SERIES 35-65
24 VAC Microprocessor-Based
Hot Surface Ignition Control F-35-65
October 2018
FEATURES
• Safe start with DETECT-A-FLAME® flame sensing
technology
• Custom pre-purge and inter-purge timings*
• 120/240 field selectable line voltage for use with 120
VAC igniter option
• 24/120/240 VAC hot surface igniter models available
• Single or three trials for ignition
• System diagnostic LED
• Flame current test points
• Local or remote flame sensing
• Automatic reset**
APPLICATIONS
• Gas furnaces
• Boilers
• Commercial cooking
• Water heaters
• Other gas-fired appliances SPECIFICATIONS
DESCRIPTION Input Power Control: 18 to 30 VAC 50/60 Hz
(Class 2 Transformer)
The 35-65 is a 24 VAC hot surface ignition (HSI) control
designed for use in all types of gas-fired appliances. The control Line Voltage Line: 24, 120 or 240 VAC
(L1 and L2 only)
uses a microprocessor to continually and safely monitor, analyze
and control the proper operation of a gas burner. On-board Input Current 300 mA max @ 24 VAC with gas
diagnostics with LED output makes troubleshooting easy and valve relay energized (control
ensures safe and efficient operation. only)
Gas Valve 2.0A max @ 24 VAC
Export Information (USA)
Hot Surface Igniter 5.0A max @ 24/120/240 VAC
Jurisdiction: EAR
ECCN: EAR99 Operating Temperature -40°F to +176°F
(-40°C to 80°C)
AGENCY CERTIFICATIONS Storage Temperature -40°F to +185°F
(-40°C to +85°C)
Design certified by CSA International to ANSI
Z21.20, CAN/CSA C22.2 No. 199-M89 Flame Sensitivity 0.7 µA minimum
Flame Failure Response 0.8 seconds maximum
CE Approved to EN298-2012
Flame Detector Self-check Once per second minimum
Rate
Factory Mutual approval on select models
Gas Types Natural, LP, or manufactured
Size (LxWxH) with enclosure 5.69 x 3.94 x 1.87 inches
Code Compliant to: (14.45 x 10.01 x 4.75 cm)
AS 4625 - 2008 Moisture Resistance Conformal coated to operate non-
AS 4622 - 2004 condensing to 95% R.H. Module
should not be exposed to water
*Pre-purge time cannot exceed inter-purge time on CE
Ingress Protection Not rated, protection provided by
Approved models. appliance in which it is installed
**Automatic reset is not allowed for CE Approved models. Tries for Ignition One or three try versions available
***EMC emission requirements shall be verified after Trial for Ignition Periods 4, 7, 10, 15 seconds available
incorporation of the burner control system into the end use Pre-purge and Inter-purge 0, 15 or 30 seconds available
appliance. Timings
1
SEQUENCE OF OPERATION / FLAME MOUNTING AND WIRING
RECOVERY / SAFETY LOCKOUT The Series 35-65 control is not position sensitive and can be
mounted vertically or horizontally. The case may be mounted on
Start-Up - Heat Mode any surface with #6 sheet metal screws. The control also
supports direct mounting to a standard NEC 4-in. junction box.
When a call for heat is received from the thermostat supplying
24 VAC to W, the control will reset, perform a self-check routine,
flash the diagnostic LED and begin a pre-purge delay. Following All wiring must be performed in accordance with
the pre-purge period, the igniter is energized for the heat up CAUTION both local and national electrical codes.
period and then the gas valve is energized for the Trial For
Ignition (TFI) period.
When the flame is detected during the TFI, the igniter is de-
activated and the gas valve remains energized. The thermostat
and burner flame are constantly monitored to assure proper Label all wires prior to disconnection when
system operation. When the thermostat is satisfied and the servicing controls. Wiring errors may cause
demand for heat terminates, the gas valve is immediately de- improper and dangerous operation. A functional
CAUTION checkout of a replacement control should always
energized.
be performed.
Failure to Light - Lockout
SINGLE TRIAL MODEL
Should the burner fail to light, or a flame is not detected during This product uses voltages of shock hazard
the TFI period, the gas valve will de-energize and the control will potential. Wiring and initial operation must be
go into lockout. The LED will indicate the fault code for ignition WARNING performed by a qualified service technician.
lockout.
MULTI-TRIAL MODEL
Should the main burner fail to light or the flame is not detected Operation outside specifications could result in
during the first TFI period, the gas valve will immediately de- failure of the Fenwal product and other
energize. The control will then go into an optional inter-purge WARNING equipment with potential for injury to people and
delay before attempting another TFI period. The control property.
attempts two additional ignition trials before de-energizing the
gas valve and entering lockout. The LED will indicate the fault
code for ignition lockout.
Terminal Designations
FLAME FAILURE-RECYCLE MODE Terminal Description Termination (inch)
Upon loss of flame, the gas valve is de-energized and the control
S1-240 240 VAC Igniter 1/4” Quick Connect
proceeds to inter-purge before attempting to relight the flame.
Multi-try models permit three tries for ignition including inter- S1-120 120 VAC Igniter 1/4” Quick Connect
purges. If the burner relights, normal operation resumes. If the (or 5-pin Mate-N-Lok)
burner does not relight, the control will enter lockout.
L1 120/240VAC Input 1/4” Quick Connect
(Hot) (or 5-pin Mate-N-Lok)
Lockout Recovery
L2 Neutral 1/4” Quick Connect
Recovery from lockout requires a manual reset by either (or 5-pin Mate-N-Lok)
resetting the thermostat, or removing 24 VAC for a period of 5
seconds. On models with automatic reset, if the thermostat is S2 Igniter/Remote Flame 1/4” Quick Connect
still calling for heat after one hour, then the control will Sense (or 5-pin Mate-N-Lok)
automatically reset and attempt to ignite the burner. R 24 VAC supply to 1/4” Quick Connect
processor (optional full
time power)
W Thermostat Input 1/4” Quick Connect
MV1 Main Valve Power 3/16” Quick Connect
GND System Ground 3/16” Quick Connect
FC+ & FC- Flame Current Test Pins Varies by model
2 F-35-65
Effective: October 2018
Wiring Diagrams - Series 35-65
Figure 1. Local Sense
Figure 2. Remote Sense
F-35-65 3
Effective: October 2018
TROUBLESHOOTING Hot Surface Igniter
Proper location of the silicon hot surface igniter is important to
Troubleshooting Guide
achieve optimum system performance for both ignition and
Symptom Recommended Actions flame sensing. See figure below.
1. Control does not start A. Miswired Note: The temperature of the ceramic holder should not
B. 24 VAC transformer fault exceed the manufacturer's specifications.
C. Fuse circuit breaker fault
D. Faulty control, check LED
for steady on or flashing
codes
2. Thermostat on - no ignition A. Miswired NO NO YES
B. Faulty thermostat, no volt-
age at thermostat terminal
W Typical Hot Surface Igniter
C. Failed igniter
3. Valve on - no igniter A. Defective igniter CERAMIC
B. Miswired HOLDER
C. Fault control, check voltage
at igniter
FIBERGLASS IGNITER
4. Igniter on - no valve A. Valve coil open INSULATION HOT ZONE
B. Open valve wire
C. Faulty control, check volt-
age at gas valve terminal Flame Current Measurement
Flame current is the current that passes through the flame from
5. Flame okay during TFI - A. Faulty igniter
sensor to ground. To measure flame current, connect a True
no flame sense after TFI B. Faulty S1 wire
RMS or analog DC micro-ammeter to the FC+ and FC- terminals.
C. Poor ground at burner
Readings should be 1.0 µA DC or higher. If the meter reads
D. Poor flame, check flame
current negative or below "0" on scale, meter leads are reversed. Re-
connect leads with proper polarity.
Alternately, a Digital Voltmeter may be used to measure DC
voltage between FC+ and FC- terminals. Each micro-amp of
Fault Conditions flame current produces 1.0 VDC. For example, 2.6 VDC equates
to 2.6 µA.
LED Indication Fault Mode
A good burner ground that matches the control ground is critical
Steady On Internal Control Failure for reliable flame sensing.
2 Flashes Flame without call for heat
Remote Sense Cable Requirements
3 Flashes Ignition Lockout
Remote flame sense cable must meet a voltage rating of 250V
and an insulation rating of 200 °C. Recommended length of 10ft
Note: During a fault condition, the LED will flash on for
(3m) or less. Consult Factory for longer lengths.
1/4 second and off for 1/4 second as needed to
indicate the fault code. The code will repeat every
3 seconds. Removing power from the control will
clear the fault code.
4 F-35-65
Effective: October 2018
DIMENSIONS
Note: All dimensions are in inches.
Figure 3. Standard Enclosure
F-35-65 5
Effective: October 2018
PART NUMBER CONFIGURATION
SERIES 35 - 65 X X X X - X X X
Product Designation Trial for Ignition
2 = 120/240 Field Selectable Line Voltage 1 = 4 Seconds
5 = Standard 3 = 7 Seconds
5 = 10 Seconds
Igniter Options 7 = 15 Seconds
0 = 120/240 VAC Mini-Igniter (6 Second Heat-Up) Inter-Purge
2 = 24 VAC Mini-Igniter (4 Second Heat-Up) CE Approved* 0 = None
5 = 120/240 VAC Igniter (20 Second Heat-Up) 1 = 15 Seconds
6 = 120/240 VAC Igniter (40 Second Heat-Up) 2 = 30 Seconds
7 = 24 VAC Mini-Igniter (4 Second Heat-Up)
Pre-Purge
Special Configurations 0 = None
3 = Special CE Approved Model* 1 = 15 Seconds
8 = Aftermarket Kit 2 = 30 Seconds
9 = Special Configuration Tries for Ignition
0 = Single Try without Automatic Reset
1 = Single Try with 1 Hour Automatic Reset
5 = Three Tries without Automatic Reset
A 3, 8 or 9 in this location
6 = Three Tries with 1 Hour Automatic Reset
(i.e. 35-65 5 901 -113)
indicates a special configuration. Terminations
9XX is a sequentially assigned 0 = ALL Q.C. Terminals without Full Time Power (W Only)
part number and does not follow 1 = Mate-N-Lok (5 Pos.) with Q.C. Terminals without Full Time Power (W Only)
the standard part numbering 2 = Mate-N-Lok (2 Pos.) with Q.C. Terminals without Full Time Power (W Only)
configuration. 5 = ALL Q.C. Terminals with Full Time Power (R Terminal)
6 = Mate-N-Lok (5 Pos.) with Q.C. Terminals with Full Time Power (R Terminal)
Consult Fenwal for operating
characteristics of this control.
*On CE Approved models, pre-purge
time cannot exceed inter-purge time
and automatic reset is not permitted.
EXPORT INFORMATION (USA)
Jurisdiction: EAR
Classification: EAR99
DETECT-A-FLAME is a registered trademark of Kidde-Fenwal, Inc., or its parents, subsidiaries, or affiliates. This document contains technical data subject to the EAR.
Fenwal Controls, Kidde-Fenwal Inc. This literature is provided for informational purposes only.
400 Main Street KIDDE-FENWAL, INC. assumes no responsibility for the prod-
Ashland, MA 01721 uct’s suitability for a particular application. The product must be
Tel: 800-FENWAL-1 properly applied to work correctly. If you need more informa-
Fax: 508-881-7619 tion on this product, or if you have a particular problem or
www.fenwalcontrols.com question, contact KIDDE-FENWAL, INC., Ashland, MA 01721.
© 2018 Kidde-Fenwal Inc. P/N F-35-65 Rev AE
Fenwal Controls
400 Main Street
Ashland, MA 01721
Tel. (508) 881-2000
EU DECLARATION OF CONFORMITY
We
Company Name: Kidde-Fenwal Inc.
Postal Address: 400 Main Street
City and Post Code: Ashland, MA 01721
Tel: 508-881-2000
Declare that the DoC is issued under sole responsibility and belongs to the following product:
Apparatus Model(s) Series 35-40, 35-53, 35-60, 35-61, 35-63, 35-608, 35-65, 35-66, 35-9X
Type: Fitting
Batch Number Date code and Revision Level Assigned per production lot, (YYWW RR)
Object of the Declaration:
Series 35-40, 12/24Vdc Direct Spark Automatic Gas Ignition Controllers
Series 35-53, 12Vdc Direct Spark Automatic Gas Ignition Controllers
Series 35-60, 35-61, 35-63, 35-608 24Vac Direct Spark Automatic Gas Ignition
Series 35-65 & 35-66 24Vac Hot Surface Automatic Gas Ignition Controllers
Series 35-9X Platform Ignition Module
SERIES 35-9X
SERIES 35-40 SERIES 35-53 SERIES 35-60/61/63/608
SERIES 35-65/66
The object of the declaration described above is in conformity within the relevant union
harmonization legislation:
Gas Appliance Regulation: (EU) 2016/426 Low Voltage Directive: 2014/35/EC
EMC Directive: 2014/30/EC Rohs 2011/65/EU
The following harmonized standards and technical specifications have been applied:
EN298:2012: Automatic Burner Control systems for Burners and appliances burning gaseous or liquid fuels.
EN13611:2007_A2:2011: Safety and control devices for Gas Burners and Gas burning appliances – General Requirements.
Name of Notified Body & Number: BSI Group, 0086, EU Type Examination Certification
Notified Body Certificate No.: Series 35-40: CE682407
Series 35-53 CE682404
Series 35-60/61/63/608 CE682405
Series 35-65/66 CE682406
Series 35-9x CE690652
Surveillance Audit Notified Body: BSI Group
For copies of the Installation Instructions and the EU DoC, got to www.fenwalcontrols.com, - Document Library - Data sheets.
Paul Finn
Kidde-Fenwal, Inc. Ashland, MA USA 01 Oct 2018 Paul Finn, Certification Engineer
Place of Issue: Date of Issue Name
© Kidde-Fenwal Inc. 06-237657-001 Rev AC