The document discusses data exchange specifications for a SCADA/DMS system under an R-APDRP project in India. It outlines how the system will transfer circuit breaker status information to a customer care system using SOA and CIM/XML. It also describes how the SCADA system will interface with a GIS system using CIM/XML models and adapters to read network models and update its own models in compliance with IEC standards for data exchange.

Uploaded by

renv
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
50 views

SCADA Project Guide - 25

The document discusses data exchange specifications for a SCADA/DMS system under an R-APDRP project in India. It outlines how the system will transfer circuit breaker status information to a customer care system using SOA and CIM/XML. It also describes how the SCADA system will interface with a GIS system using CIM/XML models and adapters to read network models and update its own models in compliance with IEC standards for data exchange.

Uploaded by

renv
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Power Finance Corporation

SCADA/DMS, system under Part A –R-APDRP


Model Technical specification
MGVCL/RAPDRP/SIA/1140

1.3.8 Data Exchange with Customer Care System Under R-APDRP IT


implementation

The ISR function shall transfer the information available in the "Circuit breaker status
table" as defined in this chapter, to the Customer Care centre under R-APDRP IT
implementation / legacy system using SOA/Enterprise Service Bus supplied by ITIA,
over CIM/XML Models, or CIM/XML OPC/ICCP /ODBC Adapters / Interfaces. The
complete Circuit Breaker Information shall be transferred to Customer care centre on
demand or Changed Information shall be send along with the quality codes and
additional information associated with the CB.

1.3.9 Data Exchange with GIS system:

SCADA Systems over CIM/XML Models using GID to IEC 61968-1 will be used
by SCADA/DMS & other IT Systems for getting network information, customer
and interconnection information.

The GIS will interface using CIM/XML adapters to other applications. SCADA will
have model aware adapters to read from GIS network model repository, and
update its own models. The system shall utilize an IEC 61970 and IEC 61968
compliant interface. The system shall enable export of all data via a CIM-XML
interface per IEC 61970-452 and IEC 61970-552-4 and shall utilize modeling
from IEC 61968-11 as appropriate.

Data exchange shall be over model neutral messaging services and CIM/XML
data exchange for real-time or RDBMS will be used. The following standards as
applicable will be used to achieve the above requirements:
Messaging interfaces shall be based on model neutral interfaces based on the
IEC 61970-40X series for access to real-time and historical data and use the IEC
61968-3 and IEC 61968-9 standards for messaging interfaces that are model
dependent for network operations and metering respectively

The Graphic data import from a GIS systems shall support native formats of GIS
systems which shall be potentially used for data import. All Technological
addresses (TAs) shall be automatically assigned within the system to the tags
linking the graphic data to the attribute data in the GIS, the attribute data shall be
loaded into the SCADA data base and the display diagrams shall be generated.
The Graphics exchange between GIS and SCADA should happen over IEC-
61970-453 Scalar Vector Graphic based XML representation