Energy Systems Unit 2
Energy Systems Unit 2
UNIT 2
Transmission
▪ The electric power can be transmitted either by means of DC or AC.
▪ However, DC has some disadvantages such as:
i. It cannot be stepped up for the transmission of power as high voltages.
ii. Electric power cannot be generated at high DC voltages due to
commutation problem.
▪ The transmission of high voltage has the following advantages:
i. such as reduced volume of the conductor,
ii. increased transmission efficiency and
iii. reduced percentage voltage drop.
▪ However, transmitting power from one generation station is not a reliable
solution.
▪ The connection of several generating s in a network of a particular
transmission voltage, in order to allow them to share the load, increases
the reliability of the power system significantly.
2.1.1 Inter-connected Systems
5
What is inter-connector
▪ Inter-connector is usually referred to as the connection between two or
more alternators, power stations or supply networks.
▪ Inter-connection increases the amount of current which flows when a
short-circuit occurs on a system. It therefore requires the installation to be
able to interrupt this large short-circuit current.
▪ The disturbance caused by a short-circuit on one system may spread to
inter-connected system unless a proper relays and circuit breakers are
provided at the point of inter-connection.
2.1.1 Inter-connected Systems
6
▪ For example, if the feeder load on the bus-bars of power station A and B
are 50 MW each and the output of the generator on the bus-bars of
power station A is 30MW, the output of the generators in the bus-bars of
power station B must then be 70 MW.
▪ Therefore, 20MW must therefore be transmitted across the inter-
connector from power station B to power station A.
Capacity =30MW Capacity =100MW
30MW 70MW
50MW 50MW
2.1.1 Inter-connected Systems
8
▪ The magnitude of the resistive voltage drop (I.R) is larger than that of the
reactive voltage drop (I.X) when the power factor is larger than 0.98.
▪ Capacitor banks, synchronous machines, shunt reactors and tap-
changing transformers are typical voltage control devices to be used.
2.1.2 Power Transfer
11
▪ For the power to be transferred from one point to another, there must be a
difference in voltage between those two points.
▪ The potential difference causes active (P) and reactive power (Q) to flow
between the two points.
▪ It can happen that P flows from power station A to power station B, and Q
flows from power station B to power station A.
▪ However, it can also happen that P flows from power station B to A, and Q
flows from power station A to B.
▪ This depends on the potential
difference between two points as a
result of magnitudes being different.
▪ This depends also on the phase
difference between the voltages.
▪ Z is the synchronous impedance of
the two power stations or the
impedance of the transmission line.
2.1.2 Power Transfer
12
Phasor diagram for voltage drop Vab Phasor diagram for voltage drop Vab
▪ The sketch shows the layout of the two power stations joined by an inter-
connector having a synchronous impedance (Z) at angle β.
▪ The subscript (i) represents the leading voltage and (j) represents the
lagging voltage.
▪ To calculate the power transfer between power station A and B, the
current will flow from (i) to (j). Current Iij is called the inter-connector
current. Therefore the voltage difference between the two power stations
is determined as follows:
Vij = Vi(ph) − Vj(ph) Or Vij = Iij . Z
β = Beta
2.1.2 Power Transfer ɸ = Phi
δ = Delta
15
▪ Below is the phasor diagram for the voltages and currents in the inter-
connected system.
▪ The current (Ii =Vi/Z) will lag the voltage Vi by an angle β and the current
(Ij =Vj/Z) will lag the voltage Vj by an angle β.
▪ The angle between the voltages Vi and Vj is δ.
▪ This angle δ is know as the load angle.
▪ It is important to note that the power formulas are derive under the
following assumptions:
1) Vi is leading Vj by angle δ.
2) The current flows from i to j, namely, Iij.
▪ The angle between the voltages Vi and Vj is δ
Qi = Vi .Iij.sin ɸ
Pj = Vj .Iij.cos ɸ
Pj = Vj.Ii.cos (β − δ) − Vj.Ij.cos β
V V Vi2
Pj = Vj [ i.cos (β − δ) − j.cos β ] So Pj = [ cos (β − δ) −cos β ]
Z Z Z
β = Beta
2.1.2 Power Transfer ɸ = Phi
δ = Delta
18
Qj = Vj .Iij.sin ɸ
▪ Now you have computed different powers (Pi, Qi, Pj & Qj) from one power
station to the other.
▪ These power are within the inter-connector of the system.
▪ Therefore, the same powers can also be computed from the apparent
powers (Si*& Sj*) transferred within the inter-connector since:
Si * = Pi ± jQi Sj * = Pj ± jQj
Si * = √3 .Vi.Iij*
Sj * = √3 .Vj.Iij*
▪ The asterisk sign (*) simply means that
the conjugate/mirror image of the
current is used (opposite sign of the
angle) during computation since
complex power method is used.
β = Beta
2.1.2 Power Transfer ɸ = Phi
δ = Delta
20
▪ How to determine the final loading (in VA) of the two power stations
using Si* & Sj*?
▪ The final loading for each power station can be determined by
considering the apparent powers entering the busbar and the apparent
powers leaving the busbar. This can be determined as follows:
Example 1: Two power stations, A and B, work at 88 kV and deliver power to their
respective consumers as follows:
Power station A: 720 MVA at a power factor of 0.819 lagging.
Power station B: 640 MVA at a power factor of 0.766 lagging.
An inter-connector with an impedance of (1.25 +j5.69) ohms per line is connected
between power station A and B. The voltage at power station A is advance with an
angle of 8˚with respect to the voltage at power station B. The real power loading of
power station A is 600 MW.