WebPage PDF
WebPage PDF
Engineers Newsletter
volume 47–4
Understanding VAV
Sound Standards
2 Trane Engineers Newsletter volume 47-4 providing insights for today’s HVAC system designer
In a parallel fan powered VAV Duct end corrections The Standard discharge and radiated sound power (for
installation, a small terminal fan in the 800 committee added “duct end the damper and, in the case of fan-
VAV box recirculates air from the corrections” to the standard beginning powered boxes, the fan), wide-open
plenum when heat is needed. In a in 2011 in an effort to account for open- damper pressure drop, and fan motor
series fan powered VAV installation, the ended duct terminations into large power consumption.
terminal fan operates continuously. rooms. This can be referred as “end
Additional tests with the fan on and off reflection loss.” This gives testers the Once approval is received,
are required for fan-powered VAV boxes ability to account for the sound that manufacturers are able to use the AHRI
because the fan generates additional should enter a test chamber to be VAV Certification Mark to show
sound and, depending upon the measured but does not. Instead, some compliance.
configuration, may not run the entire low-frequency plane waves rebound
period of operation. back into the duct and are not While certification applies to one
measured. In an installation, this operating point and cooling-only VAV
Parallel fan-powered VAV box sound phenomenon is usually desirable as it boxes, manufacturers typically publish
power data is presented for terminal reduces the amount of sound data that covers the entire operating
fan-only operation and standard cooling transmitted to the space through the range of their products, including the
operation (where the terminal fan is not supply air path. effects of options like reheat, VAV box
operating) as shown in Table 2. Series lining, and alternate housing
fan powered VAV box sound power is Certified sound Manufacturers may geometries.
presented for terminal-fan operation choose to participate in AHRI’s VAV box
only and terminal fan plus primary Certification Program. Annual AHRI Standard 885 ANSI/AHRI
airflow operation as shown in Table 3. independent verification of randomly Standard 885-2008 “Procedure for
sampled VAV boxes ensures Estimating Occupied Space Sound
Footnotes generally accompany the manufacturer’s performance claims are Levels in the Application of Air Terminals
table of data indicating which version of accurate within tolerance limits set by and Air Outlets” uses sound power
Standard 880 was used for testing and both Standard 880 and the Certification taken in accordance with Standard 880
relevant commentary on the VAV box Program. The VAV box operating to estimate sound pressure in the
and/or tests. characteristics evaluated include occupied space. This industry-
Table 1. Discharge and radiated sound power for a 700-cfm shut-off VAV box.
Table 2. Discharge and radiated sound power for a 700-cfm parallel fan powered VAV box.
Table 3. Discharge and radiated sound power for a 700-cfm series fan powered VAV box.
providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 47–4 3
developed method gives the user a created using software like the Trane
procedure to compute space sound Acoustics Program (TAP™) or a system
pressure using hand-calculations or a mock up.
spreadsheet.
Separate attenuation values are
In many presentations of VAV box provided for the discharge and radiated
sound data, a space NC level is printed. sound paths. Over the course of
The attenuation values printed in Table several publications, these attenuation
E1 of Normative Appendix E “Typical values have changed, complicating
Sound Attenuation Values”, often called matters. For example, the discharge
transfer functions, are used as deducts sound pressure from a medium sized
to compute the space sound pressure. VAV box serving 700 cfm would be
Each deduct is subtracted from the reported as NC 35 when tested in
VAV box sound power value in the accordance with ARI Standard 885-
same octave band to determine sound 1998 and NC 31 when tested with
pressure. Then, the NC-level is Standard 885-2008. For the same box,
computed using the sound pressure the radiated sound pressure would be
and published for both discharge and reported as NC 26, NC 27, or NC 22
radiated sound. The result is two depending on the acoustical ceiling tile
unique and different NC values for a material being used, if tested with
single VAV box. Standard 885-1998 version. If Standard
885-2008 were used, only NC 27
This appendix and the attenuation would be reported. See pages 5-7 for a
values used within are not used to comparison of the attenuation values
estimate sound pressure for actual and their results from the two most
installations. The attenuation values recent versions of Standard 885.
were developed with a number of
assumptions, such as the size of a
room being served by the VAV box, the
plenum depth, and acoustical ceiling
type materials. It is for these reasons
that the NC level printed in a catalog
or selection report should not be
expected in the actual installation.
Instead, the NC level gives designers
another tool to compare VAV boxes
from a sound perspective because
each VAV box NC level is computed
using the same criteria. To predict an
NC level in the actual space, an
acoustic model would need to be
4 Trane Engineers Newsletter volume 47-4 providing insights for today’s HVAC system designer
The evolution of AHRI Standard 885 Sound Attenuation Values
The sound attenuation values (transfer functions) found in AHRI Standard 885 have been changed over the course of
several publications. Discharge attenuation values have been provided in the standard from 125 to 8000 Hz while radiated
attenuation values have been provided from 125 to 4000 Hz.
In the 1998 publication, there were three options for discharge attenuation values based upon VAV box size and airflow:
In the 2008 update, the discharge attenuation values were largely republished with changes highlighted:
In the 1998 publication, there were three options for radiated sound:
In the 2008 update, only the mineral fiber option was left with no changes to the individual octave band attenuation values.
Because the octave band attenuation values were not changed for mineral fiber, a strict 1998-to-2008 comparison with
mineral fiber should yield no changes.
providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 47–4 5
The evolution of AHRI Standard 885 Sound Attenuation Values, continued
As a result, system designers must be very careful to ensure like-for-like comparisons when using Standard 885 and the
resulting NC level derived from Appendix E. Three different VAV boxes were compared using 1998 and 2008 attenuation
values. The resulting sound pressure and NC values are below.
First, a small, 150-cfm VAV box with a 4-inch inlet was evaluated with both versions:
Next, a medium sized VAV box with an 8-inch inlet serving 700 cfm is considered:
6 Trane Engineers Newsletter volume 47-4 providing insights for today’s HVAC system designer
The evolution of AHRI Standard 885 Sound Attenuation Values, continued
Finally, a large VAV box with a 10-inch inlet serving 1100 cfm is considered:
In the medium-sized VAV box, the reported discharge sound pressure is different when using the dissimilar attenuation
values.
Using NC does present some and the various paths sound takes to reach
challenges. Due to the nature of the Final Thoughts the space or receiver.
procedure, different sound spectrums
can result in the same NC level. For VAV boxes serve as both sound Published NC levels are based upon
example, a sound spectrum attenuators and regenerators in HVAC example installations where room sizes
dominated by low frequency sound systems. The industry has provided and materials are assumed and not
could result
, in NC 40 shown as the two separate sound standards that specific to the actual project. Two catalog
blue sound spectrum in Figure 2 (next pertain to VAV boxes: AHRI Standard NC values—one for discharge sound and
page). Middle frequency sound 880 to determine and present sound another for radiated—are provided. These
dominates the second sound power and AHRI Standard 885 to values, when printed in a catalog or
spectrum, in red, which results in a compute space sound pressure and selection software, should be used only for
different human response but the show space NC level with a specific comparison. When comparison does
same NC level. VAV box and representative space occur, it is important to ensure like-for-like
parameters. comparison in the radiated and discharge
material and parameters.
In general, radiated and discharge
By Eric Sturm, Trane. To subscribe or view previous
sound power is provided for VAV issues of the Engineers Newsletter visit trane.com/EN.
boxes without terminal fans. Boxes Send comments to [email protected].
with terminal fans will have radiated
and discharge sound with and without
the fan operating. Sound power is a
property of the VAV box and sound
pressure is the result of installation
providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 47–4 7
Figure 2. NC chart with two different sound spectrums resulting in the same NC level
8 Trane Engineers Newsletter volume 47-4 providing insights for today’s HVAC system designer
Join your local Trane office for the 2019 Engineers Newsletter LIVE!
Mark your calendar!
Small Building System Control. Recent innovations provide more options to
consider for controls in smaller buildings. This program will compare different
configurations of packaged rooftop systems, describe the technologies available to
control each system type, and demonstrate how to specify the controls to meet the
needs of your customer.
Chilled-Water Coil Design for ASHRAE 90.1-2016. The 2016 version of ASHRAE
Standard 90.1 requires chilled-water cooling coils be selected for at least a 15°F ΔT.
This ENL demonstrates the process for selecting coils and control valves to meet
this new requirement. illustrates coil configuration impact on part-load coil
performance, and discusses the impact on chiller plant design operation.
Trane, the Circle Logo, and TAP™ are trademarks of Trane in the United States and other countries. ANSI is a registered
trademark of American National Standards Institute, Inc. ASHRAE is a registered trademark of the American Society of
Heating, Refrigerating, and Air-Conditioning Engineers, Inc. AHRI is a registered trademark of Air-Conditioning, Heating &
Refrigeration Institute, Inc. All trademarks referenced are the trademarks of their respective owners.
Trane, This newsletter is for informational purposes only and does not constitute legal advice.
A business of Ingersoll Rand Trane believes the facts and suggestions presented here to be accurate. However, final design and
application decisions are your responsibility. Trane disclaims any responsibility for actions taken on
For more information, contact your local Trane
the material presented.
office or e-mail us at [email protected]