Initial Verification For Glass

The document summarizes the initial verification of glass for a building using three methods: calculations, SJ Mepla software, and Strand7 software. The maximum wind load was determined to be 2.13 kPa based on a tributary width of 1.5m, resulting in a uniform load of 3.195 kN/m. Verification calculations for strong and weak axes were 3.14 kN/m and 0.61 kN/m respectively. Software simulations in SJ Mepla and Strand7 were also used and found the maximum stress to be 13.94 MPa with a maximum deflection of 20.64mm.

Uploaded by

waweng22
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
218 views

Initial Verification For Glass

The document summarizes the initial verification of glass for a building using three methods: calculations, SJ Mepla software, and Strand7 software. The maximum wind load was determined to be 2.13 kPa based on a tributary width of 1.5m, resulting in a uniform load of 3.195 kN/m. Verification calculations for strong and weak axes were 3.14 kN/m and 0.61 kN/m respectively. Software simulations in SJ Mepla and Strand7 were also used and found the maximum stress to be 13.94 MPa with a maximum deflection of 20.64mm.

Uploaded by

waweng22
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

INITIAL VERIFICATION FOR GLASS 

Maximum wind load = 2.13 kPa 

Tributary width = 1.5m 

Uniform load = 2.13 x 1.5 = 3.195 kN/m 

Component of forces for tilted glass fin 

Strong axis = 3.195cos(11) = 3.14kN/m 

Weak axis = 3.195sin(11) = 0.61 kN/m 

   
VERIFICAITON USING SJ MEPLA 

 
 
VERIFICATION USING STRAND7 

Calculation for effective thickness using SGP  

 
 

 
   
Maximum stress 

 
Max stress = 13.94 MPa 

 
Max deflection = 20.64mm 