Arc Proof LV SWGR
Arc Proof LV SWGR
6
Arc-proof low voltage switchgear and
controlgear assemblies
Technical Application Papers
1.2 Standards concerning switchboards and 2.3 Effects of the electric arc on human
relevant applicability ............................... 3 beings ................................................... 14
1.5.1 Degrees of protection provided by switchgear 3.2.3 Switchgear and controlgear assemblies with
and controlgear assemblies ................................... 8 current limiting circuit-breakers............................ 18
1
Technical Application Papers
In the last years safety in LV electrical installations has overpressure, are almost always ejected to the outside
taken an increasingly dominant role. of the enclosure thus jeopardizing the operator safety.
Also from a normative point of view, the panorama has The European Directive 2006/95/EC states the funda-
become more complete and a large number of users mental safety requirements for low voltage electric ma-
consider safety in the first place among the necessary terials (from 50 V to 1000 V in alternating current, from 75
requirements for their own plant. V to 1500 V in continuos current) to be put on the market
LV switchgear assemblies are undoubtedly the compo- within the European Community.
nents of the electric installation more subject to the direct Among the essential safety requirements defined by this
intervention of personnel (operations, maintenance, etc.) Directive particular importance is given to the need of
and for this reason users demand from them higher and taking technical measures to prevent “temperature rises,
higher safety requirements. electric arcs or radiations which may result in hazards”
In the last years a lot of users have underlined the ques- from occurring.
tion of safety in electrical assemblies with reference to This aspect has always been highly considered for ap-
one of the most severe and destructive electrophysical paratus, but it has been wrongly neglected for electrical
phenomenon: the electric arc. switchgear and only in the last 10-15 years it has been
Unlike tripping devices, for which arc phenomena rep- catching on both at Italian as well as at international
resents one of the standard operating conditions, in LV level.
switchgear the electrical arc is an absolutely anomalous
and rare event.
But, if the electric arc occurs inside LV switchgear it
generates internal overpressures and results in local
overheatings which may cause high mechanical and
thermal stresses in the equipment.
1
The manufacturer is deemed to be the organization taking the responsibility for the
complete ASSEMBLY.
1.4.5 Control, measurement and protection 1.4.6 Assemblies for construction sites (ACS)
boards
1 Generalities about LV switchgear and controlgear assemblies
a)
b)
c)
1.5.1 Degrees of protection provided by As regards enclosed switchboards, the Standard requires
switchgear and controlgear assemblies
1 Generalities about LV switchgear and controlgear assemblies
The figure below shows the degrees of protection which can be obtained with ABB SACE ArTu series switchgear
ArTu L ArTu M - K
IP31 IP43 IP31 IP41 Without door IP41With door IP65
Without door With door Without door with IP41 kit and and ventilated With door and
ventilated panels panels (ArTu K blind panels
(ArTu K only) only)
ArTu L
1,7 kg
IK 08 Impact energy
300mm
Joule 5.00
Impact energy
Joule 20.00
Characteristic letters International mechanical protection With blind
door
Characteristic group numeral from
00 to 10
1.7 Forms of separation Figure 8 - Structural frame form 4b - view with rear doors open. The
metallic separations mounted on the main busbars and on the distribution
1 Generalities about LV switchgear and controlgear assemblies
busbars can be noted, as well as the insulating covers which complete the
The designation form of separation indicates the type of compartments for cable connection
subdivision provided inside the enclosure. Separations
by means of barriers or partitions (metallic or non metallic
materials) are aimed at:
• guaranteeing protection against direct contact
(minimum degree of protection IPXXB), in case of
access to an insulated part of the assembly when
voltage is still applied to the rest of the assembly;
• reducing the likelihood of ignition and propagation
of an internal arc;
• impeding the passage of solid foreign bodies from
one unit of the assembly to an adjacent one (mini-
mum degree of protection IP2X).
A partition is an element of separation between two cu-
bicles, whereas a barrier protects the operator against
direct contact and against the effects of circuit-breaker
arcs propagating in the direction of usual access.
The table below, taken from the Standard IEC 60439-1,
points out the typical forms of internal separation which
can be obtained by using barriers or partitions:
Symbols
d
Caption Representation of the structural frames in form 3a, 3b and 4b for switch-
a Enclosure gear type PC3.0/MNS R
b Internal separation
c Functional units including terminals Form 3a
for associated external conductors
d Busbars, including distribution
busbars
c
a b
Form 1
(no internal separation)
Form 4b
Form 2b Form 3b Terminals not in the same
Terminals separated from Terminals separated from compartment as the
busbars busbars associated functional unit
(2) The temperature-rise limit of 70 K is a value based on the conventional type test.
The type tests prescribed by the Standard IEC 60439-1 An ASSEMBLY used or tested under installation conditions may have connections, the type,
nature and disposition of which will not be the same as those adopted for the test, and a different
include: temperature rise of terminals may result and may be required or accepted. When the terminals
• verification of temperature-rise limits of the built-in compenents are also the terminals for external insulated conductors, the lower of
the corresponding temperature-rise limits shall be applied.
• verification of the dielectric properties (3) Manual operating means within ASSEMBLIES, which are only accessibile after the ASSEMBLY
has been opened, for example draw-out handles, which are operated infrequently, are allowed
• verification of the short-circuit withstand strength of to assume higher temperature rises.
the main circuits (4) Unless otherwise specified, in the case of covers and enclosures which are accessible but need
not to be touched during normal operation, an increase in the temperature-rise limits by 10 K
• verification of the short-circuit withstand strength of is permissible.
the protective circuit (5) This allows a degree of flexibility in respect of equipment (e.g. electornic devices) which is
subject to temperature-rise limits different from those normally associated with switchgear
• verification of the effective connection between and controlgear.
the exposed conductive parts and the protective (6) For the temperature-rise tests in accordance with 8.2.1, the temperature-rise limits shall be
specified by the manufacturer of the ASSEMBLY.
circuit As regards circuit-breakers, the temperature-rise limits are the following:
• verification of clearances and creepage distances - 70 K if an insulated conductor is connected to the terminal.
- 85 K for the terminals of ABB cirucit-breakers if insulated conductors are not directly con-
• verification of mechanical operation nected to them (the temperature-rise of 85 K is always referred to the ambient air temperature
• verification of the degree of protection of 35°C outside the assembly).
(7) Assuming that all the other listed criteria are met, a temperature-rise of 105 K for busbars and
bare copper conductors shall not be exceeded. 105 K refers to the temperature over which
copper annealing may occur.
Hearing
As already mentioned, the electrical arc is a real
explosion, whose sound may cause permanent
injuries to hearing.
In a bolted fault the most harmful effects are prevalently The only indication as regards this matter given by the
of electrodynamic type, proportional to I2, due to the high Standard 439-1 is addressed to the manufacturer who
intensity of the current and to the low fault resistance is obliged to provide all the possible precautions aimed
involved (the medium in which the fault current flows is at reducing the possibility of arcing inside an assembly.
a conducting material). However, there is a guideline document for the verifica-
tion of the internal arc withstand of LV assemblies very
On the contrary, in an arc fault the highest stresses are diffused both at Italian as well as at international level.
of thermal type and proportional to RaI2 owing to the high It is the document IEC 61641 ”Enclosed low-voltage
value taken by the arc resistance Ra; this because the switchgear and controlgear assemblies - Guide for test-
fault current flows in a medium which is always insulating, ing under conditions of arcing due to internal fault” (see
even if extremely ionized. Annex A).
Such stresses manifest themselves essentially in the Since it is a Technical Report type 3, this document
form of: has not the validity of a Standard and consequently the
• high thermal gradients caused by the quick and relevant tests do not represent a mandatory type test to
intense rise in the air temperature; the purpose of obtaining the state of TTA.
• high pressure gradients in the form of pressure
wave; Nevertheless, this document represents a solid technical
• high ionization of the air with consequent reduction reference as regards the testing modalities, defining the
of its insulating strength. main characteristics of an arc-proof assembly and the
requirements it must meet.
Generally speaking, in a LV assembly designed and According to the document IEC 616411 a LV switchgear
tested according to the Standard IEC 60439-1 an arc and controlgear assembly shall:
fault is not very likely to occur; however, should it occur, • limit the risk of injuries/accidents for the personnel
the consequences would be extremely harmful to both in case of internal arc
the equipment as well as the personnel (see Chapters • limit the damage of the switchboard to the section
2.2 and 2.3). affected by the fault, thus allowing the not-affected
part to be put into safety (emergency operations).
1
New edition to be published.
3.2 Characteristics of internal arc-proof The thermal consequences of arcing (exhausted gases at
high temperature) are then limited by designing the inside
3 Internal arc-proof switchgear and controlgear assemblies
All the above with trip times of a few milliseconds and As a consequence it is possible to install some pressure
supplanting the tripping of the CB overcurrent relay sensors which are able to signal the pressure peak as-
which, for example, could be delayed due to current sociated with the arc ignition with a delay of about 10-15
selectivity questions. ms. The signal operates on the supply circuit-breaker
without waiting for the trip times of the selectivity protec-
Figure 1 shows the possible positions where this device tions to elapse, which are necessarily longer.
can be installed inside a switchboard.
The ideal solution is that which provides the installa- Such a system does not need any electronic processing
tion of at least one detector for each column, with the device, since it acts directly on the tripping coil of the
consequent reduction to a minimum of the length of the supply circuit-breaker.
optical fibers carrying the signal.
Obviously it is essential that the device is set at fixed trip
In order to prevent from an unwanted tripping caused by thresholds. When an established internal overpressure
light sources indepent of the arc (lamps, solar radiation is reached, the arc detector intervenes.
etc.), an additional current sensor is often positioned at However, it is not easy to define in advance the value of
the incoming of the main circuit-breaker. overpressure generated by an arc fault inside a switch-
Only in the event of an arc, both the incoming sensor - board.
which detects an “anomalous” current due to the arc fault
- as well as the sensor detecting the light radiation as-
1.
3.2.3 Switchgear and controlgear assemblies than 65kA, the solutions of type a) or b) shall be with no
doubt fit for guaranteeing safety in case of an internal
with current limiting circuit-breakers
3 Internal arc-proof switchgear and controlgear assemblies
arc fault.
A last possibility to limit the effects of an internal arc fore-
sees the installation of current limiting circuit-breakers.
In this case two are the possible solutions:
• separating the parts of the installation at high short- Fig. a
circuit current (Figure a);
• limiting - at each incoming section - the short-circuit
current and consequently the intensity of a possible
arc (Figure b).
In the case a), the current limiting circuit-breaker sepa-
rates the right and the left part of the plant thus limiting
the contribution to the fault (in our case the arc fault) given
by the sound part of the plant to the affected one.
6
Versions MNS3.0, MNS R, MNS iS
Earthing
The switchgear is provided with a continuous electrolytic
copper earthing busbar, with a cross-section suitable for
the switchgear short-circuit rating and pre-set on both
The switchboards of MNS series are available in the fol-
sides for the connection to the earthing network. The fol-
lowing versions, all arc-proof:
lowing elements are connected to the earthing busbar:
• PC3.0/MNS R, main distribution switchboard (Power
• the metallic frame structures of the separate compartments;
Center)
• the not-live metallic parts of the circuit-breakers;
• MNS3.0, Motor Control Center
• the CTs and VTs earthing secondary windings.
• MN iS “intelligent”, Motor Control Center
The other not-live metallic parts of the apparatus are con-
nected to the earthing busbar by means of the metallic
The main characteristics of the primary distribution
frame of the compartment.
switchboard type PC3.0/MNS R are illustrated below.
The doors with installed apparatus are connected to
the structure by means of flexible copper braids. All
the ground connections are made with screws or bolts
provided with gripping washers.
is suitable to house both air as well as moulded-case front part of the switchgear and it can be dedicated to
circuit-breakers. It is accessible through a locked hinged each functional unit or be common to more functional
door. The circuit-breakers can be installed in all the avail- units. It is accessible through a locked hinged door.
able versions, fixed, plug-in and withdrawable, in single The measuring instruments, the protection relays and
or multiple compartments. In order to guarantee the the control and signalling devices are usually mounted
maximum safety level for the operator, the disconnection on the compartment door, whereas any other auxiliary
of air and moulded-case circuit-breakers in withdrawable apparatus, such as circuit-breakers, protection fuses of
version can be carried out also with closed door. command circuits and auxiliary relays are placed inside
the compartment.
Equipment wiring is made of flexible copper cables and
arranged in dedicated wiring channels.
The terminal blocks of each circuit-breaker are separated
and properly identified.
Distribution busbars
Connection terminals
Cable connections
Copper busbar
connections
designed and built for the installation of both ABB air stalled components, PC3.0/MNS R switchgears have
circuit-breakers type Emax as well as moulded-case been designed so as to create separate air flows in all
circuit-breakers type Isomax and Tmax, in fixed, plug-in their internal areas.
and withdrawable versions. They allow the installation
of the main ABB apparatus and of the measuring and Gratings for natural air circulation are placed on the
protection instruments available on the market, according front and rear closing panels in the bottom part of the
to the different design requirements. compartment with air outlet through the gratings on the
roof and on the rear closing panel in the top part of the
compartment.
A = Apparatus area
B = Busbar area
C = Cable area
B
A
Main busbar
compartment
Front
2200
2200
1025/1200/1400/1600
The purpose of this test is verifying that no solid parts fly The arc has been initiated between the phases by means
off in the area adjacent to the assembly due to internal of a bare copper ignition wire connecting the adjacent
arcing; the arc is caused by a current with a prospective conductors across the shortest distance. The arc shall be
short-circuit value specified by the manufacturer. More initiated on three phases so that it can turn into a three-
precisely, compliance with the following seven criteria phase fault and the point of initiation shall be chosen so
must be assessed: that the effects of the resultant arc produce the highest
1. correctly secured doors, covers , etc., do not open; stresses in the assembly. The wire size depends on the
2. parts which may cause a hazard, do not fly off (this test current.
includes both large parts as well as parts with sharp
edges); The initiation points of the arc shall be chosen where, ac-
3. arcing does not cause holes in the freely accessible cording to experience, an internal arc can form, that is:
external parts of the enclosure as a result of burning • at the connection points of the main busbar sys-
or other effects; tems;
4. the indicators arranged vertically do not ignite; • in the live not insulated parts on the supply side of
5. the equipotential bonding arrangement for the acces- the switching and protective devices;
sible parts of the enclosure is still effective; • in the areas of cable terminals.
6. the arc is limited to a defined area without re-ignition
in adjacent areas; Besides, the ignition wire shall be connected only to ac-
7. after the fault extinction, the isolation or the removal of cessible bare conductors.
the functional unit affected by the fault, it is possible
to put into safety the sound part of the switchboard The applied voltage of the test circuit shall be equal to the
(emergency operations). This shall be verified by a highest rated voltage of the assembly, with a tolerance of
dielectric test to be performed at a value which is 1.5 +5% and the prospective short-circuit current, specified
times the rated voltage for the duration of 1 minute. by the manufacturer, shall be verified by a calibration
The test shall be carried out on a test specimen not oscillogram. The peak value of the current is obtained by
previously subjected to an arcing test and the mounting multiplying the short-time withstand current by a factor
conditions shall be as close as possible to those of nor- n. The standardized values of factor n and the relevant
mal service. The test specimen shall be fully equipped power factor values are shown in the following table.
with its internal components and the assigned measure
for the protection of person shall be effective.
To verify that gases or ejected solid parts do not cause
unwanted effects, indicators constituted by pieces of
cotton cloth fitted in mounting frames are used. These
indicators shall be placed up to a maximum height of
2m and at a distance of 30cm ± 5% from the assembly,
RMS value of
short-circuit current
kA cosϕ n
I≤ 5 0.7 1.5
5 < I ≤ 10 0.5 1.7
10 < I ≤ 20 0.3 2
20 < I ≤ 50 0.25 2.1
50 < I 0.2 2.2
Note Values of this table represent the majority of applications. In special locations, for example in the vicinity of transformer or generators, lower values
of power factor may be found, whereby the maximum prospective peak current may become the limiting value instead of the r.m.s.value of the
short-circuit current.
1
4_Ur4 kV
1 k/div
-1
250
kA
1_I1
250 k/div
-250
1
kV
7_Ur1
1 k/div
-1
1
5_Ur5 kV
1 k/div
-1
250
2_I2 kA
250 k/div
-250
1
kV
8_Ur2
1 k/div
-1
1
kV
6_Ur6
1 k/div
-1
250
kA
3_I3
250 k/div
-250
1
kV
9_Ur3
1 k/div
-1
10
V
10_Cam
10/div
-10
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420
20 ms/div ms
B. test with arc ignition at the terminals of an outgoing unit The table below shows the values measured during the
After the circuit calibration an arc-proof test shall be test.
Annex A: Test on an arc-proof switchboard
to self-extinction of the arc. As a consequence also the Total specific energy [A2s] 4.38E+04 1.43E+06 1.52E+06
Arcing power [W] 6.98E+06 5.52E+06 7.55E+06
current value results to be reduced.
Arc duration [ms] 1.1 7.7 7.6
The arc has extinguished within the first half of the full
intended test duration without being ignited again and Legend:
• 1_I1, 2_I2, 3_I3: currents in the three phases
therefore, in compliance with the Technical Report IEC • 4_Ur4, 5_Ur5, 6_Ur6: arcing voltages
61641, such test shall be repeated using the same point • Cosϕ: power factor
of initiation as for the first test.
Since the arc has extinguished within the first half of the The figure below reports the oscillogram showing the
full intended duration also during this repetition, a further arcing voltages (4_Ur4, 5_Ur5, 6_Ur6), the line-to-line
test is not required. voltages (7_Ur1, 8_Ur2, 9_Ur3) and the currents (1_I1,
2_I2, 3_I3) in the three phases. In the oscillogram the
short duration of the currents due to the fast arc extinc-
tion can be noticed.
1
4_Ur4 kV
1 k/div
-1
50
kA
1_I1
50 k/div
-50
1
kV
7_Ur1
1 k/div
-1
1
5_Ur5 kV
1 k/div
-1
50
2_I2 kA
50 k/div
-50
1
kV
8_Ur2
1 k/div
-1
1
kV
6_Ur6
1 k/div
-1
50
kA
3_I3
50 k/div
-50
1
kV
9_Ur3
1 k/div
-1
2
V
10_Cam
2/div
-2
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420
20 ms/div ms
1
4_Ur4 kV
1 k/div
-1
100
kA
1_I1
50 k/div
-100
1
kV
7_Ur1
1 k/div
-1
1
5_Ur5 kV
1 k/div
-1
100
2_I2 kA
50 k/div
-100
1
kV
8_Ur2
1 k/div
-1
1
kV
6_Ur6
1 k/div
-1
100
kA
3_I3
50 k/div
-100
1
kV
9_Ur3
1 k/div
-1
2
V
10_Cam
2/div
-2
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420
20 ms/div ms
ABB SACE
A division of ABB S.p.A.
L.V. Breakers
Via Baioni, 35
24123 Bergamo - Italy
Tel.: +39 035.395.111 - Telefax: +39 035.395.306-433
http://www.abb.com