60761--0
Stop button 60761--1
Reset button 60761--2
Automatic mode button 60761--4
Test mode button 60761--5
Manual mode button 60761--6
Mains contactor close button 60761--7
Mains contactor open button 60761--8
Generator contactor close button 60761--9
Generator contactor open button 60761--10

Example-4: To change the "Operation Mode" to Manual mode;


Slave ID: 1
Command: 6 (Preset Single Register)
Register Address: 761--6 (Manual button bit)
Data: 1 (related bit)

ASCII DECIMAL HEX


Start Character : 58 0x3A Start Character
Slave ID high nibble 0 48 0x30
Device Slave ID
Slave ID low nibble 1 49 0x31
Command high nibble 0 48 0x30
06 = Preset Single Register Command
Command low nibble 6 54 0x36
Register Address MSB high nibble 0 48 0x30
Register Address MSB low nibble 2 50 0x32 Manual Button Bit Register Address
(00761 – 1 = 760 / 256 = 2 = 02 MSB)
Register Address LSB high nibble F 70 0x46 (760 - (256*2) = 248 = F8 LSB)
Register Address LSB low nibble 8 56 0x38
Data MSB high nibble 0 48 0x30 6. bit = 0100 0000 = 64
Data MSB low nibble 0 48 0x30 64 / 256= 0 = 00
Data LSB high nibble 4 52 0x34 6. bit = 0100 0000 = 64
Data LSB low nibble 0 48 0x30 64 < 256 = 64 = 40
LRC MSB B 66 0x42 1 + 6 + 2 + F8 + 40 =1+6+2+248+64 = 321
321 – 256 = 65
LRC LSB F 70 0x46 (65^255)+1= 191 = BF
13 CR 13 0xD
Stop Characters
10 LF 10 0xA
ASCII :010602F80040BFCRLF

29