Data Sheet: RISH LM 1350 / LM 1360

The document is a data sheet for the RISH LM1350/LM1360, which measures important electrical parameters in 3 phase and 1 phase networks. It displays parameters like energy, power, and basic parameters. It has optional outputs that can be configured for energy pulse output, limit output, timer function, and RTC relay. It measures THD and individual harmonics up to the 31st order. It has data logging capabilities and stores measurements internally. Key features include energy measurement accuracy, data logging, communications interfaces, display, and compliance with safety standards.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views10 pages

Data Sheet: RISH LM 1350 / LM 1360

The document is a data sheet for the RISH LM1350/LM1360, which measures important electrical parameters in 3 phase and 1 phase networks. It displays parameters like energy, power, and basic parameters. It has optional outputs that can be configured for energy pulse output, limit output, timer function, and RTC relay. It measures THD and individual harmonics up to the 31st order. It has data logging capabilities and stores measurements internally. Key features include energy measurement accuracy, data logging, communications interfaces, display, and compliance with safety standards.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

Data Sheet

RISH LM 1350 / LM 1360

Measure Control Record Analyze


Data Sheet
RISH LM1350 / LM1360

RISH LM1350 / LM1360 measures important electrical parameters in 3 phase 4 wire,3 phase 3 wire and1 phase 2 wire Network. It
displays many parameters at a glance. It measures electrical parameters like Active / Reactive / Apparent energy , power and all basic
parameter. The instrument has two optional outputs. It can be configured as pulse output for energy measurement , limit output , timer
function and RTC relay.

Applications:
Internal Energy billing/monitoring/auditing Electrical load monitoring
Sub-metering Genset, TestBenches and Laboratories

Product Features:
Energy as per IEC 62053: RTC(Real Time Clock):
Rish LM1350/LM1360 is available in Accuracy class 0.2s Inbuilt real time clock for display of date and time, along
or 0.5s option. with time stamping for data logging and Event recording.
Active Energy accuracy 0.5s as per 62053-22 or optional
0.2s as per 62053-22 Data logging:
Independent Import and Export Energy counter. Active Meter has inbuilt 8MB Flash for datalogging.
energy (kWh), Reactive energy (kVArh), Apparent energy Event Logging: Previous 5 events of factory default
(kVAh) measurement. parameters can be logged with Date and time.
Time based logging: User selectable parameters (1 to 30)
THD and Individual Harmonics Measurement: can be logged at regular intervals(1 to 60min) with Date
The instrument measures per phase THD and individual and Time stamp in internal memory and and can be
harmonic up to 31st harmonics for voltage & current . accessed via Modbus or Ethernet or USB.
If 1 Parameter for example energy is selected with logging
Limit (Alarm) or Pulse or RTC relay or Timer Relay interval of 15 minutes, log of maximum 948 days are
Output (optional) available for user.
Potential free, very fast acting relay contact. If 30 Parameters are selected with logging interval of 60
Configurable as pulse output which can be used to drive minutes, log of maximum 355 days are available for user.
an external counter for energy measurement. Load Profile logging : Logging of energy consumed and
Configurable as limit (alarm) switch. peak Demand(Power and Current) in a day and in month
RTC relay can be used to control some instrument for efficient tracking of load behaviors.
automatically over the period of a week repetitively. Maximum 1 year daily and 14years of monthly log is
Timer output can be used to operate relay in cyclic manner. available for user.

USB Interface: Big LCD display with Back-lit :


Isolated USB Interface for configuration of the Instrument, LCD shows 4 measurement parameters along with 9 digit
onsite access of measured parameter and downloading of energy parameter at a glance. It also shows load graphics
logged data. and phase rotation symbol

User Assignable Screens Direct remote access(Optional):


Instrument measures more than 85 parameters and these Remote configuration of the Instrument and access of
parameters are displayed through 28 different screens. measured parameter via Modbus or through Ethernet
For some applications user does not require all 28 screens, interface(Modbus TCP/IP).
only few screens are required.
So to have flexibility, Rishabh has added feature “User Compliance to International Safety standards
assignable screens”. In which user can select minimum Compliance to International Safety standard
1no. and maximum 10 nos. of screens out of 28 screens as IEC 61010-1- 2010
per application requirement.
For example: If 5 screens are selected out of 28 screens, EMC Compatibility
then display will scroll among that 5 selected screens. Compliance to International standard IEC 61326

Measure Control Record Analyze

Page No.: 1 Version No.: E 04/18


Data Sheet
RISH LM1350 / LM1360

Technical Specifications:
Dimensions Details: Input Voltage:
Nominal input voltage (AC RMS) 100VLL to 600 VLL
96 mm programmable on site. 57.5VLN to 346.42 VLN
System PT primary values 100VLL to 1200kVLL programmable on site.
Max continuous input voltage 120% of nominal value
Overload Withstand: 2 x rated value for 1 second, repeated 10
times at 10 second intervals
Overload Indication “-OL-” >121% of Nominal value
96mm

Display Area Nominal input voltage burden < 0.3VA approx. per phase(at nominal 240V)
Input Current:
Nominal input current 1A / 5A onsite programmable
System CT primary values From 1A to 9999A
Max continuous input current 120% of nominal value
Front View
Overload Indication “-OL-” >121% of Nominal value
Nominal input current burden < 0.3VA approx. per phase
52mm 51mm
Overload Withstand: 20 x rated value for 1 second, repeated 5
hhhhhh
times at 5 minute intervals
Auxiliary Supply:
Auxiliary supply range 100-550V AC/DC
Aux Supply frequency 45 to 65 Hz range
Auxiliary Supply burden (at 230V AC DC)
With Addon card < 6VA approx.
With Ethernet card < 8 VA approx.
Operating Measuring Ranges:
Current (Energy Measurement) 1....120% of nominal value
70mm
57mm Starting current : as per Standard IEC62053-22(0.5s)
75mm
as per Standard IEC62053-22(Class 0.2s)(optional)
Voltage 20... 120% of nominal value
Side View Power Factor 0.5 Lag ... 1... 0.8 Lead
Frequency 45Hz to 66Hz
Reference Conditions for Accuracy
Reference temperature 23°C +/- 2°C
Input Waveform Sinusoidal(distortion factor 0.005)
92mm+0.8 Input frequency 50/60 Hz ± 2%
Auxilary supply frequency 50/60 Hz ± 1%
Total Harmonic distortion 50% up to 15th Harmonics
10% up to 31st Harmonics
(Current range 20%...100% of nominal value)
92mm+0.8

Voltage range 50%.....100% of nominal value


Accuracy
Active Energy Class 0.5s as per IEC 62053 - 22
Class 0.2s as per IEC 62053- 22(optional)
Apparent Energy Class 1
Panel Cutout Reactive Energy Class 2 as per IEC 62053 - 23

Measure Control Record Analyze

Page No.: 2 Version No.: E 04/18


Data Sheet
RISH LM1350 / LM1360

Technical Specifications:
Electrical Connection:
Accuracy
Network Types :
Class 0.5s (Standard) Class 0.2s (on request)
Voltage ± 0.5% of Nominal value ± 0.2% of Nominal value
2 5 8 11 1 3 4 6 7 9 13 14 Current ± 0.5% of Nominal value ± 0.2% of Nominal value
Frequency ± 0.2% of mid frequency ± 0.2 % of mid frequency
Active Power ± 0.5% of Nominal value ± 0.2% of Nominal value
Re-Active Power ± 1.0% of Nominal value ± 1.0% of Nominal value
Apparent Power ± 0.5% of Nominal value ± 0.2% of Nominal value
L N
AUX
Power Factor/ angle ±3° ±3°
S1 S2
SUPPLY THD (Voltage / Current) ±3% ±3%
S1 S2
P1 P2
L1 L
L2 P1 P2
S1 S2
O Display update rate:
P1 P2
L3 A Response time to step input 1 sec approx.
N D
Applicable Standards:
a) 3 Phase 4 Wire
EMC IEC 61326 - 1 : 2012
Immunity IEC 61000-4-3. 10V/m – Level 3 industrial
Low level
2 5 8 1 3 7 9 13 14
Safety IEC 61010-1-2010 , Permanently connected use
IP for water & dust IEC60529
Pollution degree: 2
L N Installation category: III
AUX
SUPPLY Isolation:
S1 S2

P1 P2
Protective Class 2
L1 L
S1 S2
O High voltage test
L2
P1 P2 A Input+Aux Vs Surface 4kV RMS, 50Hz,1min
L3 D
b) 3 Phase 3 Wire Input Vs Remaining Circuit 3.3kV RMS,50Hz,1min
Environmental
Operating temperature -20 to +70°C
Storage temperature -25 to +75°C
2 11 1 3 13 14 Relative humidity 0... 95%RH (non condensing)
Warm up time Minimum 3 minute
Shock (As per IEC60068-2-27) Half sine wave, Peak acceleration
L N 30gn (300 m/s^2),duration 18ms.
AUX Vibration 10... 150...10 Hz, 0.15mm amplitude
SUPPLY
S1 S2
Number of Sweep cycles 10 per axis
P1 P2
L1 L Enclosure IP 20 (Terminal side) and IP50(Front side)
L2 O
L3 A Interfaces
N D Impulse Led For Energy testing
Relay(Optional) 250 VAC,5 A AC
c) Single Phase Load
30VDC, 5A DC
It is recommended that the wires used for Modbus (Optional) RS485,max.1200m
connections to the instrument should have lugs Baud rate : 4.8k,9.6k,19.2k,38.4k ,57.6kbps.
soldered at the end. That is, the connections should Ethernet (Optional) Ethernet access on Modbus TCP/IP Protocol.
be made with Lugged wires for secure connections.

Measure Control Record Analyze

Page No.: 3 Version No.: E 04/18


Data Sheet
RISH LM1350 / LM1360
Memory calculations for Time based datalogging :
Max Memory Locations = 273030
Actual parameter stored in Each log = Date +time+Number of parameter selected by user
for ex. Number of parameter selected by user = 1.
Actual parameter stored in Each log = 1(Date) +1(time)+ 1 = 3
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log
=273030/3= 91010
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24
=(60/15)*24 = 96
Max Days = Maximum log that can be stored / log in one day
= 91010/ 96 = 948.20 days

Measured Parameter System wise:  : Available  : Not Available

Sr No Parameters 3 Phase 4Wire 3Phase 3Wire 1Phase 2Wire


1. Import Active Energy 1   
2. Export Active Energy 1   
3. Inductive Reactive Energy1   
4. Capacitive Reactive Energy 1   
5. Apparent Energy 1   
 6. System Active Power (kW)   
7. Active Power L1 (kW)   
8. Active Power L2 (kW)   
9. Active Power L3 (kW)   
10. System Re-active Power (kVAr)   
11. Re-active Power L1 (kVAr)   
12. Re-active Power L2 (kVAr)   
13. Re-active Power L3 (kVAr)   
14. System Apparent Power (kVA) 
15. Apparent Power L1 (kVA)   
16. Apparent Power L2 (kVA)   
17. Apparent Power L3 (kVA)   
18. System Power Factor   
19. Power Factor L1   
20. Power Factor L2   
21. Power Factor L3   
22. System Phase Angle   
23. Phase Angle L1   
24. Phase Angle L2   
25. Phase Angle L3   
26. Current Demand   
27. kVA Demand   
28. Import kW Demand   
29. Export kW Demand   
30. Inductive Var Demand   
31. Capacitive Var Demand   
32. Max Current Demand   
33. Max kVA Demand   
34. Max Import kW Demand   
35. Max Export kW Demand   

Measure Control Record Analyze

Page No.: 4 Version No.: E 04/18


Data Sheet
RISH LM1350 / LM1360
Measured Parameter System wise:  : Available  : Not Available

Sr No Parameters 3 Phase 4Wire 3Phase 3Wire 1Phase 2Wire


36. Max Inductive Var Demand   
37. Max Inductive Var Demand   
38. Run Hour   
39. On Hour   
40. Number of Interruptions   
41. System Voltage   
42. Voltage L1   
43. Voltage L2   
44. Voltage L3   
45. Voltage L12   
46. Voltage L23   
47. Voltage L31   
48. System Voltage THD   
49. Voltage L1 THD   
50. Voltage L2 THD   
51. Voltage L3 THD   
52. System Current   
53. Current L1   
54. Current L2   
55. Current L3   
56. System Current THD   
57. Current L1 THD   
58. Current L2 THD   
59. Current L3 THD   
60. Individual Harmonics of VL1(Up to 31st Harmonics)   
61. Individual Harmonics of VL2 (Up to 31st Harmonics)   
62. Individual Harmonics VL3 (Up to 31st Harmonics )   
63. Individual Harmonics IL1(Up to 31st Harmonics )   
64. Individual Harmonics IL2(Up to 31st Harmonic )   
65. Individual Harmonics IL3(Up to 31st Harmonics   
66. Neutral Current   
67. Frequency   
68. RPM   
69. Phase Reversal Indication   
70. Current Reversal Indication   
71. Phase Absent Indication   
72. Old Import Active Energy 2   
73. Old Export Active Energy 2   
74. Old Inductive Reactive Energy 2   
75. Old Capacitive Reactive Energy 2   
76. Old Apparent Energy 2   
77. Old Run Hour 2   
78. Old On Hour 2   
79. Old Number of Interruptions 2   
80. Old Max kW Import Demand 2   
 81. Old Max kW Export Demand 2   
2
82. Old Max Var Inductive Demand   
2
83. Old Max Var Capacitive Demand   
84. Old Max VA Demand 2   
 85. Old Max A Demand 2   
Note: 1. Energy on display is autoranging & unit for Energy parameters on modbus are dependent on CT PT ratio or unit selected by user.
2. Parameters are available only on modbus.

Measure Control Record Analyze

Page No.: 5 Version No.: E 04/18


Data Sheet
RISH LM1350 / LM1360

Measured Parameter Model wise:  : Available  : Not Available

Sr No Parameters Rish LM 1360 Rish LM 1350


1. Import Active Energy 1  
2. Export Active Energy 1  
1
3. Inductive Reactive Energy  
4. Capacitive Reactive Energy 1  
5. Apparent Energy 1  
 6. System Active Power (kW)  
7. Active Power L1 (kW)  
8. Active Power L2 (kW)  
9. Active Power L3 (kW)  
10. System Re-active Power (kVAr)  
11. Re-active Power L1 (kVAr)  
12. Re-active Power L2 (kVAr)  
13. Re-active Power L3 (kVAr)  
14. System Apparent Power (kVA)  
15. Apparent Power L1 (kVA)  
16. Apparent Power L2 (kVA)  
17. Apparent Power L3 (kVA)  
18. System Power Factor  
19. Power Factor L1  
20. Power Factor L2  
21. Power Factor L3  
22. System Phase Angle  
23. Phase Angle L1  
24. Phase Angle L2  
25. Phase Angle L3  
26. Current Demand  
27. kVA Demand  
28. Import kW Demand  
29. Export kW Demand  
30. Inductive Var Demand  
31. Capacitive Var Demand  
32. Max Current Demand  
33. Max kVA Demand  
34. Max Import kW Demand  
35. Max Export kW Demand  
36. Max Inductive Var Demand  
37. Max Capacitive Var Demand  
38. Run Hour  
39. On Hour  
40. Number of Interruptions  
41. System Voltage  
42. Voltage L1  
43. Voltage L2  
44. Voltage L3  
45. Voltage L12  
46. Voltage L23  
47. Voltage L31  
48. System Voltage THD  
49. Voltage L1 THD  
50. Voltage L2 THD  
51. Voltage L3 THD  

Measure Control Record Analyze

Page No.: 6 Version No.: E 04/18


Data Sheet
RISH LM1350 / LM1360

Measured Parameter Model wise:  : Available  : Not Available

Sr No Parameters Rish LM1360 Rish LM 1350


52. System Current  
53. Current L1  
54. Current L2  
55. Current L3  
56. System Current THD  
57. Current L1 THD  
58. Current L2 THD  
59. Current L3 THD  
60. Individual Harmonics of VL1(Up to 31st Harmonics)  
61. Individual Harmonics of VL2 (Up to 31st Harmonics)  
62. Individual Harmonics VL3 (Up to 31st Harmonics )  
63. Individual Harmonics IL1(Up to 31st Harmonics )  
64. Individual Harmonics IL2(Up to 31st Harmonic )  
65. Individual Harmonics IL3(Up to 31st Harmonics  
66. Neutral Current  
67. Frequency  
68. RPM  
69. Phase Reversal Indication  
70. Current Reversal Indication  
71. Phase Absent Indication  
72. Old Import Active Energy 2  
73. Old Export Active Energy 2  
74. Old Inductive Reactive Energy 2  
75. Old Capacitive Reactive Energy 2  
76. Old Apparent Energy 2  
77. Old Run Hour 2  
78. Old On Hour 2  
79. Old Number of Interruptions 2  
 80. Old Max Current Demand 2  
 81. Old Max VA Demand2  
82. Old Max Import W Demand 2  
83. Old Max Export W Demand 2  
 84. Old Max Inductive VAr Demand 2  
 85. Old Max Capacitive VAr Demand 2  

Note: 1. Energy on display is autoranging & unit for Energy parameters on modbus are dependent on CT PT ratio or unit selected by user.
2. Parameters are available only on modbus.

Measure Control Record Analyze

Page No.: 7 Version No.: E 04/18


Data Sheet
RISH LM1350 / LM1360

Order Code:

Ordering Information:

Product Code : MA4L - X - 3 - 01 - 02 - X - H - X - 0000

3: RISH LM 1350
4: RISH LM 1360

R : RS485 - 2 Pulse Output


E : Ethernet
D : Ethernet - Datalogging
U : RS485 - 2 Pulse Output - Datalogging - USB
Z : NONE

2: Accuracy class 0.2s


5: Accuracy class 0.5s

Order Code Example:


MA4L-430102RH20000
LM1360 3Phase input with input voltage 100-600VLL with 1A/5A internal CT , auxiliary voltage 100 to 550 V AC DC ,with
MODBUS (RS485),with 2 pulse output with accuracy class 0.2s.

Measure Control Record Analyze

Page No.: 8 Version No.: E 04/18


Measure Control Record Analyze