Carbon Dioxide/Temperature Transmitter: Ndir Co Sensor, Universal Outputs, Optional Relay

The document describes the SERIES CDT Carbon Dioxide and Temperature Transmitters. It uses a single beam dual wavelength NDIR sensor to accurately monitor CO2 concentration and temperature. Key features include increased sensor accuracy, digital pressure adjustment, and field calibration. Models include options for an integral LCD display and relay output.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
71 views

Carbon Dioxide/Temperature Transmitter: Ndir Co Sensor, Universal Outputs, Optional Relay

The document describes the SERIES CDT Carbon Dioxide and Temperature Transmitters. It uses a single beam dual wavelength NDIR sensor to accurately monitor CO2 concentration and temperature. Key features include increased sensor accuracy, digital pressure adjustment, and field calibration. Models include options for an integral LCD display and relay output.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

®

AIR QUALITY
SERIES CDT

CARBON DIOXIDE/TEMPERATURE TRANSMITTER
NDIR CO2 Sensor, Universal Outputs, Optional Relay 1.10
[27.96] .552
YEAR LIMITED
WARRANTY

[14.02]

2x .176
[4.47]
4.50 3.000
[114.30] [76.20]
.573
[14.56]
2.80
[71.12] 1.08
[27.33] 1.18 1.16
[30] [29.39]

3.65 .33
[92.72] [8.38] 3x .15
3x .37 [3.87]
European Style North American Style [9.36]
3.56
[90.42]

4-25/32˝ 11-49/64˝
1/8˝ [121.612] [298.956]
[3.175] 1-15/64˝
4-9/32˝ [31.411]
[108.912] 2-13/16˝
[71.238]
VIDEO ON
LI
NE

Duct Ø3-5/16˝
[84.074]

The SERIES CDT Carbon Dioxide and Temperature Transmitters accurately monitor SPECIFICATIONS
the CO2 concentration and temperature in indoor environments to help achieve Sensor: Single beam, dual wavelength NDIR.
energy savings. For increased sensor accuracy, a single beam dual wavelength non- Range: CO2: 0 to 2000 or 0 to 5000 ppm (depending on model); Temperature: 32 to
dispersive infrared (NDIR) sensor is used to automatically correct the measurement 122°F (0 to 50°C).
in both occupied* and unoccupied buildings against light source aging effects. The Accuracy: CO2: ±40 ppm ±3% of reading; RH: ±2% (10 to 90% RH); Temperature:
single beam dual wavelength sensor technology provides the highest level of accuracy ±1°C @ 25°C.
compared to Automatic Baseline Correction methods which can unintentionally shift Temperature Dependence: ±8 ppm/°C at 1100 ppm.
the calibration based on CO2 levels and barometric pressure conditions. In order to Non-Linearity: 16 ppm.
achieve a higher level of accuracy, the Series CDT includes digital barometric pressure Pressure Dependence: 0.13% of reading per mm of Hg.
adjustment and the ability to field-calibrate the sensor. Response Time: 2 min for 99% step change.
For applications that require visual indication, the wall mount configurations of the Duct Air Velocity Range: 0-4000 FPM (20.32 m/s).
Series CDT can be ordered with an integral LCD display. Push buttons are standard on Temperature Limits: 32 to 122°F (0 to 50°C).
all configurations of the transmitters for access to the menu structure, but wall mount Humidity Limits: 10 to 95% RH (non-condensing).
Carbon Dioxide

configurations can be ordered without the buttons. To prevent tampering, the action of Power Requirements: 16 to 35 VDC or 19 to 28 VAC.
Transmitters

the buttons can be locked out using an internal dip switch selection. Power Consumption: Average: 2 w; Peak: 3.75 w.
Output: Current: 4 to 20 mA (max. 500 Ω); Voltage: 0 to 5 VDC or 0 to 10 VDC
FEATURES/BENEFITS (min. 500 Ω); Relay: SPST NO rated 2 A @ 30 VDC.
• Single beam dual wavelength NDIR sensor eliminates draft due to light source aging Weight: 4.4 oz (125 g).
• Integral passive temperature outputs reduce number of devices mounted in the Enclosure Rating: Duct mount: NEMA 4X (IP66) for housing only; Wall mount:
space IP20.
• Service display tool available for models without an integral LED Agency Approvals: CE.
• Optional integral display and relay output

APPLICATIONS
• Demand control ventilation in schools, office buildings, hospitals, and other indoor
environments
• LEED® certification

*For buildings occupied 24 hours per day, it is recommended that calibration be


verified every 6 to 12 months depending on application.

MODEL CHART ACCESSORIES


Example CDT -2 N 4 4 -LCD CDT-2N44-LCD Model Description
Series CDT Carbon dioxide/ GCK-200CO-2000CO2 Calibration gas kit includes a 99.99% nitrogen gas cylinder
temperature transmitter for calibrating the zero point and a 200 PPM CO / 2000
Range 2 0 to 2000 ppm CO2 range PPM CO2 gas cylinder for calibrating the span point on
5 0 to 5000 ppm CO2 range Dwyer’s gas sensing transmitters
A-449 Remote LCD display allows remote indication of
Configuration N North American style wall mount select Dwyer® wall mount transmitters for validation or
E European style wall mount certification purposes
D Duct mount A-449A Remote LCD display with buttons allows remote indication
CO2 4 4 to 20 mA / 0 to (5 or 10) VDC and calibration of select Dwyer® wall mount transmitters for
Temperature 0 None validation and certification purposes
Output 4 4 to 20 mA / 0 to (5 or 10) VDC A-CDT-KIT Accessory kit including terminal block and power supply
A 10 KΩ NTC thermistor type III
B 10 KΩ NTC thermistor type II
C 3 KΩ NTC thermistor
D Pt100 Ω RTD
E Pt1000 Ω RTD
F 20 KΩ NTC thermistor
Options FC Factory calibration certificate
LCD LCD display (wall only)
RLY Relay
NBC No buttons (wall only)
GCK-200CO-2000CO2 A-449