LV Relay Setting
LV Relay Setting
3
415 V, 42.1-SWGR-1503
RELAY SETTING TABLE
Incomer from (2 MVA) E6.2H 4000 4P For Directional Phase Over-Current and Earth Fault
1 415 42.1-TR-1505/A 42.1-SWGR-1505 A 2 (MVA) 3150.0 N/A N/A Feeder 4000/1 N/A N/A +A01 ACB_I RET620 N/A N/A N/A N/A N/A N/A N/A N/A N/A
Tranformer Ekip DIP LI Protection, Forward direction means towards Transformer
Incomer from (2 MVA) E6.2H 4000 4P For Directional Phase Over-Current and Earth Fault
2 415 42.1-TR-1505/B 42.1-SWGR-1505 B 2 (MVA) 3150.0 N/A N/A Feeder 4000/1 N/A N/A +B01 ACB_I RET620 N/A N/A N/A N/A N/A N/A N/A N/A N/A
Tranformer Ekip DIP LI Protection, Forward direction means towards Transformer
E6.2H 4000 4P
3 415 42.1-SWGR-1505/A 42.1-SWGR-1505/B A/B Bus Coupler 2 (MVA) 3150.0 N/A N/A Feeder 4000/1 N/A N/A +AB00 ACB_F REF 620 N/A N/A N/A N/A N/A N/A N/A N/A N/A
Ekip DIP LI
42.1-PU/E-2852/1A Fuel gas electric heater E4.2V 2000 3P Cable installed ampacity is less than feeder rated current.
4 415 42.1-SWGR-1505 A 407 566.2 1.00 1.00 Feeder 800.00 N/A N/A +A02 CB_F REF 620 N/A N/A N/A N/A N/A N/A N/A N/A N/A
(23FG-3) (main) Ekip DIP LI Need to be reverified.
42.1PU/E-2852/2A Fuel gas inlet electric T5L 630 3P
5 415 42.1-SWGR-1505 A 256 356.2 1.00 1.00 Feeder 630.00 N/A N/A +A03 CB_F UMC 100.3 N/A N/A 0.58 3s 1.8 0.25s 4 N/A N/A
(23FG-1) heater (main) PR231/P LS/I
42.1-PU/M-2936/1
6 415 42.1-SWGR-1505 A Jacking Oil Pump Motor 4.8 9.2 0.86 0.78 Motor N/A N/A AF52 +A07B M3.0.0 XT2L 160 MA 20 UMC 100.3 N/A N/A N/A N/A N/A N/A N/A 2 3
(88QS-1)
42.1-PU/E-2927/1A
7 415 42.1-SWGR-1505 A Lube Oil Tank Heater 10 13.9 1.00 1.00 Feeder N/A N/A AF52 +A07C 3CF3.1.1 XT2L 160 TMD 20 UMC 100.3 N/A CEM11-FBP.035 N/A N/A N/A N/A N/A N/A N/A
(23QT-1)
42.1-PU/M-2927/4 Hydraulic Oil Auxiliary
8 415 42.1-SWGR-1505 A 15 27.0 0.88 0.91 Motor N/A N/A AF65 +A07D M3.0.3 XT2L 160 MA 52 UMC 100.4 N/A CEM11-FBP.035 N/A N/A N/A N/A N/A 2 3
(88HQ-1) Pump Motor
E6.2H 4000 4P
3 415 42.1-SWGR-1505/A 42.1-SWGR-1505/B A/B Bus Coupler 2 (MVA) 3150.0 N/A N/A Feeder 4000/1 N/A N/A +AB00 ACB_F REF 620 N/A N/A 1=on 3000 1000 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
Ekip DIP LI
3=
Incomer from (2 MVA) E6.2H 4000 4P 1=Continuou
1 415 42.1-TR-1505/A 42.1-SWGR-1505 A 2 (MVA) 3150.0 N/A N/A Feeder 4000/1 N/A N/A +A01 ACB_I RET620 N/A N/A N/A N/A N/A N/A 2 0.05 0.002 10 1 Asynchronou 0.2 0.8 0.2 0.8 200 1.15 0 0 2000 100 60
Tranformer Ekip DIP LI s
s
3=
Incomer from (2 MVA) E6.2H 4000 4P 1=Continuou
2 415 42.1-TR-1505/B 42.1-SWGR-1505 B 2 (MVA) 3150.0 N/A N/A Feeder 4000/1 N/A N/A +B01 ACB_I RET620 N/A N/A N/A N/A N/A N/A 2 0.05 0.002 10 1 Asynchronou 0.2 0.8 0.2 0.8 200 1.15 0 0 2000 100 60
Tranformer Ekip DIP LI s
s
E6.2H 4000 4P
3 415 42.1-SWGR-1505/A 42.1-SWGR-1505/B A/B Bus Coupler 2 (MVA) 3150.0 N/A N/A Feeder 4000/1 N/A N/A +AB00 ACB_F REF 620 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
Ekip DIP LI
E6.2H 4000 4P
3 415 42.1-SWGR-1505/A 42.1-SWGR-1505/B A/B Bus Coupler 2 (MVA) 3150.0 N/A N/A Feeder 4000/1 N/A N/A +AB00 ACB_F REF 620 N/A N/A N/A N/A N/A N/A N/A N/A N/A D/A D/A D/A D/A D/A D/A D/A D/A 0.8 1 3000 15 1 1 1 60 20 0.2 1
Ekip DIP LI
Earth Fault through CBCT (51G) Directional Earth Fault IDMT Settings (67N)
Rated PF Taken From Load Efficiency Taken From
Rated C/T Contactor Cubicle Circ Circuit Circuit Breaker B07 ELM Earth Fault
S. No. Volt Tag From Tag to Bus Feeder description Current In List For Feeder & DS Load List For Feeder & Load Type CBCT Protection Relay B01 Measuring CT
Load Kw Detail Type No type Type CT Operat Minimum Voltage
Amps For Motor DS For Motor Start Time Type of Reset Measure Start Directi Operate Max. Min. Max. Min. Type of Min Min Min
Start e delay Operating operate Start Time Operating Char. Start Operation Reset Delay Allow Non Measurem Correction Pol Pol
value multipl reset Operation delay ment value onal delay Forward Forward Reverse Reverse reset Operation Operate Operate Operate
value x In time curve type time value x In multiplier curve type Angle Value Mode Time Dir ent Mode Angle Reversal Quantity
Mult ier curve time msec mode Mult Mode time msec Angle Angle Angle Angle curve time Current Voltage
msec msec x Un
Incomer from (2 MVA) E6.2H 4000 4P 2=Forw 9=IEC Norm. 1=Immedi 1=Phase 3=Zewo
1 415 42.1-TR-1505/A 42.1-SWGR-1505 A 2 (MVA) 3150.0 N/A N/A Feeder 4000/1 N/A N/A +A01 ACB_I RET620 N/A N/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A 0.1 1 0.05 50 80 80 80 80 80 0.01 On 20 50 0=False 2=DFT 0.005 0.01 0 0=False
Tranformer Ekip DIP LI ard inv. ate angle Seq. Volt.
Incomer from (2 MVA) E6.2H 4000 4P 2=Forw 9=IEC Norm. 1=Immedi 1=Phase 3=Zewo
2 415 42.1-TR-1505/B 42.1-SWGR-1505 B 2 (MVA) 3150.0 N/A N/A Feeder 4000/1 N/A N/A +B01 ACB_I RET620 N/A N/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A 0.1 1 0.05 50 80 80 80 80 80 0.01 On 20 50 0=False 2=DFT 0.005 0.01 0 0=False
Tranformer Ekip DIP LI ard inv. ate angle Seq. Volt.
E6.2H 4000 4P
3 415 42.1-SWGR-1505/A 42.1-SWGR-1505/B A/B Bus Coupler 2 (MVA) 3150.0 N/A N/A Feeder 4000/1 N/A N/A +AB00 ACB_F REF 620 N/A N/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A D/A
Ekip DIP LI
Directional Over-Current IDMT Settings (67) Earth Fault IDMT Settings (51N)
Rated PF Taken From Load Efficiency Taken From
Rated C/T Contactor Cubicle Circ Circuit Circuit Breaker B07 ELM Earth Fault
S. No. Volt Tag From Tag to Bus Feeder description Current In List For Feeder & DS Load List For Feeder & Load Type CBCT Protection Relay B01 Measuring CT Minimu
Load Kw Detail Type No type Type CT Type Voltage Reset Minimum
Amps For Motor DS For Motor Operate Max. Min. Max. Min. Pol Num of m Measur Min Min Start Start Time Operate Operating Type of Reset Measure
Start value Start value Time Operating Directional of Mem. Operati delay Allow operate
delay time Char. Angle Forward Forward Reverse Reverse Quant start operate ement Operate Operate value x value multipl delay time curve reset Operation delay ment
x In Mult multiplier curve type Mode reset Time on time Non Dir time
msec Angle Angle Angle Angle ity phases time mode Current Voltage In Mult ier msec type curve time msec mode
curve ms msec msec
msec
Incomer from (2 MVA) E6.2H 4000 4P 9=IEC 1=imm 5=Cros 1=1 out 9=IEC
1 415 42.1-TR-1505/A 42.1-SWGR-1505 A 2 (MVA) 3150.0 N/A N/A Feeder 4000/1 N/A N/A +A01 ACB_I RET620 N/A N/A 0.1 1.000 0.050 40.000 2=Forward 80 80 80 80 80 40 On 20 20 DFT 0=False 0.01 0.01 0.2 1 0.34 40 1 1 20 20 2=DFT
Tranformer Ekip DIP LI Norm. inv. ediate s Pol of 3 Norm. inv.
Incomer from (2 MVA) E6.2H 4000 4P 9=IEC 1=imm 5=Cros 1=1 out 9=IEC
2 415 42.1-TR-1505/B 42.1-SWGR-1505 B 2 (MVA) 3150.0 N/A N/A Feeder 4000/1 N/A N/A +B01 ACB_I RET620 N/A N/A 0.1 1.000 0.050 40.000 2=Forward 80 80 80 80 80 40 On 20 20 DFT 0=False 0.01 0.01 0.2 1 0.34 40 1 1 20 20 2=DFT
Tranformer Ekip DIP LI Norm. inv. ediate s Pol of 3 Norm. inv.
42.1-PU/E-2852/1A Fuel gas electric heater E4.2V 2000 3P 10=IEC Very 1=Immediat
4 415 42.1-SWGR-1505 A 407 566.2 1.00 1.00 Feeder 800.00 N/A N/A +A02 CB_F REF 620 N/A N/A 0.75 1 0.05 40 1=on 1=1 out of 4 20 20 2=DFT D/A D/A D/A D/A D/A D/A
(23FG-3) (main) Ekip DIP LI inv. e
42.1PU/E-2852/2A Fuel gas inlet electric T5L 630 3P
5 415 42.1-SWGR-1505 A 256 356.2 1.00 1.00 Feeder 630.00 N/A N/A +A03 CB_F UMC 100.3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
(23FG-1) heater (main) PR231/P LS/I
42.1-PU/M-2936/1
6 415 42.1-SWGR-1505 A Jacking Oil Pump Motor 4.8 9.2 0.86 0.78 Motor N/A N/A AF52 +A07B M3.0.0 XT2L 160 MA 20 UMC 100.3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
(88QS-1)
42.1-PU/E-2927/1A
7 415 42.1-SWGR-1505 A Lube Oil Tank Heater 10 13.9 1.00 1.00 Feeder N/A N/A AF52 +A07C 3CF3.1.1 XT2L 160 TMD 20 UMC 100.3 N/A CEM11-FBP.035 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
(23QT-1)
42.1-PU/M-2927/4 Hydraulic Oil Auxiliary
8 415 42.1-SWGR-1505 A 15 27.0 0.88 0.91 Motor N/A N/A AF65 +A07D M3.0.3 XT2L 160 MA 52 UMC 100.4 N/A CEM11-FBP.035 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
(88HQ-1) Pump Motor
R_BC_SW_1505/AB - N
100
OC1
100 BusDuct12
ABB
REF 620 ±
50 CT Ratio 4000:1 50
Overload Ground
Pickup = 20 (20 - 80 x49 Pickup)
Time Delay = 0.1 s
42.1-SWGR-1505/A CB143
5 5
Seconds
Seconds
3 3 R
CB977 R_BC_SW_1505/AB
1 1 R_OG_1505_88BA_1
.5 .5
∆ 0.241 s Cont44
.3 .3
∆ 0.244 s Cable605
.1 .1 2-3/C 120
R_OG_1505_88BA_1 - G - LG
77.28kA @ 0.473kV
Contactor fault interrupting
.01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
.01 rating provided is not greater
Amps X 10 42.1-SWGR-1505/B (Nom. kV=0.415, Plot Ref. kV=0.415) ETAP Star 16.2.0D
than the MCCB instantaneous
1_0.415_42.1-SWGR-1505_M magnetic rating.
Project: ADMA SWITCHGEAR UPGRADE Date: 14-02-2019 Hence its rating selection needs
Location: DAS ISLAND SN: DLR-MUMBAI
Contract:
Engineer:
181401
PP/SP
Rev:
Fault:
Base
Ground
to reviewed with vendor.
Seconds
UMC100.3
3 Transformer Through Fault Class 10 warm 3 R
38.83kA @ 0.415kV Pickup = 194 (180 - 310 Primary)
CB977 R_BC_SW_1505/AB
Cable605 - P
.5 .5
Cont44
.3 .3
CB977 ∆ 0.88 s ∆ 0.24 s
ABB SACE PR221 (T5)
Sensor = 400 Cable605
LT Pickup = 1 (400 Amps)
LT Band = 12s
.1 ST Pickup = 3.5 (1400 Amps) .1 2-3/C 120
ST Band = 0.1s (I^x)t = IN
42.1-TR-1505/A R_BC_SW_1505/AB - 3P
Inst. Pickup = 4.5 (1800 Amps)
Override = 5000 Amps Inrush 82.313kA @ 0.473kV
(Sym)
.05 .05
R_IC_SW_1505/A - 3P
85.883kA @ 0.473kV 1505A-88BA-1-E
(Sym)
.03 R_OG_1505_88BA_1 - 3P .03 110 kW
Cont44 77.28kA @ 0.473kV
Interrupting current 4.6 kA
Dropout time 0.047 s CB977 - 3P
77.28kA @ 0.473kV Contactor fault interrupting
.01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
.01 rating provided is not greater
Amps X 100 42.1-SWGR-1505/A (Nom. kV=0.415, Plot Ref. kV=0.415) ETAP Star 16.2.0D
than the MCCB instantaneous
1_0.415_42.1-SWGR-1505_M magnetic rating.
Project: ADMA SWITCHGEAR UPGRADE Date: 14-02-2019 Hence its rating selection needs
Location: DAS ISLAND SN: DLR-MUMBAI
Contract:
Engineer:
181401
PP/SP
Rev:
Fault:
Base
Phase
to reviewed with vendor.
500 500
Cable51-37
300
Ampacity 300
R_IC_SW_1505/A - N
OC2
42.1-TR-1505/A
ABB 2 MVA
RET 620
CT Ratio 4000:1
100 IEC Normal Inverse 100
Pickup = 0.135 (0.01 - 5 xCT Sec)
Time Dial = 0.34
3x = 2.14 s, 5x = 1.46 s, 8x = 1.12 s BusDuct12
50 50
R_BC_SW_1505/AB - N
30 OC1 30 ±
ABB R_IC_SW_1505/A
REF 620 R
4000/1
CT Ratio 4000:1
IEC Normal Inverse
Pickup = 0.135 (0.01 - 5 xCT Sec) 4000/1
±
10 Time Dial = 0.2 10 CB151
3x = 1.26 s, 5x = 0.856 s, 8x = 0.659 s
42.1-SWGR-1505/A
5 5
Seconds
Seconds
3 3 R
R_BC_SW_1505/AB
CB419
1 1
±
R
800/1
.5 .5
∆ 0.241 s ±
.3 .3 R_1505_OG_23FG-3
100/1
∆ 0.241 s
Cable51-37
.1 .1
R_1505_OG_23FG-3 - G R_1505_OG_23FG-3 - LG
R_1505_OG_23FG-3 - N 83.429kA @ 0.473kV 4-3/C 185
OC1 (Sym)
.05 OC1 .05
ABB R_IC_SW_1505/A - LG
ABB
REF 620 87.047kA @ 0.473kV
REF 620 (Sym)
.03 CT Ratio 100:1 .03
CT Ratio 800:1 R_BC_SW_1505/AB - LG
IEC Inverse
IEC Normal Inverse 83.429kA @ 0.473kV
Pickup = 0.2 (0.01 - 5 xCT Sec) (Sym)
Pickup = 0.15 (0.01 - 5 xCT Sec)
Time Dial = 0.06
Time Dial = 0.06 R_1505_OG_23FG-3 - G - LG
1505A-23FG-3
3x = 0.378 s, 5x = 0.257 s, 8x = 0.198 s 83.429kA @ 0.473kV
3x = 0.378 s, 5x = 0.257 s, 8x = 0.198 s (Sym)
.01 .01 407 kVA
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Amps X 10 42.1-SWGR-1505/B (Nom. kV=0.415, Plot Ref. kV=0.415) ETAP Star 16.2.0D
1_0.415_42.1-SWGR-1505_F
1505A-23FG-3
FLA
500 500
Cable51-37 R_IC_SW_1505/A - P
Ampacity OC1
300 300
ABB
42.1-TR-1505/A
42.1-TR-1505/A RET 620
FLA - KNAF 65 CT Ratio 4000:1 2 MVA
IEC Normal Inverse
42.1-SWGR-1505/A Pickup = 0.7 (0.05 - 5 xCT Sec)
100
Time Dial = 0.21 100
3x = 1.32 s, 5x = 0.899 s, 8x = 0.692 s
BusDuct12
50 50
30 30 ±
R R_IC_SW_1505/A
4000/1
4000/1
±
10 10 CB151
42.1-SWGR-1505/A
5 Cable51-37 - P 5
Seconds
Seconds
3 Transformer Through Fault 42.1-TR-1505/A 3 R
38.83kA @ 0.415kV
R_BC_SW_1505/AB
CB419
1 1
±
R
800/1
.5 R_BC_SW_1505/AB - P .5
OC1 ±
.3
ABB .3 R_1505_OG_23FG-3
REF 620 ∆ 0.24 s 100/1
CT Ratio 4000:1
IEC Normal Inverse 42.1-TR-1505/A
Pickup = 0.7 (0.05 - 5 xCT Sec) Inrush
Time Dial = 0.09 Cable51-37
∆ 0.24 s
.1 3x = 0.567 s, 5x = 0.385 s, 8x = 0.297 s .1
R_1505_OG_23FG-3 - P
OC1 4-3/C 185
.05
ABB R_1505_OG_23FG-3 - 3P .05
REF 620 82.313kA @ 0.473kV
CT Ratio 800:1 (Sym)
Amps X 100 42.1-SWGR-1505/A (Nom. kV=0.415, Plot Ref. kV=0.415) ETAP Star 16.2.0D
1_0.415_42.1-SWGR-1505_F