Shear Wall Design

Transverse reinforcement is required for boundary elements to provide confinement. The document provides input values for the length, width, and height of the boundary element, as well as the steel reinforcement sizes and concrete strength. It calculates the required area of transverse reinforcement for confinement perpendicular and parallel to the wall. The provided transverse reinforcement meets or exceeds the code requirements in both cases.

Uploaded by

er.praveenraj30
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
202 views8 pages

Shear Wall Design

Transverse reinforcement is required for boundary elements to provide confinement. The document provides input values for the length, width, and height of the boundary element, as well as the steel reinforcement sizes and concrete strength. It calculates the required area of transverse reinforcement for confinement perpendicular and parallel to the wall. The provided transverse reinforcement meets or exceeds the code requirements in both cases.

Uploaded by

er.praveenraj30
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 8

Transverse Reinforcement for Boundary Elements

Confinm
Input values only in cells colored yellow
ent
Uni Parallel
Imperial System IS System Units
ts to Wall
Lp = 120 in = 2400 mm ###

tp = 8 in = 400 mm

hw = 1618 in = mm
Length of Boundary
Element, LBZ = 20 in = 900 mm
Width of Boundary
Element,tp = 8 in = 400 mm

HBZ = 120 in Lp = 2400 mm


18.10.6.2
Mu/4Vu (b)

Crossties are not used when hx<


hx = 4.50 in = 341 mm
14in
fy = 60 ksi = 413 Mpa

f'c = 3 ksi = 28 Mpa

CC = 1.0 in = 25 mm
Longitudinal Bar size in
# 8 No = 8∅ mm
Bondary Zone =

Confinement Perpendicular to the Wall:


hc = 4.50 in = 341 mm

Smax = 2.00 in 0.25tp = 100 mm


6 × diameter of
Smax = 6.00 in longitudinal bar or 48 mm

Smax = 7.17 in or 103 mm


ACI
Controlling Hoop, Smax = 2.00 in Sections = 48 mm
18.10.6.2
Required Ash = 0.04 in 2 or = 98 mm2
18.10.6.3
(ACI 21-
Select Hoops Bar Size = #4 = 12 ∅ mm
5)
Hoops Area = 0.20 in 2 = 113 mm2

Select No. of legs,= 2 No Put No. of Legs only = 2 No

Provided Ash = 0.39 in 2 - = 226 mm2

Confinement Parallel to the Wall:


hc = 16.50 in = 816 mm
Required Ash = 0.15 in 2 = 235 mm2

Select Hoops Legs = 4 No = 4 No

Provided Ash = 0.79 in 2 - = 452 mm2


#3

#4

#5 3

#6 4

#4 5

#5 6

#6

#7

#8

#9
###

###

###

###
Confinm
ent
Parallel
to Wall
###in

120 in

8 in
8

10

12

14

16

18

20

22

28

30
2