Transformer Pile Calculation 2

The document summarizes the design of pile reinforcement for a 230 kV transformer foundation. It considers compression plus bending, tension plus bending, and tension only cases. For the compression plus bending case, it determines the required rebar area to be 785.4 mm^2 with 4 nos. of 16 mm diameter bars. For the tension plus bending and tension only cases, it also determines 4 nos. of 16 mm diameter bars to be sufficient.

Uploaded by

MaienAhasan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
63 views2 pages

Transformer Pile Calculation 2

The document summarizes the design of pile reinforcement for a 230 kV transformer foundation. It considers compression plus bending, tension plus bending, and tension only cases. For the compression plus bending case, it determines the required rebar area to be 785.4 mm^2 with 4 nos. of 16 mm diameter bars. For the tension plus bending and tension only cases, it also determines 4 nos. of 16 mm diameter bars to be sufficient.

Uploaded by

MaienAhasan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Foundation Design For 230 KV Transformer

Project: Design, Supply, Installation, Testing and Commissioning of 230 KV Indoor GIS Substation with 132 kV AIS at Faridpur and
GIS Bay Ex-tension of existing 230/132 kV Barisal (North) AIS Substation on turnkey basis
Design of Pile Reinforcement
Compression plus bending case
Maximum compression, N = 380000 N
Corresponding bending moment, M = 60000000 N-mm

we will use design graph (Annexure-1) for pile design


here,

h = Pile diameter = 500 mm


2
Ac = 196350 mm
γc = 1.5
concrete strength = 20 Mpa
yield strength of rebar = 500 Mpa
From graph,
  N
ν v c  = 0.097
 1.5  f c Ac
  M
μ   c  = 0.031
 1.5  f c Ac h
  c  Atot f y
ω    = 0.1
 1.5  Ac f c 2
So, As = 1.5ωAcfc/γcfy = 785.4 mm
2
Minimum rebar requirement in pile 0.4% = 785.4 mm
Rebar area need to be provided = 785.4 mm2
main rebar for pile consider = 16 mm
Rebar needed = 4 nos
Provide 6nos. 16 mm dia bar as longitudinal reinforcement

Tension plus bending case


Maximum uplift, N = 0.00 N
Corresponding bending moment, M = 0.00 N-mm

we will use design graph (Annexure-1) for pile design


here,

h = Pile diameter = 500 mm


2
Ac = 196350 mm
γc = 1.5
concrete strength = 20 Mpa
yield strength of rebar = 500 Mpa
From graph,
  N
ν v c  = 0.000
 1.5  f c Ac
μ   M
  c  = 0
 1.5  f c Ac h
ω   c  Atot f y = 0.015
   2
So, As = 1.5ωAcfc/γcfy  1.5  Ac f c = 117.81 mm
2
Minimum rebar requirement in pile 0.4% = 785.4 mm
Rebar area need to be provided = 785
main rebar for pile consider = 16 mm
Rebar needed = 4 nos
Provide 4 nos of 16 mm dia bar as longitudinal reinforcement.
Tension only case:
Maximum uplift, N = 0N
Corresponding bending moment, M = 0 N-mm
ν = 0
μ = 0
ω = 0.01
2
So, As = 1.5ωAcfc/γcfy = 78.54 mm
2
Minimum rebar requirement in pile 0.4% = 785.4 mm
Rebar area need to be provided = 785.4
main rebar for pile consider = 16 mm
Rebar needed = 4 nos
Provide 4 nos of 16 mm dia bar as longitudinal reinforcement.