Partial Discharge
Partial Discharge
Partial discharge (PD) monitoring system by UHF (Ultra high frequency) method has high sensitivity and high S/N ratio.
This UHF PD monitoring system is suitable for PD diagnosis of GIS. Calibration technique of highly sensitive UHF sensor was
clarified by injecting the artificial PD pulses. PD sensitivity of each sensor was verified and calibrated results were fully
satisfactory. PDs were simultaneously measured with both the conventional method described in IEC-60270 and the UHF PD
monitoring system by using many kinds of PD sources and various tank sizes. Owing to this measurement, conversion of dBm
units in UHF PD monitoring system to pC units (apparent charge) became possible and it was clarified that the conversion
curve was independent of PD sources and tank size. These characteristics were confirmed by the theoretical analysis.
Keywords : partial discharge, insulation diagnosis, UHF method, calibration, SF6gas, GIS
measuring systems.
850mm.
1: HV. Coupling Capacitor 6: Pre-Amplifier simultaneously by both detectors. Figure 5 shows examples of
2: Input Unit 7: Spectrum Analyzer measured results for free metallic particles. Figure 5 (a) and (b)
3: SF6 Test Chamber for PD 8: UHF PDM System show frequency spectrum and phase spectrum measured by UHF
4: PD Source 9: Discharge Detector PDM system, and (c) and (d) show phase characteristics, and ƒÓ-q
(b) and (d), it can be observed that the phase characteristics are
Fig. 4. Measuring circuit almost identical. In this case, the magnitude, q, of the PD pulse
(Measuring frequency
655MHz)
(a) Protrusion (3mm): applied voltage 67kV, q=0.6 pC
(d)ƒÓ-q characteristics
(Charge magnitude
17.7pC)
Fig. 5. Typical PD characteristics in free particle case Fig. 6. Frequency and phase spectra for various defects
1228 T.IEEJapan,Vol.122-B,
No .11,2002
Sensitivity Calibration of UHF PDM System
PD pattern was different for each defect. Since the output in the 4.3 Theoretical Analysis of dBm-pC Conversion PDs
UHF methodis measured in dB units, in order to judge the risk of are generated in a minute space where electric field exceeds the
defects,we must convert these units pC units currentlyused from discharge initiation field strength, and the real charge of PDs is
the former.Figure 6 shows (a) -49 dBm at q = 0.6 pC, (b) -50 determined by the capacitance of this minute space. However, the
dBm at q = 0.5 pC, (c) -48 dBm at q = 1.8 pC. Thus, dBm values magnitude of real charge cannot be measured. Therefore, apparent
were calibratedas pC values for various defects.Figure 7 plots the charge q, which moves due to the capacitance between high
magnitudeq (pC) of PD charges by the conventionalmethod and voltage electrode and grounding electrode, is measured. Since the
the maximum intensity (dBm) of 400 - 1500 MHz by the UHF minute space is small sufficiently compared with the space
method.In Fig. 7, a remarkable differencefor various defects was between electrodes, q is inversely proportional to the tank
not observed. Even for different kinds of defect, measured data diameter b (12). Apparent charge, q,is expressed by the following
convergeswell to a single curve. This curve can be expressed by equation.
equation(1).
q∞1/b・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・(2)
q=10(x+50)/20・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・(1)
As the tank diameter increase, the apparent charge decreases, even
That is, pC is easily converted from the measured dBm value from if the real charge remains constant.
equation (1).
Figure 8 shows pC - dBm characteristics of various tank sizes. It
is clear that even if the tank size changes, the relationship between
pC and dB converges well to a single curve. No dependency on
tank size is observed. The relationship between pC and dBm can
be expressed in equation (1).
Fig. 8. pC - dBm characteristics for different tank size Fig. 9. Electromagnetic distribution in tank
(a) Dia.=250mm the horizontal axis shows frequency and the vertical axis shows
The electric field is stronger near the conductor than on the tank.
sizes. Even for the same PD, when tank sizes differ the signal
clear that these three lines coincide well with each other. That is,
even if the size of real charge is the same, when tank size
becomes smaller at the same rate. This means that one universal
shown in figure 7.
5. Conclusions
Fig. 10. Intensity from same PD for different tank size
UHF PDM system has advantages of high sensitivity and high
References
1230 T.IEEJapan,Vol.122-B,
No.11,2002
Sensitivity Calibration of UHF PDM System
(9) T.Kato,and F.Endo :"Development of UHF InsulationDiagnosis Systemof Tatsuro Kato (Member) was born on 11 March, 1969. He
GIS", T.IEEJapan, 119-B,No.4, pp.458-463(1999-4) received B.S. and Dr. degrees in electrical
(10) N.Kock, B.Coric, and RPietsch : "UHF PD Detection in Gas-Insulated engineeringfrom NagoyaUniversity,Japan,in
Switchgear-Suitability and Sensitivityof the UHF Method in Comparison 1992 and 1996.He joined Hitachi,Ltd., Japan,
with the IEC 270 Method", IEEE Electrical InsulationMagazine, 12, No.6, in 1996. He has engaged in research of
pp.20-25(1996) diagnostic system of power apparatus. Now,
(11) CIGRE TF 15/33.03.05 : "Partial Discharge Detention System for GIS: he is an engineer in Power & Industrial
Sensitivity Verificationfor the UHF Method and the Acoustic Method", SystemsR & D Laboratory,Hitachi,Ltd.
ERECTRA,No.183, pp.75-87 (1999)
(12) G.C.Crichton, P.W.Karlsson, and A.Pedersen : "Partial Discharges in Fumihiro Endo (Member) was born in Tottori, Japan, on 25
Ellipsoidal and Spheroidal Void", IEEE. Trans. EI, 24, No.2, pp.335-342 November, 1945. He received B.S. and Dr.
(1989) degrees from Osaka University in 1968 and
(13) H.Muto, M.Doi, H.Fujii, and M.Kamei : "Resonance Characteristicsand 1989, respectively. He joined Hitachi Research
Identification of Modes Electromagnetic Waves Exited by Partial Laboratory, Hitachi, Ltd., Japan, in 1968, and
Dischargesin GIS", T.IEEJapan, 118-B,No.12, pp.1406-1414(1998-12) has been engaged in the research and
(14) M.C.Zhang, and H.Li : "TEM- and TE-Mode Waves Excited by Partial development of SF6 gas, air and vacuum
Dischargein GIS",Proc. of High VoltageEngineeringSymposium,No.467, insulation, GIS, GCB and diagnostic systems
pp.5.144.P5-5.147.P5(1999) of GIS. Now, he is a chief research engineer in Power & Industrial
(15) M.D.Judd, B.F.Hampton, and O.Farish "Modeling Partial Discharge Systems R & D Laboratory, Hitachi, Ltd. Dr. Endo is members of
Excitation of UHF Signals in Waveguide Structure Using Green's IEEE and the lEE of Japan.
Function",IEE Proc.-Sci. Meas. Technol.,143,No.1, pp.63-70(1996)
(16) M.D.Judd, O.Farish,and B.F.Hampton: "Tbe Excitation of UHF Signals by Shingo Hironaka (Member) was born in Yamaguchi, Japan, on
Partial Discharge in GIS", IEEE 7Fans. Dielectrics & Electrical Insulation, December 17, 1949. He received the B.S
3, No.2, pp213-228 (1996) degree from Kyusyu Institute of Technology in
1973. He joined Hitachi, Ltd., Kokubu Works,
Japan, from 1973 to 1998, and joined Hitachi
Engineering & Services., Ltd., Japan from
1998. He has been engaged in the
commissioning of Metal-Enclosed Switchgear
and diagnosis of substation equipments.