Trans Series, M
Trans Series, M
1.2 Generator
1
GEN POWER LEVEL (Generator->Power level)
Under power shutdown Generator Under Power Shutdown 40123
Under power prealarm Generator Under Power Pre-Alarm 40124
Under power reset Generator Under Power Pre-Alarm Reset 40125
Over power shutdown Generator Over Power Shutdown 40126
Over power prealarm Generator Over Power Pre-Alarm 40127
Over power reset Generator Over Power Pre-Alarm Reset 40128
Shutdown delay time Generator Power Shutdown Delay Time 40129
Reverse power set Reverse Power Set 40130
2. Technician Parameters
2.1 System
2
BREAKERS (System->Breakers)
Type of Breaker Hardware Breaker Selection 40011
Gen.brk.cls.contact Gen Close Breaker Contact Type 40012
Gen.brk.cls.relay Gen Close Breaker Relay Type 40013
Gen.brk.cls.time Gen Close Timer 40014
Gen.brk.open relay Gen Open Breaker Relay Type 40015
Gen.brk.open time Gen Open Timer 40016
Mains.brk.cls.contact Mains Close Breaker Contact Type 40017
Mains.brk.cls.relay Mains Close Breaker Relay Type 40018
Mains.brk.cls.time Mains Close Timer 40019
Mains.brk.open relay Mains Open Breaker Relay Type 40020
Mains.brk.open time Mains Open Timer 40021
Break.close puls.time Breaker Close Pulse Time 40022
Break.open pulse time Breaker Open Pulse Time 40023
Transfer time Transfer Time 40024
Spring loading time Spring Loading Time 40025
Retry number Retry Number 40026
COMMUNICATION (System->Communication)
Slave address Slave Address 40040
Baud Rate 40041
0 - 1200 baud
Baud rate 1 - 2400 baud
2 - 4800 baud
3 - 9600 baud
4 - 19200 baud
5 - 38400 baud
Parity Parity 40042
0 - NONE
1 - ODD
2 - EVEN
Stop bit Stop Bit (0-> 1 stop bit,1-> 2 stop bit) 40043
3
DEFAULT SETTINGS (System->Default settings)
Save setting to def. Save setting to default 40055
Reset default sets Reset default sets 40056
Reset factory sets Reset factory sets 40057
2.2 Mains
MAINS VOLT LEVEL (Mains->Volt level)
Under volt trip Mains Under Voltage 40066
Under volt reset Mains Under Voltage Reset 40067
Over volt trip Mains Over Voltage 40068
Over volt reset Mains Over Voltage Reset 40069
2.3 Generator
4
GEN CUR LEVEL & ACT (Generator->Current level & act.)
Under cur. set Generator Under Current Set 40106
Under cur. prealarm Generator Under Current Pre-Alarm 40107
Under cur. reset Generator Under Current Pre-Alarm Reset 40108
Under cur. act. Generator Under Current Actions 40109
0 - Disable
1 - Warning (Alarm Only, No Shutdown)
2 - Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
3 - Shutdown (Alarm And Shutdown)
Under act. delay time Generator Under Current Actions Delay Time 40110
Over cur. set Generator Over Current Set 40111
Over cur. prealarm Generator Over Current Pre-Alarm 40112
Over cur. reset Generator Over Current Pre-Alarm Reset 40113
Over cur. act. Generator Over Current Actions 40114
0 - Disable
1 - Warning (Alarm Only, No Shutdown)
2 - Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
3 - Shutdown (Alarm And Shutdown)
Over act. delay time Generator Over Current Actions Delay Time 40115
Short circuit cur. Generator Short Circuit Current Set 40116
Earth fault cur. Generator Earth Fault Current Set 40117
Earth fault cur. act. Generator Earth Fault Current Actions 40118
0 - Disable
1 - Warning (Alarm Only, No Shutdown)
2 - Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
3 - Shutdown (Alarm And Shutdown)
E.F. act. delay time Generator Earth Fault Current Actions Delay Time 40119
5
GEN WORKING CALENDAR (Generator->Working calendar)
Disable/enable select Working Calendar Disable or Enable 40133
Start time on monday Working Calendar Work Start Time on Monday 40134
Stop time on monday Working Calendar Work Stop Time on Monday 40135
Start time on tues. Working Calendar Work Start Time on Tuesday 40136
Stop time on tuesday Working Calendar Work Stop Time on Tuesday 40137
Start time on wednes. Working Calendar Work Start Time on Wednesday 40138
Stop time on wednes. Working Calendar Work Stop Time on Wednesday 40139
Start time on thurs. Working Calendar Work Start Time on Thursday 40140
Stop time on thursday Working Calendar Work Stop Time on Thursday 40141
Start time on friday Working Calendar Work Start Time on Friday 40142
Stop time on friday Working Calendar Work Stop Time on Friday 40143
Start time on satur. Working Calendar Work Start Time on Saturday 40144
Stop time on saturday Working Calendar Work Stop Time on Saturday 40145
Start time on sunday Working Calendar Work Start Time on Sunday 40146
Stop time on sunday Working Calendar Work Stop Time on Sunday 40147
2.4 Engine
6
ENGINE PLANT BATTERY (Engine->Plant battery)
Under volt Battery Undervolts Warning 40186
Under volt reset Battery Undervolts Warning Reset 40187
Under volt delay Battery Undervolts Volts Delay 40188
Over volt Battery Overvolts Warning 40189
Over volt reset Battery Overvolts Warning Reset 40190
Over volt delay Battery Overvolts Delay 40191
Alt. chg. warning Charge Alternator Warning 40192
7
CANBUS ERROR SET (Engine->CanBus error set)
CAN fault actions Can Fault Actions: 40208
0- Disable
1- Warning Non-Latching
2- Warning (Alarm Only, No Shutdown)
3- Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
4- Shutdown (Alarm And Shutdown)
8
ENGINE MAINTENANCE (Engine->Maintenance)
Running hour interval Running Hours Interval 40219
Maint.date interval Maintenance Date Interval 40220
Eng. stop when maint Force Engine Shutdown When Maintenance Is Due 40221
Eng.running hour(lsb) Engine Running Hour (Lsb) 40222
Eng.running hour Engine Running Hour 40223
Eng.running hour(msb) Engine Running Hour(Msb) 40224
Maintenance okay Maintenance Okay 40225
EXERCISE (Engine->Exercise)
Time of period Generator exercise working period on related day 40231
Week Generator exercise working day of week 40232
Start time Generator exercise work start time on related day 40233
9
2.5 Inputs
10
SENDER LINEARISATION (Inputs->Sender linearisation)
Oil pressure sender 1 Oil Pressure Sender Point-1 40279
Oil pressure 1 Oil Pressure Point-1 40280
Oil pressure sender 2 Oil Pressure Sender Point-2 40281
Oil pressure 2 Oil Pressure Point-2 40282
Oil pressure sender 3 Oil Pressure Sender Point-3 40283
Oil pressure 3 Oil Pressure Point-3 40284
Oil pressure sender 4 Oil Pressure Sender Point-4 40285
Oil pressure 4 Oil Pressure Point-4 40286
Oil pressure sender 5 Oil Pressure Sender Point-5 40287
Oil pressure 5 Oil Pressure Point-5 40288
Oil pressure sender 6 Oil Pressure Sender Point-6 40289
Oil pressure 6 Oil Pressure Point-6 40290
Oil pressure sender 7 Oil Pressure Sender Point-7 40291
Oil pressure 7 Oil Pressure Point-7 40292
Oil pressure sender 8 Oil Pressure Sender Point-8 40293
Oil pressure 8 Oil Pressure Point-8 40294
Oil pressure sender 9 Oil Pressure Sender Point-9 40295
Oil pressure 9 Oil Pressure Point-9 40296
Oil pressure sender 10 Oil Pressure Sender Point-10 40297
Oil pressure 10 Oil Pressure Point-10 40298
Temperature sender 1 Temperature Sender Point-1 40299
Temperature 1 Temperature Point-1 40300
Temperature sender 2 Temperature Sender Point-2 40301
Temperature 2 Temperature Point-2 40302
Temperature sender 3 Temperature Sender Point-3 40303
Temperature 3 Temperature Point-3 40304
Temperature sender 4 Temperature Sender Point-4 40305
Temperature 4 Temperature Point-4 40306
Temperature sender 5 Temperature Sender Point-5 40307
Temperature 5 Temperature Point-5 40308
Temperature sender 6 Temperature Sender Point-6 40309
Temperature 6 Temperature Point-6 40310
Temperature sender 7 Temperature Sender Point-7 40311
Temperature 7 Temperature Point-7 40312
Temperature sender 8 Temperature Sender Point-8 40313
Temperature 8 Temperature Point-8 40314
Temperature sender 9 Temperature Sender Point-9 40315
Temperature 9 Temperature Point-9 40316
Temperature sender 10 Temperature Sender Point-10 40317
Temperature 10 Temperature Point-10 40318
Conf. AI1 sender 1 Configurable Analogue Input-1 Sender Point-1 40319
Conf. AI1 value 1 Configurable Analogue Input-1 Point-1 40320
Conf. AI1 sender 2 Configurable Analogue Input-1 Sender Point-2 40321
Conf. AI1 value 2 Configurable Analogue Input-1 Point-2 40322
Conf. AI1 sender 3 Configurable Analogue Input-1 Sender Point-3 40323
Conf. AI1 value 3 Configurable Analogue Input-1 Point-3 40324
Conf. AI1 sender 4 Configurable Analogue Input-1 Sender Point-4 40325
Conf. AI1 value 4 Configurable Analogue Input-1 Point-4 40326
Conf. AI1 sender 5 Configurable Analogue Input-1 Sender Point-5 40327
Conf. AI1 value 5 Configurable Analogue Input-1 Point-5 40328
11
Conf. AI1 sender 6 Configurable Analogue Input-1 Sender Point-6 40329
Conf. AI1 value 6 Configurable Analogue Input-1 Point-6 40330
Conf. AI1 sender 7 Configurable Analogue Input-1 Sender Point-7 40331
Conf. AI1 value 7 Configurable Analogue Input-1 Point-7 40332
Conf. AI1 sender 8 Configurable Analogue Input-1 Sender Point-8 40333
Conf. AI1 value 8 Configurable Analogue Input-1 Point-8 40334
Conf. AI1 sender 9 Configurable Analogue Input-1 Sender Point-9 40335
Conf. AI1 value 9 Configurable Analogue Input-1 Point-9 40336
Conf. AI1 sender 10 Configurable Analogue Input-1 Sender Point-10 40337
Conf. AI1 value 10 Configurable Analogue Input-1 Point-10 40338
Conf. AI2 sender 1 Configurable Analogue Input-2 Sender Point-1 40339
Conf. AI2 value 1 Configurable Analogue Input-2 Point-1 40340
Conf. AI2 sender 2 Configurable Analogue Input-2 Sender Point-2 40341
Conf. AI2 value 2 Configurable Analogue Input-2 Point-2 40342
Conf. AI2 sender 3 Configurable Analogue Input-2 Sender Point-3 40343
Conf. AI2 value 3 Configurable Analogue Input-2 Point-3 40344
Conf. AI2 sender 4 Configurable Analogue Input-2 Sender Point-4 40345
Conf. AI2 value 4 Configurable Analogue Input-2 Point-4 40346
Conf. AI2 sender 5 Configurable Analogue Input-2 Sender Point-5 40347
Conf. AI2 value 5 Configurable Analogue Input-2 Point-5 40348
Conf. AI2 sender 6 Configurable Analogue Input-2 Sender Point-6 40349
Conf. AI2 value 6 Configurable Analogue Input-2 Point-6 40350
Conf. AI2 sender 7 Configurable Analogue Input-2 Sender Point-7 40351
Conf. AI2 value 7 Configurable Analogue Input-2 Point-7 40352
Conf. AI2 sender 8 Configurable Analogue Input-2 Sender Point-8 40353
Conf. AI2 value 8 Configurable Analogue Input-2 Point-8 40354
Conf. AI2 sender 9 Configurable Analogue Input-2 Sender Point-9 40355
Conf. AI2 value 9 Configurable Analogue Input-2 Point-9 40356
Conf. AI2 sender 10 Configurable Analogue Input-2 Sender Point-10 40357
Conf. AI2 value 10 Configurable Analogue Input-2 Point-10 40358
12
CONF. INPUT-1 (Inputs->Conf. input-1)
Dis,user conf.or list 0- Disable 40363
1- User Configured
2- Select From List
Polarity 0- Normally Open (Close To Activate) 40364
1- Normally Close (Open To Activate)
Indication If User Configured 40365
0- Status
1- Warning Non-Latching
2- Warning Latching
3- Electrical Trip
4- Shutdown
Activation If User Configured 40366
0- Active From Starting
1- Active From Safety On
2- Always Active
Select from list If Select From List 40367
0-Remote Start On Load
1-Remote Start Off Load
2-Auxiliary Mains Fail
3-Simulate Lamp Test Button
4-Simulate Horn Reset Button
5-Simulate Alarm Reset Button
6-Simulate Auto Button
7-Simulate Test Button
8-Simulate Manual Button
9-Simulate Start Button
10-Simulate Stop Button
11-Generator Closed Auxiliary
12-Generator Load Inhibit
13-Mains Closed Auxiliary
14-Mains Load Inhibit
15-Auto Restore Inhibit
16-Auto Start Inhibit
17-Panel Lock
18-Scheduled Runs Inhibited
19-Priority Select
20-Transfer To Generator/Open Mains
21-Transfer To Mains/Open Generator
22-Remote Inhibit
23-Being Found Alive
24-Generator is Loaded in STOP Mode
25-Emergency Stop (only conf. input-1)
25-Low Oil Pressure (only conf. input-4)
25-High Temperature (only conf. input-5)
26-Low Oil Level (only conf. input-4)
13
CONF. INPUT-3 (Inputs->Conf. input-3)
Dis,user conf.or list The same as Config. Input-1 options 40379
Polarity The same as Config. Input-1 options 40380
Indication The same as Config. Input-1 options 40381
Activation The same as Config. Input-1 options 40382
Select from list The same as Config. Input-1 options 40383
Active delay The same as Config. Input-1 options 40384
14
CONF. INPUT-7 (Inputs->Conf. input-7)
Input type 0- Disable 40411
1- User Configured (Digital)
2- Select From List (Digital)
3- Cabin Temperature (Anolog)
Polarity If Input Type is Digital 40412
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
Indication If Input Type is User Configured 40413
0- Status
1- Warning Non-Latching
2- Warning Latching
3- Electrical Trip
4- Shutdown
Activation If Input Type is User Configured 40414
0- Active From Starting
1- Active From Safety On
2- Always Active
Select from list If Input Type is Select From List 40415
0-Remote Start On Load
1-Remote Start Off Load
2-Auxiliary Mains Fail
3-Simulate Lamp Test Button
4-Simulate Horn Reset Button
5-Simulate Alarm Reset Button
6-Simulate Auto Button
7-Simulate Test Button
8-Simulate Manual Button
9-Simulate Start Button
10-Simulate Stop Button
11-Generator Closed Auxiliary
12-Generator Load Inhibit
13-Mains Closed Auxiliary
14-Mains Load Inhibit
15-Auto Restore Inhibit
16-Auto Start Inhibit
17-Panel Lock
18-Scheduled Runs(Exercise) Inhibited
19-Priority Select
20-Transfer To Generator/Open Mains
21-Transfer To Mains/Open Generator
22-Remote Inhibit
23-Being Found Alive
24-Generator is loaded in stop mode
Active delay Input active delay (If Input Type is Digital) 40416
Cabin temp.low prealr Cabin temperature low prealarm 40417
Cabin temp.low reset Cabin temperature low prealarm reset 40418
Cabin temp.low shutd. Cabin temperature low shutdown 40427
Cabin temp.high preal Cabin temperature high prealarm reset 40436
Cabin temp.high reset Cabin temperature high prealarm 40445
Cabin temp.high shutd Cabin temperature high shutdown 40454
15
CONF. EXP. INPUT-1 (Inputs->Conf. exp. input-1)
Dis,user conf.or list 0- Disable 40419
1- User Configured
2- Select From List
Hardware type 0-> -Ve (Switched To Battery -) 40420
1-> +Ve (Switched To Battery +)
Polarity 0- Normally Open (Close To Activate) 40421
1- Normally Close (Open To Activate)
Indication If User Configured 40422
0- Status
1- Warning Non-Latching
2- Warning Latching
3- Electrical Trip
4- Shutdown
Activation If User Configured 40423
0- Active From Starting
1- Active From Safety On
2- Always Active
Select from list If Select From List 40424
2-Auxiliary Mains Fail
3-Simulate Lamp Test Button
4-Simulate Horn Reset Button
5-Simulate Alarm Reset Button
6-Simulate Auto Button
7-Simulate Test Button
8-Simulate Manual Button
9-Simulate Start Button
10-Simulate Stop Button
11-Generator Closed Auxiliary
12-Generator Load Inhibit
13-Mains Closed Auxiliary
14-Mains Load Inhibit
15-Auto Restore Inhibit
16-Auto Start Inhibit
17-Panel Lock
18-Scheduled Runs Inhibited
19-Reserved
20-Transfer To Generator/Open Mains
21-Transfer To Mains/Open Generator
Active delay Input active delay 40425
16
CONF. EXP. INPUT-3 (Inputs->Conf. exp. input-3)
Dis,user conf.or list The same as Expansion Config. Input-1 options 40437
Hardware type The same as Expansion Config. Input-1 options 40438
Polarity The same as Expansion Config. Input-1 options 40439
Indication The same as Expansion Config. Input-1 options 40440
Activation The same as Expansion Config. Input-1 options 40441
Select from list The same as Expansion Config. Input-1 options 40442
Active delay The same as Expansion Config. Input-1 options 40443
18
CONF. OUTPUT-2 (Outputs->Conf. output-2)
Polarity 0- Normally Open (Close To Activate) 40495
1- Normally Close (Open To Activate)
19
CONF. EXP. OUTPUT-7 (Outputs->Conf. exp. output-7)
Polarity 0- Normally Open (Close To Activate) 40539
1- Normally Close (Open To Activate)
2.7 Timers
START TIMERS (Timers->Start timers)
Mains transient delay Mains Transient Delay 40547
Mains fail start dely Mains Fail Start Delay 40548
Remote start delay Remote Start Delay 40549
Pre-heat Pre-Heat 40550
Pre-heat bypass Pre-Heat Bypass 40551
Safety on delay Safety On Delay 40552
Warming up time Warmup Time 40553
Horn duration Horn Duration 40554
Chg. excitation time Charge Excitation Time 40555
Cooling fan time Cooling Fan Time 40556
Idle mode time Idle Mode Time (Smoke Limiting) 40557
Idle mode time off Idle Mode Time Off (Smoke Limiting Off) 40558
20
DUAL SET MODULE (Expansion modules->Dual set)
Disable/enable select Expansion Dual Set Module Selection 40595
Node ID Device Address 40596
Working period Dual Working Period 40597
Early start time Early Start Time 40598
Remote priority selct Remote Priority Selection: 40599
0- Pasive, 1- High Priority, 2- Low Priority
21
Example-1: To read the "Nominal Alternator Frequency" parameter's value;
Slave ID: 1
Command: 3 (Read Holding Register)
Register Address: 95 (Nominal Alternator Frequency)
Register Count: 1
ASCII DECIMAL HEX
Start Character : 58 0x3A Start Character
Slave ID high nibble 0 48 0x30
Device Slave ID
Slave ID low nibble 1 49 0x31
Command high nibble 0 48 0x30
03 = Read Holding Register Command
Command low nibble 3 52 0x34
Register Address MSB high nibble 0 48 0x30
Register Address MSB low nibble 0 48 0x30 Nominal Alternator Frequency Register Address
(00095 – 1 = 94 / 256 = 0 = 00 MSB)
Register Address LSB high nibble 5 53 0x35 (94 < 256 = 94 = 5E LSB)
Register Address LSB low nibble E 69 0x45
Register Count MSB high nibble 0 48 0x30
1 / 256 = 0 = 00
Register Count MSB low nibble 0 48 0x30
Register Count LSB high nibble 0 48 0x30
1 < 256 = 1 = 01
Register Count LSB low nibble 1 49 0x31
LRC MSB 9 57 0x39 1 + 3 + 5E + 1 =1+3+94+1 = 99
99 < 256 = 99
LRC LSB D 68 0x44 (99 ^ 255)+1= 157 = 9D
13 CR 13 0xD
Stop Characters
10 LF 10 0xA
ASCII :0103005E00019DCRLF
22
Device Type and Revision Number Bits
Description Address--Bit
Device Type 30053--(9-15 bits). If the value of these bits is 64,
the unit is "TRANS-AMF".
Device Revision 30053--(0-7 bits).
Observation Values
Description Unit Address
25
Warning and Alarm Bits
26
Bit Description Address--Bit
27
Bit Description Address--Bit
28
Optional Expansion Modules Status Bits
Bit Description Address--Bit
Ethernet module plugged 30041--8
GSM module plugged 30041--9
GPRS module plugged 30041--10
Dual set module plugged 30041--12
Web server module plugged 30041--13
29