Installation and Maintenance Manual Softstarters PS S 18/30 300/515
Installation and Maintenance Manual Softstarters PS S 18/30 300/515
maintenance manual
Softstarters
PS S 18/30
300/515
PS S18/30-500
44/76-500 PS S50/85-500
72/124-500
PS S18/30-690
72/124-690
PS S85/147-500
142/245-500 PS S175/300-500
300/515-500
PS S85/147-690
142/245-690 PS S175/300-690
300/515-690
Contents
1. Softstarter marking 3
2. Mounting 4
2.1 Drilling plan 4
2.2 Minimum distance to wall/front 4
3. Connection 5
3.1 Main circuit Bar 1L1, 3L2, 5L3 5
as well as 2T1, 4T2 och 6T3
3.2 Control voltage and control circuit 6
4. Setting 9
4.1 Start ramp 9
4.2 Stop ramp 9
4.3 Initial voltage (UINI) / Current limit 9
function (ILIM)
4.4 Switch for selection of connection 10
type, Line/Delta switch S1
4.5 Basic settings for different 11
applications
5. Maintenance 12
6. Trouble shooting 12
7. Technical data 15
7.1 Dimensions 15
7.2 Circuit diagram 16
WARNING
More than one live circuit
- see diagram
Do not operate machine with the grounding wire disconnected
WARNING
The operation, installation and servicing of this product must
be carried out by a qualified electrician, following installation
standards and safety regulations. Check that you have the
correct softstarter unit in regards to net voltage, rated motor
data and type of connection.
2
1. Softstarter marking
Terminal marking of
Supply voltage Us
control circuit
Softstarter Type
Status indication
Green
Green
Red
Red
Terminal marking of
main circuit
Technical data
acc. to UL 508
Picture 1.1
Serial number
3
2. Mounting
!
All technical data for the softstarter are
valid for an ambient temperature of 40ºC.
For temperatures above of 40ºC, up to Picture 2.1
max. 60ºC, the rated current has to be
derated with 0,8% per ºC.
K L M
PS S18/30-500...44/76-500 105 184 M6
PS S50/85-500...72/124-500
125 234 M6
PS S18/30-690...72/124-690
PS S85/147-500...142/245-500
158 320 M6
PS S85/147-690...142/245-690
Picture 2.2
PS S175/300-500
300/515-500
333 320 M6
PSS175/300-6900
300/515-690
4
3. Connection
!
Remember to set the Line/Delta
switch S1 in the right position.
See further on page 10
Picture 3.2
!
transformer for the current limit
function, see further
instructions section 3.2.6
on page 8.
Motor side
PS S18/30-500...44/76-500
ø 6,5 Pozidriv N° 2
2 x 2,5... 16 mm 2
PS S50/85-500...72/124-500
PS S18/30-690...72/124-690
ø 6,5 2
1 x 6 ... 50 mm2
2 x 6 ... 25 mm
M8 AWG 1...8
13
1 x 6 ... 36 mm22
2 x 6 ... 16 mm
10
4 Nm - 35 lb.in
PS S85/147-500...142/245-500
PS S85/147-690...142/245-690
Max. 22mm
M8 Max. 24mm
Max. 8mm
9 Nm - 80 lb.in
PS S175/300-500...300/515-500
PS S175/300-690...300/515-690
Max. 30mm
M10 Max. 32mm
Max. 10mm
18 Nm - 160 lb.in
5
3. Connection
Picture 3.4
!
Picture 3.5
The earthing cable should be
as short as possible and shall
be connected to an earthing
point close to the softstarter.
Picture 3.6
M3 3,5 x 0,6
2
0,14 ... 2,5 mm
1.............................12 AWG 12...22
2
0,14 ... 2,5 mm
6
3. Connection
Picture 3.7
Picture 3.10
7
3. Connection
Mounting T2
Mount the current transformer close to the softstarter,
see pictures 3.11 and 3.12.
Connection
Check in table 3.1 how many turns you need for the
primary side of the transformer. Connect the trans- Picture 3.12
former acc. to picture 3.12 for one turn, or acc. to
picture 3.11 for two turns.
8
4. Setting
Picture 4.1
Picture 4.2
Picture 4.3
BLUE scale
The same rotating switch as for initial voltage (UINI).
Sets the current limit, if a current transformer T2 is
connected to terminals 11 and 12.
Adjustable in 11 steps between 1,5 and 4 times the
current transformers ratio. When setting the
parameter (ILIM) on the blue scale, the initial voltage
(UINI) will always be a fixed value of 40%.
9
4. Setting
Picture 4.5
Alt 1 Alt 2
10
4. Setting
Tab 4.2
Type of load Ramp time Ramp time Initial voltage Current limit
for start for stop UINI ILIM (xle)
(sec) (sec) (Fixed value) (start)
Bow thruster 10 0 (40%) 2,5
Centrifugal fan 10 0 (40%) 3,5
Centrifugal pump 10 20 (40%) 3
Piston compressor 10 0 (40%) 3
Lifting equipment 10 10 (40%) 3,5
Rotary converter 10 0 (40%) 2,5
Stirrer, Mixer 10 0 (40%) 3,5
Scraper 10 10 (40%) 3,5
Screw compressor 10 0 (40%) 3,5
Screw conveyor 10 10 (40%) 3,5
Unloaded motor 10 0 (40%) 2,5
Conveyor belt 10 10 (40%) 3,5
Heat pump 10 20 (40%) 3
Escalator 10 0 (40%) 3
Hydraulic pump 10 0 (40%) 2,5
11
5. Maintenance
Check that the cooling airways of the softstarter
unit are free from dirt and dust. Check also that
the fan is working and rotating freely. The fan can
be checked at voltage free state, so that rotation
of blades is possible without resistance. They shall
not rotate heavily.
6. Trouble shooting
Motor humming / starts without given start signal
Status / Indication Check
Is start signal given (closed circuit between terminals 5 and 6)?
Is the circuit closed between terminals 6 and 4?
Verify that start and stop signals are not given at the same time.
Is the Line/Delta switch S1 in the right position?
12
6. Trouble shooting
Motor stops during start / continuous operation
Status / Indication Check
Phase loss in the main circuit? Has the thermal overload relay
tripped and opened the main contactor? Has a fuse blown?
Check all connections.
RESET:Give stop signal or disconnect voltage from terminals 1 and 2.
Fault at stop
Phase loss main circuit? Has main contactor opened before stop
ramp has finished? Has a fuse blow?
Is the by-pass contactor stuck in closed position
RESET: Give both start and stop signal or disconnect voltage from
terminals 1 and 2.
13
6. Trouble shooting
Bad motor sound during stop or stop ramp finish too early
Status / Indication Check
!
In some cases the actual ramp time can differ
from the set value. If motor starts/stops softly,
then everything is OK.
14
7. Technical data
7.1 Dimensions
PS S18/30-500
44/76-500 PS S50/85-500
72/124-500
PS S18/30-690...72/124-690
163
163
10
10
120 140
6,5(4x)
6,5(4x)
200
184
250
234
2
9
PS S85/147-500
142/245-500 PS S175/300-500
300/515-500
PS S85/147-690
142/245-690 PS S175/300-690
300/515-690
265
265
1.5
1,5
181 3,1
158
356 3.1
333
320
340
320
340
7(4x)
7(4x)
10
10
15
7. Technical data
16