Operating Instructions: XV-102 Micro Panel
Operating Instructions: XV-102 Micro Panel
Operating Instructions
Effective February 2013
Supersedes December 2011
Manufacturer
Eaton Automation AG
Spinnereistrasse 8-14
CH-9008 St. Gallen
Switzerland
www.eaton-automation.com/en
www.eaton.com
Support
Region North America Other regions
Eaton Corporation Please contact your local supplier or send
Electrical Sector an Email to: [email protected]
1111 Superior Ave.
Cleveland, OH 44114
United States
877-ETN-CARE (877-386-2273)
www.eaton.com
Original instructions
The German version of this document is the original instructions.
Editor
Monika Jahn
Copyright
© Eaton Automation AG, CH-9008 St. Gallen
All rights reserved, also for the translation.
None of this document may be reproduced or processed, duplicated or distributed by
electronic systems in any form (print, photocopy, microfilm or any other process) without
the written permission of Eaton Automation AG, St. Gallen.
Subject to modifications.
Contents
Contents
1 General....................................................................................................................... 5
1.1 Purpose of these Operating Instructions..................................................................... 5
1.2 Comments about this document ................................................................................. 5
1.3 Additional documentation............................................................................................ 6
5 Installation ................................................................................................................. 23
5.1 Safety regulations ....................................................................................................... 23
5.2 Requirements for the place of installation ................................................................... 24
5.2.1 Engineering conditions of acceptability by Underwriters Labaratories Inc. (UL) ......... 24
5.2.2 Requirements for the mounting position ..................................................................... 24
5.3 Interfaces .................................................................................................................... 25
5.3.1 Overview of interfaces................................................................................................. 26
5.3.2 Preparation of cables with D-Sub connector............................................................... 28
5.3.3 Power supply............................................................................................................... 30
5.3.4 RS232 (System Port) .................................................................................................. 31
5.3.5 Ethernet....................................................................................................................... 33
5.3.6 USB Device................................................................................................................. 34
5.3.7 USB Host .................................................................................................................... 34
5.3.8 SmartWire-DT Master ................................................................................................. 35
5.3.8.1 Additional documentation for devices with SmartWire-DT Master interface ............... 35
6 Operation ................................................................................................................... 55
6.1 Safety regulations ....................................................................................................... 55
6.2 Starting the device ...................................................................................................... 56
6.3 Switching off the device .............................................................................................. 56
6.4 Inserting and removing an SD card............................................................................. 57
1 General
) Read Chapter 3 Safety regulations, 11 before working with the device. This contains
important information for your personal safety. This chapter must be read and under-
stood by all persons working with this device.
WARNING
Incomplete copy of the Operating Instructions
Working with individual pages of these Operating Instructions may cause damage
to property or personnel by failure to observe safety-related information.
X Always work with the complete document.
) The documents can also be downloaded from www.eaton.com (search document No.
via search field of the home page).
Documents relevant for the devices with SmartWire-DT Master interface, see Chapter
5.3.8 SmartWire-DT Master, 33.
2 Device description
2.1 Function
MICRO PANELs XV-102 can be used as HMI devices or as integrated HMI/PLC devices.
Qty Designation
1 MICRO PANEL:
XV-102-…-35MQR… or
XV-102-…-35TQR…
4 Retaining brackets with threaded pin for mounting the device
1 Sealing strip for mounting the device (glued in the device and/or loose enclosed)
1 Power supply connector for the device
1 Power supply connector for SmartWire-DT Master (only supplied with XV-102-BE-…
devices)
1 Stylus
Tab. 2 Package contents for 3.5" devices
Qty Designation
1 MICRO PANEL:
XV-102-…-57TVR…
6 Retaining brackets with threaded pin for mounting the device
1 Sealing strip for mounting the device (glued in the device and/or loose enclosed)
1 Power supply connector for the device
1 Power supply connector for SmartWire-DT Master (only supplied with XV-102-E… devices)
1 Stylus
Tab. 3 Package contents for 5.7" devices
Qty Designation
1 MICRO PANEL:
XV-102-…-70TWR…
8 Retaining brackets with threaded pin for mounting the device
1 Sealing strip for mounting the device (glued in the device and/or loose enclosed)
1 Power supply connector for the device
1 Power supply connector for SmartWire-DT Master (only supplied with XV-102-E… devices)
1 Stylus
Tab. 4 Package contents for 7.0" devices
2.5 Accessories
Different accessories are available. Use only original accessories.
2.6 Designation
Nameplate A nameplate is fixed on the rear of the device in order to identify it. The nameplate contains the following
information:
Manufacturer address
Type designation
Power supply required
Part no. (Part-No or Art.-No)
Serial no.
Time of manufacturing (week/year)
Approval mark and information to the approval
Arrangement of interfaces and operating elements
Permissible mounting options (top edge «Top»)
Support To ensure fast and optimum support always provide the support personnel with the following informa-
tion on the nameplate:
Part no. (Part-No or Art.-No)
Serial no.
3 Safety regulations
3.1 General
Hazards may still occur even though the device meets the current state of the art and complies with all
recognized safety requirements.
The device must only be installed and commissioned in perfect technical condition and in compliance
with this document.
) Read this chapter before working with the device. This contains important information
for your personal safety. This chapter must be read and understood by all persons work-
ing with this device.
DANGER
Signal word DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death
or serious injury.
WARNING
Signal word WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death
or serious injury.
CAUTION
Signal word CAUTION
Indicates a potentially hazardous situation which, if not avoided, could result in minor
or moderate injury.
CAUTION
Signal word CAUTION without safety alert symbol
Indicates a situation which, if not avoided, could result in material damage.
The danger symbol used and the text indicate the actual danger and the related preventative measures.
WARNING
Incomplete copy of the Operating Instructions
Working with individual pages of these Operating Instructions may cause damage
to property or personnel by failure to observe safety-related information.
X Always work with the complete document.
DANGER
Explosion hazard
Death, serious injury or material damage may occur if an electrical plug connection
is removed in a potentially explosive atmosphere during operation or if the device is
subjected to hazardous knocks.
X Only use the device in the following environments:
- Environments not subject to explosion hazards
- Potentially explosive atmosphere, Zone 22 (according to ATEX 94/9/EC)
X Prevent the device from being subjected to hazardous knocks.
X Only operate the device in potentially explosive atmospheres if it is correctly
mounted.
X Switch off the device before removing the plug connections.
WARNING
Live parts in the device
When the device is opened, there is a risk of electric shock if live parts are touched.
X The device must not be opened.
WARNING
Potential equalization currents
Large equalization currents between the protective ground systems of different de-
vices may cause operational malfunctions due to signal interference and may even
cause fires.
X If necessary, a potential equalization conductor should be installed parallel to the
cable. This should have a cross-section that is a multiple of the cable shield.
CAUTION
Electrostatic discharge
Electrostatic discharge may damage or destroy electronic components.
X Avoid contact with components (such as connector pins) that are susceptible to
electrostatic discharge.
X Discharge (by touching a grounded metal object) any static charge accumulated
in your body before touching the device.
CAUTION
Non-isolated interfaces
The device may be damaged due to potential differences.
X The GND terminals of all bus stations must be connected.
CAUTION
Sensitive resistive touch surface
Damage to the resistive touch due to the use of pointed or sharp objects.
X Only activate the resistive touch with your finger or a stylus.
X When wearing gloves, ensure that these are clean. They must not be covered
with abrasive dust or sharp particles.
CAUTION
Data loss
During a write operation, the SD card may lose data or may be destroyed if it is re-
moved or if there is a power failure.
X Only insert the SD card when the device is in a de-energized state.
X Avoid write operations to SD cards. Reasons:
- The number of write cycles possible on SD cards is limited.
- A power failure during write operations will most likely lead to loss of data.
X Only remove the SD card when the device is in a de-energized state.
X Before switching off, ensure that no software write operations to the SD card are
in progress.
CAUTION
Device condensation
If the device is or was exposed to climatic changes (temperature fluctuation, air hu-
midity) moisture can form on or in the device (device condensation). In this case,
there is a risk of short-circuit.
X The device must not be switched on when device condensation is present.
X If condensation is present on the device, or if it was exposed to temperature fluc-
tuations, it must be allowed to adjust to room temperature (do not expose the de-
vice to the direct heat of heating devices) prior to commissioning.
CAUTION
UV light
When exposed to UV light, plastics can embrittle and the lifespan of the device is
reduced.
X Protect the device against direct sunlight (UV rays).
CAUTION
Cleaning the device
Damage to the device due to the use of pointed or sharp objects or by liquids.
X Do not use any pointed or sharp objects (e.g. knife) for cleaning.
X Do not use any aggressive or abrasive cleaning agent or solvent.
X Avoid any liquid entering the device (risk of short-circuit).
4.1 Overview
Fig. 5 Operating and indication elements of the 5.7" and 7.0" devices
Element Function
A Control button Function depends on the software used.
B Display Display operating and indication elements.
C Touch sensor Resistive touch:
Detection of the actuation of the operating elements shown on the
display. These devices are operated by touching the operating
elements with your finger or with a stylus.
D SD slot 0 Slot for SD card.
Tab. 5 Operating and indication elements
5 Installation
) Read Chapter 3 Safety regulations, 11 before installing and commissioning the de-
vice. This contains important information for your personal safety.
5.3 Interfaces
WARNING
Potential equalization currents
Large equalization currents between the protective ground systems of different de-
vices may cause operational malfunctions due to signal interference and may even
cause fires.
X If necessary, a potential equalization conductor should be installed parallel to the
cable. This should have a cross-section that is a multiple of the cable shield.
CAUTION
Operational malfunctions
Use of unsuitable or improperly prepared cables, as well as incorrect wiring will
mean that neither the values stated in the technical data nor the electromagnetic
compatibility (EMC) can be ensured.
X Only use cables prepared by specialists.
X The cables used must be prepared according to the interface description in this
document.
X The wiring instructions for the relevant interface must be observed when wiring
the device.
X Any generally applicable regulations and standards must be fulfilled.
CAUTION
Non-isolated interfaces
The device may be damaged due to potential differences.
X The GND terminals of all bus stations must be connected.
) The interfaces will vary depending upon the device version. See nameplate and Chapter
2.3 Device versions, 6.
3
5…8 mm
1 Strip the cable end so that approx. 3 cm of the shield braid is exposed.
2 Fold back the shield braid over the cable shield.
3 Fit approx. 3 cm of heat shrinkable tubing over the folded back end of the shield braid or use a
rubber grommet.
5…8 mm of the shield braid must be exposed at the cable end.
The folded back shield braid end must be covered by the heat shrinkable tubing or by the
rubber grommet.
4 Fit the D-Sub connector to the cable end:
The exposed metal shield braid must be clamped to the connector casing with the cable clamp.
A B C D E F
) The EMC values stated in the technical data (immunity and emission) can only be guar-
anteed by observing the prescribed cable preparation!
Wiring Phoenix Contact MSTB 2.5/3-ST-5.08 connector, Phoenix order no. 1757022 is supplied with the
device.
+24 VDC 0V
Fig. 11 Phoenix Contact MSTB 2.5/3-ST-5.08 connector (view from the wiring side)
Connection Assignment
+24 VDC +24 VDC power supply
? Functional earthing connected with connector cover.
Does not have to be connected.
This connection can be used as protective earthing connection if the
mounting environment requires this.
0V 0 V power supply
Tab. 7 Assignment of connector
CAUTION
Non-isolated interfaces
The device may be damaged due to potential differences.
X The GND terminals of all bus stations must be connected.
1 2 3 4 5
6 7 8 9
) When preparing the cables, ensure that there is a low-resistance connection between
the cable shield and the connector casing (o Chapter 5.3.2, 26).
5.3.5 Ethernet
LINK ACT
CAUTION
Forces acting on the Ethernet interface
Communication can be disturbed and the connection mechanics damaged if the
Ethernet interface is exposed to severe vibration or the RJ45 plug connection is
pulled.
X Protect the RJ45 connection from severe vibration.
X Protect the RJ45 connection from pulling on the socket.
CAUTION
Not electrically isolated SmartWire-DT system
The device may be damaged due to potential differences.
X Provide a common star point for the earth wiring.
) The documents can also be downloaded from www.eaton.com (search document No. via
search field of the home page).
Element Function
A POW/AUX interface Power supply interface for SmartWire-DT
(o Chapter 5.3.8.3, 35)
B POW LED Lit if the SmartWire-DT netwerk is supplied with current.
C SWD LED Indicates whether the physical structure of the SmartWire-DT network
matches the target configuration. Each time the power supply is
switched on, the configurations are compared (o Chapter 5.3.8.5,
37).
D Config LED Indicates whether the project configuration of the SWD master defined
in the PLC matches the target configuration of the SmartWire-DT
network stored in the device. Each time the power supply is switched
on, the configurations are compared (o Chapter 5.3.8.5, 37).
E Configuration button Configuring the SmartWire-DT network.
F SWD interface SmartWire-DT interface (o Chapter 5.3.8.4, 36)
Tab. 12 Operating and indication elements of the SmartWire-DT Master interface
Wiring WAGO connector, order no. 734-104 is supplied with the device.
Connection Assignment
+24 VDC POW Supply voltage UPow +24 VDC
0 V POW Supply voltage UPow 0 V
+24 VDC AUX Supply voltage UAux +24 VDC
0 V AUX Supply voltage UAux 0 V
Tab. 13 Assignment of connector
For UAux, an external over-current and short-circuit protection by miniature circuit-breaker or fuse
is required.
87654321
Cabling Use only the following ribbon cables for connecting the SmartWire-DT netwerk at the SWD inter-
face:
SWD4-100LF8-24 with the relevant blade terminals SWD4-8MF2 or
SWD4-(3/5/10)F8-24-2S (prefabricated cable)
) Detailed instructions on fitting the blade terminal SWD4-8MF2 are provided in the Doc-
ument «MN05006002Z-EN Manual SmartWire-DT The System», Chapter «Fitting the
blade terminal SWD4-8MF2».
Configuration check
Each time the supply voltage is switched on, the configuration checks are performed:
1 The slaves actually found on the network are compared with the target configuration stored in the
device.
If the physical structure of the SmartWire-DT network matches the target configuration, the
SmartWire-DT network is ready for data exchange.
2 The target configuration stored in the device is compared with the project configuration defined in
the PLC.
If the target configuration matches the project configuration, the Config LED lights up.
5.3.9 CAN
The CAN interface is not electrically isolated.
CAUTION
Non-isolated interfaces
The device may be damaged due to potential differences.
X The GND terminals of all bus stations must be connected.
1 2 3 4 5
6 7 8 9
)
Pin 3 (CAN-GND) and 6 (GND) are connected internally in the device.
nc: Pins 1, 4, 5, 8 and 9 must not be connected.
The CAN bus drivers are fed internally with power.
No power supply for third-party devices is implemented on the CAN connector.
Cable specifications
Rated surge impedance 120 :
Permissible surge impedance 108…132 :
Capacitance per unit length < 60 pF/m
Core cross-section / max. cable length t 0.25 mm2 / 100 m
t 0.34 mm2 / 250 m
t 0.75 mm2 / 500 m
Tab. 18 Cable specifications
) The use of repeaters is recommended with cables over 1000 m in length. Repeaters
can also be used to implement electrical isolation. Refer to the documentation of the
repeater manufacturer for further information.
Observe the recommendations of the CiA (CAN in Automation).
When preparing the cables, ensure that there is a low-resistance connection between
the cable shield and the connector casing (o Chapter 5.3.2, 26).
5.3.10 Profibus
The Profibus interface is not electrically isolated.
CAUTION
Non-isolated interfaces
The device may be damaged due to potential differences.
X The GND terminals of all bus stations must be connected.
5 4 3 2 1
9 8 7 6
Wiring Shielded twisted pair cables, cable type A (in accordance with Profibus standards IEC/EN 61158
and IEC/EN 61784) must be used.
Cable specifications
Rated surge impedance 150 :
Permissible surge impedance 135…165 :
Capacitance per unit length < 30 pF/m
Loop resistance < 110 :/km
Core cross-section t 0.34 mm2 (22 AWG)
Tab. 21 Cable specifications
) When preparing the cables, ensure that there is a low-resistance connection between
the cable shield and the connector casing (o Chapter 5.3.2, 26).
) The maximum cable length can be increased by using repeaters. Refer to the documen-
tation of the repeater manufacturer for further information.
Only use bus terminal connectors that are specified for use in the Profibus network. They hold both
bus cables on a bus station and ensure a low impedance connection of the cable shield to the
shield reference potential of the bus station. These bus terminal connectors contain the Profibus
cable termination that can be switched on as required.
A bus segment must be provided with cable termination at both ends. The termination is passive
and is fed from the bus station. It ensures a defined idle signal on the bus when no bus station is
transmitting. These bus terminations should be implemented externally in the connector casing
according to the Profibus standard (they can also be implemented with the bus terminating
connector described above).
1 1 1 1
390 6 6 6 6 390
2 2 2 2 7
3 7 7 7
B B3 B B3 B B3 220
220 8A A 8A A 8A A 8
4 4 4 4
9 9 9 9
390 5 M5EXT M5EXT 5 M5EXT M5EXT 5 M5EXT M5EXT 5 390
(GND) (GND) (GND) (GND) (GND) (GND)
)
The bus segment must be terminated at both ends.
No more than two terminations must be provided on each bus segment.
At least one of the two terminations must be fed by the bus station.
Transmission faults can occur if operation is carried out without the correct termina-
tion on the Profibus network.
5.3.11 RS485
The RS485 interface is not electrically isolated.
CAUTION
Non-isolated interfaces
The device may be damaged due to potential differences.
X The GND terminals of all bus stations must be connected.
1 2 3 4 5
6 7 8 9
Cable specifications
Rated surge impedance 120 :
Permissible surge impedance 108…132 :
Max. cable length 1200 m
Possible baud rates 9600 Bit/s
19200 Bit/s
38400 Bit/s
57600 Bit/s
115200 Bit/s
Tab. 24 Cable specifications
) When preparing the cables, ensure that there is a low-resistance connection between
the cable shield and the connector casing (o Chapter 5.3.2, 26).
) The maximum cable length can be increased by using repeaters. Refer to the documen-
tation of the repeater manufacturer for further information.
A bus segment must be provided with cable termination (120 :) at both ends. These terminations
must be connected directly between pin 3 and 7 in the connector.
1 1 1 1
6 6 6 6
2 7A A
2 7A A
2 7A A
2 7
120 3 120
B B3 B B3 B B3
8 8 8 8
4 4 4 4
9 9 9 9
5 GND GND 5 GND GND 5 GND GND 5
5.4 Mounting
CAUTION
Operational malfunctions
Use of unsuitable or improperly prepared cables, as well as incorrect wiring will
mean that neither the values stated in the technical data nor the electromagnetic
compatibility (EMC) can be ensured.
X Only use cables prepared by specialists.
X The cables used must be prepared according to the interface description in this
document.
X The wiring instructions for the relevant interface must be observed when wiring
the device.
X Any generally applicable regulations and standards must be fulfilled.
CAUTION
Device condensation
If the device is or was exposed to climatic changes (temperature fluctuation, air hu-
midity) moisture can form on or in the device (device condensation). In this case,
there is a risk of short-circuit.
X The device must not be switched on when device condensation is present.
X If condensation is present on the device, or if it was exposed to temperature fluc-
tuations, it must be allowed to adjust to room temperature (do not expose the de-
vice to the direct heat of heating devices) prior to commissioning.
1 Check the device for damage in transit.
) The device must only be installed and commissioned in perfect technical condition and
in compliance with this document.
2 Mount the device in the control cabinet, control panel or the control desk. See Chapter 5.4.1
Mounting the device, 47.
3 Connect the device as required.
Follow the instructions on wiring the relevant interface. See Chapter 5.3 Interfaces, 23.
) The device is not provided with an On/Off switch. If the power supply is not provided
with a switch, the device will start up (boot) as soon as it is connected to the power sup-
ply.
117.0 +1/-1
87.0 +1/-1
Fig. 26 Mounting cutout for 3.5" devices Fig. 27 Mounting cutout for 5.7" devices
122.0 +1/-1
197.0 +1/-1
3 If no sealing strip is glued in the groove (A) on the rear of the device front plate, insert the sealing
strip supplied in the groove (A) and cut it so that the join is tight.
CAUTION
Poor sealing
Poor sealing resulting from the twisting of the sealing strip or due to a gap between
the ends of the sealing strip.
X The join of the sealing strip must be positioned on the bottom of the device.
X Do not twist the sealing strip when it is inserted.
X Cut the sealing strip to a suitable length so that the join is tight.
5 Fit the device from the front into the mounting cutout.
6 Clip on the retaining brackets in the recesses provided for them on the device as shown below and
fix the device by tightening the threaded pins until the front of the MICRO PANEL is flush with the
surface of the control cabinet at the fixing points.
CAUTION
Mechanical damage to the device
Tightening the threaded pins too tightly may damage the device.
X Tighten threaded pins with a max. tightening torque of 0.1 Nm.
3.5" devices:
One retaining bracket each at all four fixing positions
Fig. 31 3.5" devices with four retaining brackets (meet IP65 / NEMA 4X requirements)
Fig. 32 5.7" devices with four retaining brackets (do not meet IP65 / NEMA 4X requirements)
5.7" devices which must be mounted in accordance with IP65 / NEMA 4X or used in potentially
explosive atmospheres:
One retaining bracket each at all six fixing positions
Fig. 33 5.7" devices with six retaining brackets (meet IP65 / NEMA 4X requirements)
Fig. 34 7.0" devices with four retaining brackets (do not meet IP65 / NEMA 4X requirements)
7.0" devices which must be mounted in accordance with IP65 / NEMA 4X or used in potentially
explosive atmospheres:
One retaining bracket each at all eight fixing positions
Fig. 35 7.0" devices with eight retaining brackets (meet IP65 / NEMA 4X requirements)
6 Operation
) Read Chapter 3 Safety regulations, 11 before working with the device. This contains
important information for your personal safety.
CAUTION
Sensitive resistive touch surface
Damage to the resistive touch due to the use of pointed or sharp objects.
X Only activate the resistive touch with your finger or a stylus.
X When wearing gloves, ensure that these are clean. They must not be covered
with abrasive dust or sharp particles.
CAUTION
Device condensation
If the device is or was exposed to climatic changes (temperature fluctuation, air hu-
midity) moisture can form on or in the device (device condensation). In this case,
there is a risk of short-circuit.
X The device must not be switched on when device condensation is present.
X If condensation is present on the device, or if it was exposed to temperature fluc-
tuations, it must be allowed to adjust to room temperature (do not expose the de-
vice to the direct heat of heating devices) prior to commissioning.
) The lifespan of the backlight can be increased by reducing the brightness (o Document
«MN05010007Z-EN System Description Windows CE»).
CAUTION
Data loss
During a write operation, the SD card may lose data or may be destroyed if it is re-
moved or if there is a power failure.
X Only insert the SD card when the device is in a de-energized state.
X Avoid write operations to SD cards. Reasons:
- The number of write cycles possible on SD cards is limited.
- A power failure during write operations will most likely lead to loss of data.
X Only remove the SD card when the device is in a de-energized state.
X Before switching off, ensure that no software write operations to the SD card are
in progress.
) Do not apply any force (SD cards are protected against reverse insertion).
) Read Chapter 3 Safety regulations, 11 before working with the device. This contains
important information for your personal safety.
7.2 Maintenance
Devices with resistive touch are maintenance-free. However, the following work may be necessary:
Cleaning of the resistive touch if contaminated.
Recalibration of the resistive touch if it does not respond correctly to touch operation.
CAUTION
Cleaning the device
Damage to the device due to the use of pointed or sharp objects or by liquids.
X Do not use any pointed or sharp objects (e.g. knife) for cleaning.
X Do not use any aggressive or abrasive cleaning agent or solvent.
X Avoid any liquid entering the device (risk of short-circuit).
1 Clean the resistive touch carefully with a clean, soft, damp cloth.
With stubborn contamination, spray a little cleaning agent onto the damp cloth first.
7.2.3 Battery
The integrated battery cannot be exchanged. Lifespan, see Chapter 9.4 System, 67.
7.3 Service
7.3.1 Repairs
The device must only be opened by the manufacturer or by an authorized repair center.
Contact your local supplier or Eaton technical support for repairs.
Only the original packaging should be used for transporting the device.
7.4 Troubleshooting
) Read Chapter 3 Safety regulations, 11 before installing and commissioning the de-
vice. This contains important information for your personal safety.
8.2 Storage
The ambient conditions for storage must be fulfilled. See Chapter 9.9 Ambient conditions, 74.
8.3 Transport
Damage to the device must be prevented during transport (use an appropriate packaging).
The ambient conditions must be fulfilled even when the device is transported. See Chapter 9.9 Ambient
conditions, 74.
1 Check the device on arrival for damage in transit.
8.4 Disposal
DANGER
Explosive and toxic materials
Any improper handling causes a risk of explosion due to the lithium battery soldered
in the device.
X Dispose of the device properly.
Devices that are no longer used must be properly disposed of in accordance with the applicable national
regulations or returned to the manufacturer or sales office.
9 Technical data
100
85
121 25
136 30
120.6
135
195.6 33
210 38
9.2 Display
Property XV-102
Type TFT-LCD
Resolution (W u H)
3.5" devices QVGA (320 u 240 pixels)
5.7" devices VGA (640 u 480 pixels)
7.0" devices WVGA (800 u 480 pixels)
Visible display area
3.5" devices 70 mm u 53 mm (3.5" screen diagonal)
5.7" devices 115 mm u 86 mm (5.7" screen diagonal)
7.0" devices 152 mm u 91 mm (7.0" screen diagonal)
Color resolution
3.5" devices
XV-102-…-35MQR… 32 grayscales
XV-102-…-35TQR… 64k colors
5.7" and 7.0" devices 64k colors
Contrast ratio Normally 300:1
Brightness Normally 250 cd/m2
Backlight
Technology LED
Dimmable via software
3.5" devices 100 % … 1 % brightness
5.7" devices 100 % … 30 % brightness
7.0" devices 100 % … 20 % brightness
Lifespan Normally 40 000 h
Resistive touch back panel Touch sensor (glass with foil)
Tab. 31 Display
Property XV-102
Type Resistive touch
Technology 4-wire
Tab. 32 Touch sensor
9.4 System
Property XV-102
Processor RISC, 32-bit, 400 MHz
Internal memory
DRAM 64 MByte
NAND Flash 64 MByte
NVRAM
XV-102-A… –
All device versions 125 KByte
except XV-102-A…
NOR Flash
3.5" devices –
5.7" and 7.0" devices 2 MByte
External memory
SD memory card slot 1u SDA specification 1.00
Suitable for SD cards (not for SDHC cards or cards
of newer standard)
Use only original accessories.
Real-time clock (battery backup)
Battery type CR2032 (190 mA/h), maintenance-free (soldered)
Backup time in de-energized state Normally 10 years
Tab. 33 System
9.5 Interfaces
Property XV-102
Ethernet 100Base-TX / 10Base-T
USB Device USB 2.0, not electrically isolated
Interfaces, depending on the device version:
USB Host USB 2.0 (1.5 / 12 / 480 MBit/s),
not electrically isolated
SmartWire-DT Master SmartWire-DT, not electrically isolated
o Chapter 9.5.2, 70
RS232 (System Port) RS232, not electrically isolated
CAN CAN, not electrically isolated
Profibus Profibus, not electrically isolated, max. 1.5 Mbit/s
RS485 RS485, not electrically isolated
Power supply o Chapter 9.5.1, 69
DIAG Only for service tasks
Jumper UPD/RUN Only for service tasks
Tab. 34 Interfaces
Property XV-102
Rated voltage 24 VDC SELV (safety extra low voltage)
Permissible voltage RMS value:
19.2 … 30.0 VDC
(rated voltage -20 % / +25 %)
Absolute with ripple:
18.0… 31.2 VDC
Battery operation:
18.0… 31.2 VDC
(rated voltage -25 % / +30 %)
35 VDC for a period < 100 ms
Voltage dips 10 ms from rated voltage (24 VDC)
5 ms from undervoltage (20.4 VDC)
Power consumption
3.5" devices Max. 5 W
5.7" and 7.0" devices
Basic device Max. 7 W
USB stations on USB host Max. 2.5 W
Total Max. 9.5 W
Current consumption
Continuous current Max. 0.4 A (24 VDC)
Continuous current
3.5" devices Max. 0.2 A (24 VDC)
5.7" and 7.0" devices Max. 0.4 A (24 VDC)
Starting current inrush 1.5 A2s
Protection against reverse polarity Yes
Fuse Yes (replacement only by the manufacturer or by an
authorized repair center)
Potential isolation No
Tab. 35 Power supply
Property XV-102
Supply voltage UAux (control voltage for contactor coils)
Operating voltage
Rated voltage 24 VDC
Permissible voltage RMS value:
20.4…28.8 VDC (rated voltage -15 % / +20 %)
Input voltage residual ripple Max. 5 %
Protection against reverse polarity Yes
Current
In accordance with DIN VDE 0641, Max. 3 A1)
Part 11 and IEC/EN 60898
In accordance with UL 508 Max. 2 A1)
and CSA-22.2, No. 14
Short-circuit strength No, external protection required
(e. g. FAZ Z3, o Chapter 5.3.8.3, 35)
Power loss Normally 1 W
Potential isolation No
Rated operating voltage of Normally UAux - 0.2 V
24 VDC slaves
Supply voltage UPow (for SmartWire-DT slaves)
Supply voltage
Rated voltage 24 VDC
Permissible voltage RMS value:
20.4…28.8 VDC (rated voltage -15 % / +20 %)
Input voltage residual ripple Max. 5 %
Protection against reverse polarity Yes
Current Max. 0.7 A
Overload proof Yes
Inrush current and length 12.5 A/6 ms
Power loss at 24 VDC 1.0 W
Potential isolation between UPow and No
15 V SmartWire-DT supply voltage
Bridging voltage dips 10 ms
Property XV-102
Repetition rate 1s
Status indication Yes (LEDs)
Tab. 36 POW/AUX (power supply interface for SmartWire-DT)
1) If contactors and/or motor starters with a total power consumption > 3 A (DIN VDE 0641, Part 11 and IEC/EN 60898) or > 2 A
(UL 508 and CSA-22.2, No. 14) are connected, a power feeder module EU5C-SWD-PF1 or EU5C-SWD-PF2 has to be used.
Property XV-102
SmartWire-DT supply voltage UVP
Rated operating voltage 14.5 VDC ±3 % (14.0…15.0 VDC)
(internally transformed supply voltage UPow)
Current Max. 0.7 A1)
Short-circuit strength Yes
Number of SmartWire-DT slaves on the Max. 99
SmartWire-DT netwerk
Address setting of the SmartWire-DT slaves Automatic
Baud rate 125 Kbit/s
250 Kbit/s
1) If SmartWire-DT slaves with a total power consumption > 0.7 A are connected, a power feeder module EU5C-SWD-PF2 has
to be used.
Property XV-102
Front IP65, Enclosure Type 4X (indoor use only)
Required number of retaining brackets and
threaded pins for mounting:
3.5" devices: 4 pieces each
5.7" devices: 6 pieces each
7.0" devices: 8 pieces each
Rear IP20, Enclosure Type 1
Tab. 38 Enclosure ratings
Property XV-102
EMC 2004/108/EC
Explosion protection II 3D Ex tc IIIC T70°C IP6x (ATEX 94/9/EC):
Zone 22, category 3D1)
Required number of retaining brackets and
threaded pins for mounting:
3.5" devices: 4 pieces each
5.7" devices: 6 pieces each
7.0" devices: 8 pieces each
UL Devices delivered with a glued in seal:
UL 508, file no. E205091
3.5" devices delivered with a loose seal:
UL 60950, file no. E208621
Required number of retaining brackets and
threaded pins for mounting:
3.5" devices: 4 pieces each
5.7" devices: 6 pieces each
7.0" devices: 8 pieces each
Property XV-102
EMC (in relation to CE)
IEC/EN 61000-6-2 Immunity for industrial areas
IEC/EN 61000-6-4 Emission for industrial environments
IEC/EN 61131-2 Programmable logic controllers, equipment require-
ments and tests
IEC/EN 61000-6-3 Emission for residential, commercial and light-
(5.7" devices only without cables at the inter- industrial environments
faces USB Host and USB Device)
Explosion protection (in relation to CE)
ATEX 94/9/EC: Zone 22, Category 3D (II 3D Ex tc IIIC T70°C IP6x):
IEC/EN 60079-0 Explosive atmospheres: equipment - general
requirements
IEC/EN 61241-0 Electrical apparatus for use in the presence of
IEC/EN 61241-1 combustible dust
Safety
IEC/EN 60950 Safety of information technology equipment
UL 60950 (only 3.5" devices)
UL 508 Industrial control equipment
(Engineering conditions of acceptability by UL,
o Kapitel 5.2.1, 22)
Product standards
EN 50178 Electronic equipment for use in power installations
IEC/EN 61131-2 Programmable logic controllers, equipment require-
ments and tests
Tab. 40 Applicable standards and regulations
Property XV-102
Temperature
Operation 0 … 50°C
Storage / Transport -20 … 60°C
Relative air humidity 10 … 95%, non-condensing
Vibration in accordance with IEC/EN 60068-2-6 Displacement:
5…9 Hz: 3.5 mm
9…60 Hz: 0.15 mm
Acceleration:
60…150 Hz: 2 g
Schock in accordance with IEC/EN 60068-2-27 15 g / 11 ms
Fall test In accordance with IEC/EN 60068-2-31
Tab. 41 Ambient conditions
Eaton Corporation
Electrical Sector
1111 Superior Avenue
Cleveland, OH 44114 USA
Eaton.com