Unigen 2.0 Synchro Technical Documentation en PDF
Unigen 2.0 Synchro Technical Documentation en PDF
0 synchro
Slave Synchro Unit
2
A51 V0 9 0020 A EN User manual – technical documentation
Preamble
SETTINGS
The tables whose header have an orange-coloured background describe settings.
Settings (and readings) that show only in CRE Config, but not on the LCD, feature a purple border in
the HMI chapter as follows:
assignment assignment
Digital xxxx
Digital
input output
SYMBOLOGY
CRE Technology believes that all information provided herein is correct and reliable and reserves the
right to update at any time. CRE Technology does not assume any responsibility for its use.
You can download the most up-to-date version of this documentation and different other
documentations relating to UNIGEN 2.0 on our web site http://www.cretechnology.com.
3
User manual – technical documentation A51 V0 9 0020 A EN
Content
1 Presentation ......................................................................................................................... 7
1.1 Generator automatic control ...................................................................................................... 7
1.2 Breakers control .......................................................................................................................... 7
1.3 Human machine interface ........................................................................................................... 8
1.4 Setting and supervision utility ..................................................................................................... 9
2 Installation ......................................................................................................................... 10
2.1 On-desk-ethernet setup ............................................................................................................ 10
2.1.1 Setting the PC connection ............................................................................................. 10
2.1.2 Changing the UNIGEN 2.0 IP address ............................................................................ 11
2.1.3 Hostname ...................................................................................................................... 11
2.1.4 Copyright ....................................................................................................................... 11
2.2 In-panel installation................................................................................................................... 12
2.2.1 Unpacking ...................................................................................................................... 12
2.2.2 Installation ..................................................................................................................... 12
2.2.3 Wiring the unit............................................................................................................... 13
2.2.4 Connection diagrams..................................................................................................... 18
3 Applications ........................................................................................................................ 20
3.1 Synchronization ......................................................................................................................... 21
3.1.1 Configuration ................................................................................................................. 21
3.1.2 Tuning ............................................................................................................................ 22
3.1.3 Manual synchronization ................................................................................................ 22
4 Operation ........................................................................................................................... 23
4.1 Protections ................................................................................................................................ 23
4.1.1 General .......................................................................................................................... 23
4.1.2 Audio or visual annunciator .......................................................................................... 23
4.2 Potential Alarms/Faults catalog ................................................................................................ 24
4.2.1 Generator electrical fault .............................................................................................. 24
4.2.2 Engine and battery ........................................................................................................ 24
4.2.3 Analog inputs ................................................................................................................. 24
4.2.4 Communication ............................................................................................................. 24
4.2.5 Reset .............................................................................................................................. 24
4.3 Breaker management ................................................................................................................ 25
5 Commissioning ................................................................................................................... 26
5.1 Introduction............................................................................................................................... 26
5.2 Analog speed governor output ................................................................................................. 27
5.3 Analog AVR (Auto Voltage Regulator) control .......................................................................... 29
5.4 Speed/voltage controlled by contacts/pulses ........................................................................... 31
5.4.1 Setup.............................................................................................................................. 31
5.4.2 Speed calibration procedure ......................................................................................... 32
4
A51 V0 9 0020 A EN User manual – technical documentation
5
User manual – technical documentation A51 V0 9 0020 A EN
6
A51 V0 9 0020 A EN User manual – technical documentation
1 PRESENTATION
UNIGEN 2.0 SYNCHRO is a panel mounting electronic unit meant for the control of a single, two or three-
phase low-voltage generator. It is designed to work as a slave of a PLC unit. UNIGEN 2.0 SYNCHRO can
be used to synchronize one generator with an other power source.
The engine-generator may have an Electronic Control Unit with CAN J1939 interface. J1939 and
CANopen interfaces can coexist – on a second CAN media – provided they use the same bit-rate.
The engine speed is derived from the AC frequency.
The generated voltages and currents are measured in true RMS and used to calculate the load demand
across the aggregate. The synchronization requests drive the primary control which, according to its
configuration:
Produces an analog signal Speed out+, sends pulses “+/- f” to digital outputs or writes to J1939
bus.
Produces an analog signal AVR out+ or sends pulses “+/- U” to digital outputs.
7
User manual – technical documentation A51 V0 9 0020 A EN
Press to access:
.the Fault page if new fault occurred (Fault
blinks)
.the Alarm page if new alarm occurred (Al.
blinks)
.pages with 2 statuses (Power and Engine) and
10 readings of special interest.
Press again to return.
Keyboard:
Keys Navigation mode Edition mode
Cyclic navigation through menu & settings list Used to change the value of a setting. Hold down to change
faster
Esc Return to parent menu (3 times to home) or Setting change rejection and return to the Navigation mode
preceding menu
Enter Page opening / switch to Edition mode Validation of the new setting and return to Navigation mode
8
A51 V0 9 0020 A EN User manual – technical documentation
This allows you to preset all the UNIGEN 2.0 units when they are on desk: a text file that reflects the
first UNIGEN 2.0 unit’s configuration can serve as a template to deploy the setup to the other
UNIGEN 2.0 units in the cluster. The CRE Config multi-tabbed interface makes it easy.
Once all UNIGEN 2.0 units are mounted, CRE Config can be used to set them up and monitor the
generators. The CRE Config features a Scada section that can be used in particular as an event console to
UNIGEN 2.0:
Information
Information
2
1
9
User manual – technical documentation A51 V0 9 0020 A EN
2 INSTALLATION
Connect UNIGEN 2.0 to a PC with a 100 Ethernet Direct connection to PC: use a crossover cord.
cord Connection through a switch: use a direct cord; a
crossover cord such as 3-m long A53W1 is OK if the
switch manages it.
Power up UNIGEN 2.0 using a stabilized power Power supply range: 8…35VDC
supply
Open Windows control panel
Click:
10
A51 V0 9 0020 A EN User manual – technical documentation
Enter a PC address that differs from the one of the Last number: 0 … 255; avoid 0 and 255 as they are
UNIGEN 2.0 only by the last number, & click OK often taken for other purposes
To change UNIGEN 2.0 IP address, in CRE Config (or on LCD), navigate to “System/Network
configuration (resp. About)”.
UNIGEN 2.0 supports the DHCP function: in this case, UNIGEN 2.0 must be connected on a network
with a DHCP server. During the power-on sequence, UNIGEN 2.0 is assigned an IP address by the
DHCP server. If DHCP process fails, the fixed IP address is used (factory setting: 192.168.11.1).
Note: Contact your network administrator to configure your router and module(s) to your needs.
2.1.3 Hostname
You can assign an alias to UNIGEN 2.0, in addition to the IP address; enter it in CRE Config to get
connected.
To change this alias, in CRE Config navigate to System/Network configuration.
Maximum length: 16 characters. With Windows, the last character defines the type of service (0 is
the usual value).
Allowed characters: reduced ANSI set; "-" and "." are allowed except at the start and end.
2.1.4 Copyright
UNIGEN 2.0 Ethernet communication uses the open source lwIP TCP-IP stack. Read
copyright/disclaimer below. More details on lwIP Web site:
http://savannah.nongnu.org/projects/lwip/
Copyright © 2001-2004 Swedish Institute of Computer Science. All rights reserved.
Redistribution and use in source and binary forms, with or without modification, are permitted provided that
the following conditions are met:
1. Redistributions of source code must retain the above copyright notice, this list of conditions and the following
disclaimer.
2. Redistributions in binary form must reproduce the above copyright notice, this list of conditions and the
following disclaimer in the documentation and/or other materials provided with the distribution.
3. The name of the author may not be used to endorse or promote products derived from this software without
specific prior written permission.
THIS SOFTWARE IS PROVIDED BY THE AUTHOR ``AS IS'' AND ANY EXPRESS OR IMPLIED WARRANTIES, INCLUDING,
BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE ARE DISCLAIMED. IN NO EVENT SHALL THE AUTHOR BE LIABLE FOR ANY DIRECT, INDIRECT,
INCIDENTAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO,
PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS
INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT
LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE USE OF THIS
SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.
11
User manual – technical documentation A51 V0 9 0020 A EN
The unit is designed for panel mounting, which provides user with access only to the front panel.
WARNING
THE UNIT IS NOT GROUNDED
Take all measures against Electronic Static Discharges.
Do not try to open the unit.
Failure to follow these instructions may damage the unit
Environmental requirements:
Operating temperature: -30°C (-22°F) … 70°C (158°F); LCD display slows down a bit under -5°C
(23°F). Avoid direct exposure to the sun
Storage temperature: -40°C (-40°F) … 80°C (176°F)
Altitude: up to 2,000 m (6,561 ft); on higher altitudes, recommended max. AC voltage : 100VAC
2.2.1 Unpacking
2.2.2 Installation
Preparation
1. Cut out the panel to 220x160 mm minimum (8.7 in x 6.3 in)
2. Make sure the cut-out is smooth and clean
Mounting
12
A51 V0 9 0020 A EN User manual – technical documentation
Tool: insulated screwdriver Ø2.5 mm (0.1 in), tightening torque: 0.8 Nm (7 lb-in) max.
Accessories: 4, 5, 6, 8, 15 & 18-terminal cable connectors, protective gloves, carpet if the floor is wet.
WARNING
THE UNIT IS NOT PROTECTED
Use external fuses:
Bus bar and Generator phases: 100mA/600VAC
Battery positive: 5A/40VDC
Install the fuses as near as possible the unit, in a place easily accessible to the user.
The disconnection device must NOT be fitted in a flexible cord.
Failure to follow these instructions may damage the unit
!l DANGER
l
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
The unit must only be installed and serviced by qualified electrical personnel
Apply appropriate personal protective equipment (PPE) & follow safe electrical work practices
Turn off power before installing or removing fuses, and before installing the unit
Use a properly rated voltage sensing device to confirm the power is off
Do not use renewable link fuses in fused switch
Failure to follow these instructions will result in death or serious injury
General procedure
1. Make sure the cable connectors are NOT plugged
2. Take on protective gloves
3. Connect the wires on each cable connector in accordance with the National Wiring Regulations
4. Plug each cable connector onto the related connector
1. 5. Plug a direct Ethernet cord (RJ45, male-male, 100 m max., 100; a crossover cable
such as 3-m long A53W1 is OK if the switch manages it or if the link to PC is direct) and lock
the rear door.
Recommandations
Wires section: 2.5 mm² (AWG13).
To avoid ElectroMagnetic Interferences, shield cables appropriately; for CAN bus, see the Appendix
CAN bus Good practices.
Segregation: keep power cables separate from the CAN bus cables. The latter can be installed in the
same duct as the low level DC I/O wires (under 10V).
If power & communication cables have to cross each other, do it at right angles to avoid crosstalk:
13
User manual – technical documentation A51 V0 9 0020 A EN
Overview
14
A51 V0 9 0020 A EN User manual – technical documentation
Upper blocks
!l DANGER
EXPOSED TERMINALS l
Do not touch terminals L1, L2, L3 nor use non-insulated tools near them. These terminals are
unprotected and will expose the user to dangerous voltages
Failure to follow this instruction will result in death, serious injury or equipment damage
15
User manual – technical documentation A51 V0 9 0020 A EN
Lower blocks
WARNING
RISK OF EQUIPMENT DAMAGE
As a protection against polarity reversal, install a 6A fuse between Battery positive lug & terminal 8-35VDC +.
Connect battery negative to GENSYS terminal 8-35VDC– with 2.5 mm² (AWG13) cable.
Failure to follow this instruction can damage the controller
16
A51 V0 9 0020 A EN User manual – technical documentation
WARNING
RISK OF EQUIPMENT DAMAGE
Switch off the unit before plugging or unplugging the CAN bus connector or disconnecting wires
Failure to follow this instruction can damage the CAN transmitter/receiver
Note: Crank dropout: the unit survives for 70 ms at 24V, and 20ms at 12V.
17
User manual – technical documentation A51 V0 9 0020 A EN
18
A51 V0 9 0020 A EN User manual – technical documentation
19
User manual – technical documentation A51 V0 9 0020 A EN
3 APPLICATIONS
Starting from the default settings, just enter the installation specification:
Setting Label Value
2000 Count of gen. 1 ≤ N ≤ 32
2001 GE Number 1 to 32 (differs for each UNIGEN 2.0 on the CAN bus)
After the engines have started, the UNIGEN 2.0 with an active « UNIGEN activation » signal :
- Set the digital output « Synch check relay » if the bus bar is unpowered (with an election in
island operation)
- Synchronize the generator if the bus bar is powered. The digital output « Synch check relay »
is set once the breaker can be closed.
Notes:
After the closure of the breaker, speed output and voltage output are equal to 0 percent..
In island operation, each generator is controlled by a UNIGEN 2.0 SYNCHRO. Communication by CAN
Bus allows to close the breaker on a dead bus bar by avoiding simultaneous closures.
If the generators are not yet started, when they lose the CAN bus, a downgraded mode is enforced;
the generator couplings are phased in: the generator #n cannot close its breaker before
[2306]/10 + 7 x n (seconds)
20
A51 V0 9 0020 A EN User manual – technical documentation
3.1 SYNCHRONIZATION
3.1.1 Configuration
Various settings and readings are offered to control and monitor the synchronization:
UNIGEN 2.0 launches the synchronization only if the bus bar/mains provides at least 80% of nominal
voltage. The bus bar/mains frequency and voltage are the set points of loop controls. When the
generator and bus bar match, UNIGEN 2.0 orders the breaker closing.
Time chart:
21
User manual – technical documentation A51 V0 9 0020 A EN
3.1.2 Tuning
Prerequisite: Speed & AVR outputs are scaled to match the generator. See 5.2 and 5.3.
Associated parameters may be set in menu “Configuration/ Synchronization”.
Tuning process :
1. Bus bar is live (Fed by Mains/Other generator).
2. Start this generator and go to “Display/Synchronization”
3. The generator synchronizes within 5s; otherwise, isolate the root cause (Voltage, frequency or
phase) and adjust:
In a first time, the proportional in order to be closer of the set point
In a second time (if need), the integral in order to faster reach the set point
These digital inputs can be used only in « waiting » state (breaker open and digital input “UNIGEN
Activation” deactivates.
22
A51 V0 9 0020 A EN User manual – technical documentation
4 OPERATION
4.1 PROTECTIONS
4.1.1 General
Protections are triggered by internal and external events (alarms, faults, digital inputs, CAN bus loss
…). To protect the process, the engine or the alternator, you must associate one of the predefined
actions to each such event. These actions or effects are of various kinds:
they can just raise an alarm; notice shows on the front panel (ANSI30); a summary can be reported
they can secure the equipment: the breaker trips safe … and can activate a free protective digital
output
The action is an attribute of the protection: CT settings, or of inter-module CAN bus loss. The Droop
effect is reserved to CAN bus fault.
The actions are configured in CRE Config. Numerical values show only in text file. See 8.2.
Protection
RS
S
2478
OUT Horn
t
R
Stop horn
23
User manual – technical documentation A51 V0 9 0020 A EN
4.2.4 Communication
Potential Alarms/Faults Description On level 1/Min On level 2/Max
Communication problem on the inter-unit CAN (only –
CAN1 bus fault 3052
power plant applications)
CAN2 bus fault A J1939/CANopen bus error is detected on CAN2. 3053 –
An alarm is activated to indicate a CANopen
CANopen
communication fault.
4.2.5 Reset
Clearing of faults/alarms:
- Locally: Shift +
24
A51 V0 9 0020 A EN User manual – technical documentation
As long as the breaker is closed, the digital output « Synch check relay » is activated. It will
deactivate if a protection configured as « Generator electrical fault » occurs.
The digital output « Generator electrical faults summary » can be also used to open the breaker
when a protection configured as « Generator electrical fault » occurs.
25
User manual – technical documentation A51 V0 9 0020 A EN
5 COMMISSIONING
5.1 INTRODUCTION
Each function produces a speed or voltage deviation based on its own GPI coefficients.
UNIGEN 2.0 feeds the sum of deviations to the output stage either as analog signals (Speed out and
AVR out+) or as pulses train or J1939 frames (speed):
CAUTION
Follow strictly, throughout the aggregate, the scaling procedures (amplitude -offset) to have the best
synchronization, load sharing and droop
26
A51 V0 9 0020 A EN User manual – technical documentation
The Speed output signal provides the set point for ESG, used in speed control and frequency
synchronization. It is the sum of the components listed in the section 5.1. The voltage range -10V
…+10V must be fitted in amplitude and offset to allow UNIGEN 2.0 to vary the ESG set point on a
correct range; the aim is that UNIGEN 2.0 can control the frequency in the +/-3Hz band around the
nominal frequency:
F
3Hz
+V Sum
Nom
Amplitude offset
3Hz
-V
Speed common
1. Connect the speed common wire only
2. In “Configuration/Engine”, preset the amplitude and offset as described in the table further
(if not listed, contact CRE Technology)
ESG amplitude …V
ESG offset …V
F 50Hz Lecture
Engine Speed 1500 Lecture
Speed Sum 0000
27
User manual – technical documentation A51 V0 9 0020 A EN
8. Select the Speed Sum and adjust it to –100% with the Shift + keys in order to check the
variation range till 47Hz (or 57Hz)
9. Adjust the speed sum to 0%.
The next table gives both settings for various ESGs. For other models, preset amplitude and
offset according the manufacturer documentation and/or contact our Customer service.
Manufacturer Model ESG ampl. ESG ESG input ESG ref Note
offset
with analog input 0.5V 0V ILS input 4V
BARBER 0.5V 0V ILS signal ILS+2.5V
COLMAN Digital The tuning depends
DPG 2201 ILS signal
supply(+5V) on the connections
ILS signal BAT-
ECM for QSK23 / 11 (Barber
QSK40 / QSK45 / 2.5V 0V Colman Freq. 06 (5V)
QSX15 / QSK 60 bias input)
EFC 1.5V 0V 8 9 See schematic
ECM (QST30) 18 15 (7,75V)
+/- 1.5 Hz not to reach
EMR 2V 2.5V 24 25
EMR overspeed
ESD5330 –5V M G
All other ESD –5V N G
GHANA
PWC 2000 J G
CONTROL
E6 B3
KG6 / System E6 2.5V 2.5V E3 A3
PANDAROS DC6 2V 2.5V B3 A3
2V 2.5V L C Two different wirings
JDEC
G2 5V(ref speed) 999 for the same governor
2 and 12 connected
ECM 1300 2V 2.5V 30 5V
for external setting
EDC IV
1.5V 3V Pot. signal
EDC III
- 2301A/D ILS+speed 0V 3V 10 11 Shunt 14-16
- (Without U&I) 25 26 Shunt 26 (com) on 0V
2301D
2301A Speed only 4.5V 2.5V 15 16 16 connected to 0V
EPG System
Remove the shunt
P/N 8290-189 2.5V 0V 11 (0.6V) nc
P/N 8290-184 between 11 and 12
Because of the very high sensitivity of Cummins EFC module input, use the schematic below to
connect UNIGEN 2.0 to the EFC. The resistors must be as close as possible to the speed governor
terminal. This way, UNIGEN 2.0 analog speed output can be set higher (2205) according to the
resistors used.
28
A51 V0 9 0020 A EN User manual – technical documentation
The AVR out signal provides the set point for AVR, used in voltage control and voltage
synchronization (U=U). The components of AVR output are listed in the section 5.1. The voltage
range -10V …+10V must be fitted in amplitude and offset to allow UNIGEN 2.0 to vary the AVR set
point on a correct range; the aim is that UNIGEN 2.0 can control the voltage in the +/-30V band
around the nominal voltage:
U
+V Sum 30V
Nom
Amplitude
offset
30V
-V
AVR common
AVR amplitude …V
AVR offset …V
V1 230V Lecture
U31 400V Lecture
Voltage Sum 0000
29
User manual – technical documentation A51 V0 9 0020 A EN
8. Adjust Voltage Sum to -100% with the Shift + keys in order to check the variation range till
370V
9. Adjust voltage Sum to 0%.
Table below gives both settings for various AVRs. For other models, contact our Customer service.
Manufacturer Model AVR ampl. AVR offset AVR out AVR common Comment
Mid point of a
R16 0V 8 resistive bridge
betw. 7 & 9/10
Cosimat N 4.5V 4.5V Mn n
MA329 A2(+) A1(-)
AEC63-7 Remove shunt between
6 7
AVC63-4(A) terminal 6 & 7 of the AVR
AVC63-12 1.0V 0V 2 3
DECS32-15-xxx
DECS63-15-xxx
Use VAR control included in the DECS
DECS125-15-xxx
DECS300
DVR KVAR/PF 7 45
VR6 1.0V 0V 3 2
CDVR 4.5V 0V P12.3 P12.6
K65-12B
1.0V 0V 2 3
K125-10B
30
A51 V0 9 0020 A EN User manual – technical documentation
UNIGEN 2.0
K1 K2 K3 K4
De crease Volt
De crease Hz
Increase Volt
Increase Hz
K1 K2 K3 K4
A digital potentiometer, that converts the pulses into analog values, has its own settings: U0 (fsd) & Time.
A motorized potentiometer: a stepper motor with a brake moves the tap
5.4.1 Setup
In “Configuration/Outputs/Digital outputs”, assign to outputs a function Increase/Decrease
speed/voltage by pulse.
When digital outputs are used to control speed/voltage by pulse, dedicated parameters are shown in
the speed/voltage regulation control menu. Those parameters are listed in the table below.
A pulse is generated when the absolute value of the regulation output is bigger than the dead band
setting. The higher the regulation output is, the closer pulses will be from each other. Period
between two pulses can be calculated as follows:
Note that calculated value of the regulation output depends on the settings applied to the dedicated
PIDs.
31
User manual – technical documentation A51 V0 9 0020 A EN
Preliminary step:
1. Adjust the resistance at mid value or set the potentiometer tap in the mid position or the
tapper in the mid position (unless UNIGEN 2.0 is directly connected to the governor)
2. Check the sum of all deviations [4405]
The components of total deviation are split in two, as they are compensated in different ways. Finally,
the compensations will be added.
Set 3650 to 1.00% which is 1 percent of deviation (i.e. 0.03Hz of dead band)
Set 3652 to 0.2s which corresponds to a 200ms pulse width
Remove the I component of the synchronization control: set 2906 and 2902 to 0
Note: To get the best results during synchronization, it's often useful to set the P values 2901 and
2905 high when tuning the synchronization (typical values from 80 to 200).
If the generator oscillates around the set point during an active phase or if it’s hard to reach the set
point, it means that the dead band 3650 is not properly adjusted:
Decrease dead band 3650 to improve the accuracy around the set point
Increase dead band 3650 if the generator oscillates in frequency or in load
If there is a digital potentiometer between UNIGEN 2.0 and the speed governor, set U0 (fsd) and
Time; if you don’t get the desired compensation, check the following points:
Is the potentiometer still running when UNIGEN 2.0 sends an output signal?
Check that the speed/voltage range controlled by the potentiometer is wide enough
Note: If pulses always generate an over-compensation, then it may be because the potentiometer is
still running even after the UNIGEN 2.0 pulse is finished. In this case a shunt resistor on the
potentiometer input may correct the problem by ensuring a proper low level at the input when UNIGEN
2.0 issues no pulse
5.5 TESTS
Make sure that you have the latest power plant schematics and that all the cables (CAN bus, shielded
cables, speed governor / UNIGEN 2.0 interface...) are ready. The HMI can be either LCD or CRE
Config/Scada.
5.5.1 Individual check
Check up
1. Disconnect the breaker control cables for safety purpose
2. Check the speed governor and AVR control settings and connection
32
A51 V0 9 0020 A EN User manual – technical documentation
33
User manual – technical documentation A51 V0 9 0020 A EN
6 HUMAN-MACHINE INTERFACE
UNIGEN 2.0 features password-protected access levels to define which menu and items can be
accessed:
2 1234 Used to change advanced settings All items (CRE Config only);
INDEX
Display
Configuration
System
34
A51 V0 9 0020 A EN User manual – technical documentation
Bits numbers:
Inhib.bit 8 7 6 5 4 3 2 1
Press ESC ENTER and type in the level 1 password as described above to access the top level menu:
INDEX
Display
Configuration
System
A black pointer spots the currently selected item/setting; a white one features other items/settings.
Three main menus are available on the LCD screen and the web client monitor:
Display gives information on generator & busbar, & displays real-time information & status
Configuration is used to hone the settings done in CRE Config/Configuration
System is used to change on the fly the settings done in CRE Config/System (Date/Hour,
Screen features, ...)
To cycle through the menus and menu items, press or .
Next
35
User manual – technical documentation A51 V0 9 0020 A EN
6.1.4 Edition
To change a setting:
1. Navigate to the setting
2. Press ENTER to switch to Edition mode; the current value blinks
3. Press or to get the new value
4. Press ENTER to validate the new value, ESC to reject it. UNIGEN 2.0 returns to Navigation
mode.
It is also possible via the bus Modbus TCP. See 7.1.
6.2 SUPERVISION
If you keep the PC connected, you can monitor the generator from CRE Config/Scada through
UNIGEN 2.0.
36
A51 V0 9 0020 A EN User manual – technical documentation
To do so:
1. Connect UNIGEN 2.0 to your PC using an Ethernet direct cable
2. Start a Web browser such as Firefox or Internet Explorer
3. Type in the IP address (factory setting: http://192.168.11.1), or UNIGEN 2.0 hostname
4. When the UNIGEN 2.0 password page appears, enter your password
In the browser, the only soft key is ESC, used to return to the parent menu.
37
User manual – technical documentation A51 V0 9 0020 A EN
B Bus/Mains
These pages display in real time all bus/mains electrical measurements.
B- 1 Global view
Phase-to-neutral voltage of phase 1
Phase-to-phase voltage of phase pair 3-1
B- 2 Frequency
B- 3 Phase to neutral (V)
V1, V2, V3
B- 4 Phase to phase (U)
U31, U23, U12
Note: These pages fit the voltage system selected (see further)
38
A51 V0 9 0020 A EN User manual – technical documentation
C Synchronization
This page displays:
Synchroscope (phase difference)
Differential frequency and voltage (bar graphs)
D Engine meters
D- 1
Engine speed (RPM)
Battery voltage
D- 2
Running hours
E Inputs/outputs state
E- 1 Digital inputs 1-5
The name of each input is displayed with its status: active =full dot, inactive = hollow dot.
1 (Raw) is the status of the physical input,
2 (Processed) is the status after conditioning (delay, …).
E- 2 Digital inputs 6-9
Idem.
E- 3 Digital outputs
The name of each output is displayed with its state: active =full dot, inactive = hollow dot.
E- 4 Relay outputs
This menu shows the state of the two relay outputs (Generator breaker).
The name of each output is displayed with its state: active =full dot, inactive = hollow dot.
E- 5 Analog inputs 1-3
The name of each input is displayed with its
Value if really analog
Status if digital: active =full dot, inactive = hollow dot.
F About
These pages show only if you have entered as observer (no password). Otherwise, find it in
“System/About“.
1. S/N: serial number, Type (A51V0), Version, Boot version
Host name, IP, NM (network mask), GW (gateway). See 2.1.
39
User manual – technical documentation A51 V0 9 0020 A EN
4450 Loss of speed sensor Time since the speed sensor signal is not available 2203
4465 Speed & voltage stabilization Time generator is waiting to let engine speed & volt stabilize 3469
before taking the load (not applicable to static paralleling)
4466 Voltage stabilization Voltage stabilization counter for static paralleling 2056
40
A51 V0 9 0020 A EN User manual – technical documentation
To access this menu, a password is required; the LCD menu gives access to the following information:
Power plant
Generator
Bus
Engine
Protections (Only CRE Config software)
Timers (Only CRE Config software)
Synchronization
Modification by variable n°
The settings with a purple left border are for CRE Config only.
A Power plant
B Generator
B- 1 Generator
Setting Label Description
2102 Nominal voltage Generator nominal voltage
2253 Nominal voltage (2) Second nominal voltage of the generator, activated with logical input
B- 2 Generator
Setting Label Description
2100 PT ratio Ratio of the voltage transformers (Ex: 20 kV to 100 V: type in 200). Default value: 1
B- 3 Generator
AVR CONTROL
Setting Label Description
2251 AVR amplitude
Use in case of analog voltage control. See 5.3.
2252 AVR offset
3651 Dead band
Use in case of voltage control by pulse. See 5.4.
3653 Pulse width
41
User manual – technical documentation A51 V0 9 0020 A EN
C Bus/Mains
C- 1 Bus/Mains
Setting Label Comment
2150 PT ratio Ratio of the potential transformers
D Engine
42
A51 V0 9 0020 A EN User manual – technical documentation
E Protections
All protections work with :
A threshold: triggering level of protection
A timer: time before triggering the protection
An action to do when the fault is present
Generator
Protection 1 (level 1) 2 (level 2)
Threshold Delay Action Threshold Delay Action
Over frequency 2400 2401 2402 2436 2437 2438
Under frequency 2403 2404 2405 2439 2440 2441
Over voltage 2406 2407 2408 2442 2443 2444
Under voltage 2409 2410 2411 2445 2446 2447
G Synchronization
This page allows setting the synchronization settings used to allow the synch check relay to operate.
Setting Label Description
2810 Voltage match Maximum difference (in %) between generator and bus bar voltage for
coupling
2811 Freq. match Maximum frequency difference between generator and bus bar for
coupling
2802 Phase match Maximum phase angle difference between generator and bus bar for
coupling
2803 Fail to synch. Allocated time to synchronize
(1)
2809 C2S dwell time Synchronization dwell time before authorizing to close the breaker (default
value 200ms)
2804 Control on fail Selects the action in case of synchronization fails
synch
(1) This setting can be modified using TXT file or modification by variable number menu
Used to tune the frequency and phase synchronization PID to decrease the synchronization time. The
built-in synchroscope shows and lets you monitor in real time any change made on these settings.
Setting Label Description
Voltage
2951 P Proportional gain of the voltage synchro
2952 I Integral of the voltage synchro
Frequency
2901 P Proportional gain of the frequency synchro
43
User manual – technical documentation A51 V0 9 0020 A EN
In CRE Config/Configuration/Logger:
Tick the box Log on/off to enable the data logger
Enter the codes in the text area (using the spin is NOT recommended as you have to scroll a lot).
The records can be downloaded from CRE Config or the web site.
44
A51 V0 9 0020 A EN User manual – technical documentation
A Date / Time
“Date / Time” allows you to modify the date and the time:
Label Description
Date Year/Month/Day/Day of week
Time (hh:mm) Time adjustment (H M)
C Ethernet
This page allows to configure the Ethernet connexion with the following parameters:
DHCP
IP address
Network Mask
GateWay IP address
HTTP port
Modbus port
D About
This page displays some information on module and on Ethernet connection.
Serial number (S/N)
Module reference (type)
Software version
Boot software version
Hostname
IP address
Network Mask
GateWay IP address
45
User manual – technical documentation A51 V0 9 0020 A EN
SCREEN SAVER
The page displayed when the user does not interact with UNIGEN 2.0 (keys not used) is called
“SCREEN SAVER”. Information displayed on this page depends on the UNIGEN 2.0 status, as
described in the following table. Some settings can also be used to customize this behaviour.
PASSWORD
This page allows you to change passwords, from level 0 to the currently connected level. Passwords
are limited to 8 characters maximum. Refer to chapter 6.1.1.
LANGUAGES
Setting Label Possible value Description
English
Francais Language of the menus displayed on the LCD and on
3556 Language
Espanol embedded web site
Italian
46
A51 V0 9 0020 A EN User manual – technical documentation
Notes: On CRE Config, these modifications are taken into account during power on sequence. Restart
UNIGEN 2.0.
On LCD, modification of port numbers is taken into account during power on sequence. Restart
UNIGEN 2.0.
47
User manual – technical documentation A51 V0 9 0020 A EN
If an active fault exist and has not been acknowledged yet, the active fault page will be displayed.
Otherwise if an active alarm exist and has not been acknowledged yet, the active alarm page will be
displayed.
Otherwise the information page will be displayed.
You can navigate through these dedicated pages with the high, low, left, right arrows buttons.
To return on previous page, press ESC or button.
6.7.2 Information
These pages allow displaying the power current state with the associate elapsed time in this state.
In addition, 2 variables per page can be consulted.
Power [4001] displays the unit current state regarding power management.
Custom variables: To display any reading, enter its 5-digit code.
48
A51 V0 9 0020 A EN User manual – technical documentation
7 COMMUNICATION BUSES
7.1.1 Capabilities
In addition, in order to decrease load on Ethernet, the following functions are supported:
Reading Bit Fields, listed in a dedicated tab of the file and organized in 16-bit words
Reading contiguous configurable data block
7.1.2 Configuration
UNIGEN 2.0 handles up to 4 Modbus TCP connections. This can be used for multiple HMIs for
example.
For more details on the Ethernet configuration, see the chapter 2.1.
7.1.3 Description
WARNING
RISK OF UNINTENDED EQUIPMENT OPERATION
It’s recommended to stop the engine before changing some settings
Failure to follow this instruction can damage equipment
Functions
UNIGEN 2.0 supports the following Modbus functions:
Function Description
01, 02 Read logical values (coil status, discrete input status)
03, 04 Read holding/input registers (16 bits)
05 Write logical value (single coil)
06 Write single register (16-bit variable)
15 (0x0F) Write multiple logical values (multiple coils)
16 (0x10) Write multiple registers
All UNIGEN 2.0 variables are 16-bit registers. Yet it might be useful to consider them as logical values
(if they are only set to 0 or 1) to simplify Modbus communication with some external PLC. If function
01 or 02 is used to read an internal register that is different from 0, then returned value will be 1.
49
User manual – technical documentation A51 V0 9 0020 A EN
UNIGEN 2.0 registers start from address 0. Depending on your Modbus TCP client equipment-
software, you may need to use an offset of 1 when reading/writing registers as addresses may start
from address 1. In this case, request address/register number 1 to access variable 0000 inside
UNIGEN 2.0.
Access rights
The access rights depend on the parameter nature and on massive permissions. To grant massive
access rights, set to 1 the corresponding bits in the word 3015:
function registers
Writing to Engine
Writing to input
Reading using
Writing using
Modbus TCP
Modbus TCP
Date/Time
Not used
Not used
Writing to
Not used
Not used
Not used
counters
Bit # 9 8 7 6 5 4 3 2 1 0
Default value 1 1 0 0 0 0 1 0 0 0
Bit Fields
Bit fields are meant for decreasing communication bus load. They pack up to 16 logic variables inside
a single register. This way a single Modbus request can be used to read a chunk of information. Each
variable contains the current value of 16 logic variables such as breaker positions, faults, alarms…
They are listed out in the Bit fields tab of the document A51V0 90030_.xls.
The bit fields 0956 … 0969 have latched values: a reset is required for them to return to 0.
Note: Available data are related only to faults that occurred after the latest power up sequence.
Events that occurred before UNIGEN 2.0 has been power cycled are listed in the FAULT pages but NOT
among the variables.
50
A51 V0 9 0020 A EN User manual – technical documentation
Custom blocks
To create your own blocks, use the variables 10000 … 10299 in CRE Config/Configuration/Modbus.
There are two ways to configure these blocks:
A. Configuration in CRE Config/Modbus: enter the codes of the variables to read; the readings
on the registers 10000 … 10299 will be the pointed values
B. Configuration by an external device; this device must request the following:
1. Write 1 to 3016 to enter into the configuration mode
2. Write the codes to the desired registers (10000 … 10299)
3. Write 0 to 3016 to enter into the read mode
Then to read your own block, you just need to read by Modbus the register 10000 to 10299.
Time stamping is done by the master.
Example:
If the configuration is as follows E10000 = 14; E10001=15; E10002=16, the reading by Modbus of the
3 registers will give to you the hours/minutes/seconds of the UNIGEN 2.0.
51
User manual – technical documentation A51 V0 9 0020 A EN
CANopen extension modules can be used to increase the number of digital inputs and outputs of
UNIGEN 2.0. Overall max. count of added inputs: 32 I and 32 O. They are read/written to every
100ms.
7.2.1 Hardware
Each bus coupler is a slave node that supports up to 64 I/O modules that offer different kinds of I/O.
Outputs can be by transistors or relays. I/Os can be distributed across up to 4 daisy-chained couplers.
750-3xx
The modules are stackable and mounted on a DIN-rail. Refer to the extension module’s user manual
for correct wiring on the CANopen module side. Check whether the inputs/outputs are protected
against short-circuits. If needed, connect the drain to the DIN rail.
Make sure there is a resistor of 120 between CAN H and CAN L on both ends of the cable. For
details, refer to the Appendix CAN bus good practices.
52
A51 V0 9 0020 A EN User manual – technical documentation
7.2.2 Configuration
Setting Label Value Description
3151 CANopen config 1 8 inputs + 8 outputs of coupler ID# 1
2 16 inputs + 16 outputs of coupler ID# 1
3 32 inputs + 32 outputs of coupler ID# 1
4 Custom configuration, defined by more settings
3153 CANopen ID# 1 0 … 255 Identifier of the first coupler
3154 CANopen IN 1 0 … 32 Count of inputs on the first coupler
3155 CANopen OUT 1 0 … 32 Count of outputs on the first coupler
3156 CANopen ID# 2 0 … 255 Identifier of the second coupler
3157 CANopen IN 2 0 … 32 Count of inputs on the second coupler
3158 CANopen OUT 2 0 … 32 Count of outputs on the second coupler
3159 CANopen ID# 3 0 … 255 Identifier of the third coupler
3160 CANopen IN 3 0 … 32 Count of inputs on the third coupler
3161 CANopen OUT 3 0 … 32 Count of outputs on the third coupler
3162 CANopen ID# 4 0 … 255 Identifier of the fourth coupler
3163 CANopen IN 4 0 … 32 Count of inputs on the fourth coupler
3164 CANopen OUT 4 0 … 32 Count of outputs on the fourth coupler
The assignment of I/Os is done in the order of couplers and the lower variable number is associated
to the lower message number configured.
The CANopen inputs and outputs have the same attributes as regular inputs and outputs except the
Delay on drop-off of inputs (See chapter 8.3):
Setting Attribute
Digital inputs 1 … 32
3200 … 3231 Function
3232 … 3263 Delay on pick-up
3264 … 3295 Validity
3296 … 3327 Direction
Digital outputs 1 … 32
3350 … 3381 Function
3382 … 3413 Mode (direction):
0: normally de-energized
1: normally energized
7.2.3 Mapping
53
User manual – technical documentation A51 V0 9 0020 A EN
7.3.1 Overview
J1939 is a CAN protocol used by “electronic” motors, which include an ECU (or ECM, EMS). In the
case of UNIGEN 2.0, it allows you to send commands of speed control.
UNIGEN 2.0 can communicate with a large number of J1939 engines. As the engine list accrues,
please contact CRE Technology or your local distributor if your engine is not mentioned in this
document.
In any case, if your ECU does not belong to the following list, try:
1. To select the generic ECU from your manufacturer
2. To select the GENERIC manufacturer, then modify the UNIGEN 2.0 [3103] and ECU [3102]
address according to the ECU documentation (Modification by variable number)
54
A51 V0 9 0020 A EN User manual – technical documentation
[10]
ECU8 + Smart Connect [3]
Voir Appendice MTU
(1) Cummins 109G ECU may not support speed control through J1939. ECU with Cummins G Drive firmware should support J1939 speed control
55
User manual – technical documentation A51 V0 9 0020 A EN
Erase
PC
Erase and Reset to factory settings are available in CRE Config (for the latter, select
Options/Advanced and connect on level 2).
CAUTION
To edit a new configuration from the configuration file, it is strongly recommended to
use a configuration file compatible with the installed firmware version:
1. Upload the file from UNIGEN 2.0
2. Modify it
3. Download this new configuration file to UNIGEN 2.0
56
A51 V0 9 0020 A EN User manual – technical documentation
Log file
Upload the file. In the web browser, to save the file, right-click in the page with the file, and select
Save as.
List of actions on alarm/fault
By selecting “Action on alarm/fault”, a file containing all potential alarms/faults and their use is
displayed.
To save this file, right-click in the page with the text file, and select Save as.
Example:
S/N:4316A0003
Type:A51V0
Version:v0.03
Bootversion:v1.20
Date:06/01/17
Hour:10h30m59s
0 : Disable
1 : Gen electrical fault
3 : Alarm
57
User manual – technical documentation A51 V0 9 0020 A EN
The parameters are stored in a non-volatile FLASH memory in the unit. It is possible to download or
upload them with a PC, which allows the user to save, modify and reuse them later.
All these values are stored in the text file. This chapter describes the layout of the file.
8.2.2 Text file description
The complete unit setup can be contained in a simple text file. This file can be downloaded from
UNIGEN 2.0 to be kept on a PC. It can also be manually edited on a PC and sent to UNIGEN 2.0 to fully
setup it in a single step.
This text file is made up of different blocks:
Parameter values
Label definitions
Text definitions
Unit and accuracy definitions
Parameter definition block
The block start is the {PARAMETERS} statement. Each setting (2000 … 4000) can be found as an input
in this block. The structure of the input is as follows:
The variable parameter number preceded by the letter V (Ex: V02000)
The parameter value (Ex: 2)
The label (optional: only for user information) (Ex: Nb of gen.)
The minimal value (optional: only for user information) (Ex: +00001)
The maximal value (optional: only for user information) (Ex: +00032)
Unit
Example:
{PARAMETERS}
V02000 2 Nb of gen. +00001 +00032
V02001 1 GE number +00001 +00032
It is possible to modify the values directly in the text file before uploading it into UNIGEN 2.0. The
user must be sure that the modified value is within the minimum / maximum range of the
parameter. Failure to do so leads to an error message during uploading (see chapter 9.3).
It is also possible to write to an incomplete parameter block (not all parameters are displayed in the
list). When uploaded, such a file modifies only the parameters which have been entered, the others
remain unchanged. This procedure can be used to upload an old text file into a newer module or to
activate special features independently.
Label definition block
The block start is the {LABELS} statement. This block is used to define custom labels for CRE Config
and the LCD (digital I/Os, analog Is, CANopen I/Os, relay outputs, cycles before maintenance).
Each line of this block contains 2 elements:
The variable number of the text, preceded by the letter L for label
The text itself between quotes
{LABELS}
L01130 Sample label
58
A51 V0 9 0020 A EN User manual – technical documentation
{UNITS}
U00150 14
U00151 18
U00152 00
…
A00150 1
A00151 1
A00152 0
…
The table below shows the list of codes which correspond to the supported accuracies and units. In
the examples above, analog input #1 (150 variable) is displayed in mBar (Unit code = 14) and with
one decimal digits (Accuracy code = 1).
Code Accuracy Code Unit Code Unit Code Unit Code Unit Code Unit
00 ““ Power-energy Pressure Temperature Time
0 1 Electrical 07 kW 13 Bar 18 °C 24 s
1 0.1 01 V 08 kWh 14 mBar 19 °F 25 h
2 0.01 02 kV 09 kVAR 15 kPa Volume 26 days
3 0.001 03 mA 10 kVARh 16 PSI 20 L Time related
3
04 A Rotating speed Angle 21 m 27 Hz/s
3 3
05 kA 11 rpm 17 ° 22 mm 28 m /h
Frequency Percent Mass 23 Gal 29 L/h
06 Hz 12 % 31 kg 30 Gal/h
59
User manual – technical documentation A51 V0 9 0020 A EN
Each input is tagged with a label defined in CRE Config/Configuration, and features several attributes
set in the Configuration menu:
Validity
Direction
Delay
Function
Configurable input label
This is the name you give to the input. The name shows in the info, alarm, and fault
screens if programmed accordingly.
Direction
For each input, two options are available:
Delays
For each input, two delays can be defined in 100ms steps between 0 and 6553s.
Raw input
Delay on Delay on
pick-up drop-off
Delayed input
Raw input
Delay on Delay on
pick-up drop-off
Delayed input
Summary
60
A51 V0 9 0020 A EN User manual – technical documentation
Note: If a digital input changes a piece of data also to be written by Modbus, the latest request takes
over the other. If 2 digital inputs are assigned to one function, the latest change is taken into account.
Input functions
ESSENTIAL INPUTS
Function Use/Description Ref. chapter
Must be selected if the input is not connected (default value
Not used
generally)
Generator breaker
Generator breaker position feedback 4.3
feedback
UNIGEN CONTROL
Function Use/Description Ref. chapter
UNIGEN activation This digital input allows you to start or stop the synchronization. 3
EXTERNAL ALARMS/FAULTS
Function Use/Description Ref. chapter
Generator fault request External protection set a generator fault. 4.1.1
Remote alarm External protection set an alarm on the product ibidem
Selective external reset; in addition, an output must be preset to
Stop horn 4.1.2
Horn
ALTERNATIVE SELECTIONS
Function Use/Description Ref. chapter
Nominal speed 2 Alternative nominal speed selected
Nominal voltage 2 Alternative nominal voltage selected
61
User manual – technical documentation A51 V0 9 0020 A EN
Each output is tagged with a label defined in CRE Config/Configuration, and features several
attributes set in the Configuration menu:
Direction
Pulse length: 0 means no pulse
Function
Directions
Each output can be:
NE: normally energized; the output is de-energized when its function is activated
ND: normally de-energized; the output is energized when its function is activated
Pulse length
Each digital output can be configured to act as a pulse. The pulses lengths are defined with the
parameters E2761 to E2766.
Output functions
SYNCHRO COMMANDS
Function Description Ref. chapter
Synch check relay Command to close generator breaker 4.3
LEDS STATUS
Function Description Ref. chapter
Faults LED Reflects the led status
Alarm LED idem
Generator LED Reflects the led status
GENERATOR STATUS
Function Description Ref. chapter
Generator ready Activated when generator voltages and frequency are stable
Generator voltage
Activated if the generator is started and a voltage is detected
presence
Generator stop Activated if generator is at rest
62
A51 V0 9 0020 A EN User manual – technical documentation
SPEED/VOLTAGE COMMANDS
Function Description Ref. chapter
Increase speed by pulse Speed regulator requiring +/- contacts 5.4
Decrease speed by
Speed regulator requiring +/- contacts. ibidem
pulse
Increase voltage by
Idem speed ibidem
pulse
Decrease voltage by
Idem speed ibidem
pulse
SYNCHRONIZATION
Function Description Ref. chapter
Dead bus bar 4.1
Phase sequence match Phase sequences are the same for synchronization 3.1
Voltage match Voltages are close enough for synchronization ibidem
Frequency match Frequencies are close enough for synchronization ibidem
Phase match Phases are close enough for synchronization ibidem
Authorization to close
Synchronization request accepted ibidem
breaker
Fail to synchronize Synchronization request denied (PID setting, fail to close breaker) ibidem
ALARMS/FAULTS SUMMARY
Function Description Ref. chapter
Generator electrical faults 4.1
External panel. Trigger: at least one generator-detected “fault”
summary
Alarms summary External panel. Trigger: at least one generator-detected “alarm” ibidem
External horn or flashing light. Activated whenever a protection
Horn triggers. The output is activated when one or more of summary 4.1.2
outputs is activated, and reset on acknowledgment
63
User manual – technical documentation A51 V0 9 0020 A EN
In addition, most protection activations described in chapter 4.2 can be reported on a digital output.
On CRE Config, they are listed by categories as shown below. These outputs are available only if the
associate alarm/fault is configured.
ENGINE PROTECTION
GENERATOR PROTECTION
COMMUNICATION FAULTS
64
A51 V0 9 0020 A EN User manual – technical documentation
Input
Each input is tagged with a name and preset to a function. It features several attributes preset in CRE
Config/Configuration/Inputs/Analog inputs:
Accuracy (number of digits after decimal point) among 1 / 0.1 / 0.01 / 0.001
Unit, among No unit, V, kV, mA, A, kA, Hz, kW, kWh, kVAR, kVARh, rpm, %, Bar, mbar, kPa,
psi, °, °C, °F, L, Gal, s, h, days, Hz/s, m3/h, L/h, Gal/h
Calibration, measure value according to resistor value in
Calibration
Calibration is used to estimate a reading from a resistance value by interpolation between 2
wrapping resistance values. Negative values are supported for readings. Enter a table in CRE Config
/Configuration/Inputs/Analog inputs/Analog Measure Calibration or in text file.
Select the Accuracy, desired grade of details for tweaking and manual entering: 0.001, 0.01, 0.1 or 1.
Enter the limits of reading according to the sensor calibration; generally the lower limit is 0 and the
slope is Range/Rating. Calculate and enter the intermediary readings to get a linear distribution.
Protections
The input threshold features several attributes preset in CRE Config/Configuration/Protections/
Analog inputs protection:
Level (LV): limit value in units; it can be a low or high threshold
Delay (TM): time after which the trespassing is confirmed
Validation (CT): protection type to which the signal contributes (3 potential values; see chapter 6.1)
Direction (SS): is it a low (0) or high (1) threshold
SS C2
C3
IN
H,2
LV OUT: past threshold
L,3
TM TON
CT C1 8
1 OUT: protection type
Reset
Summary
The attributes show in the text file:
Threshold
Level Delay Validation Direction Function
AI 1 level 1 2600 2601 2602
2606 2607
AI 1 level 2 2603 2604 2605
AI 2 level 1 2608 2609 2610
2614 2615
AI 2 level 2 2611 2612 2613
AI 3 level 1 2616 2617 2618
2622 2623
AI 3 level 2 2619 2620 2621
65
User manual – technical documentation A51 V0 9 0020 A EN
66
A51 V0 9 0020 A EN User manual – technical documentation
9 MAINTENANCE
Prerequisite:
1. Upgrading software is done via the Ethernet connection. It’s mandatory to have a PC and to
connect on UNIGEN 2.0
2. Stop the generator
3. Save the current configuration as a text file; refer to chapter 8.1.1 Otherwise the default
settings will be enforced (except for the Ethernet settings)
4. Disconnect all the terminals, except the power supply and Ethernet connections.
Start upgrade:
1. Connect to CRE Config/System/PC transmit-receive or to UNIGEN 2.0 web site
2. Select Update firmware and browse the archive (UNIGEN 2.0 version .zip, ex: v1.00.zip)
3. Click on Update button
Alarm/Fault leds blink and state is display on LCD screen
4. Wait until Update firmware successful shows
5. If need, restore the settings from the text file previously save.
Note: During upgrading (about 2 minutes), UNIGEN 2.0 re-start. Wait until you receive the end of
upgrade before using UNIGEN 2.0.
2. Downloading
When you receive the related .bin file, in CRE Config/System/PC transmit-receive, download
.bin file via Upload file command.
Wait until Download successful shows.
Note: Unless the contrary is expressly stipulated, CRE Technology reserves the right to use your
translation for other uses.
9.3 TROUBLESHOOTING
To get a history of alarms-faults, stop the generator, connect to CRE Config/System/PC transmit-
receive/Download log file from UNIGEN 2.0, and click Download.
To restore factory settings into CRE Config, navigate to CRE Config/System/PC transmit-receive/Reset
factory settings, and click Reset.
67
User manual – technical documentation A51 V0 9 0020 A EN
No J1939 communication
Check that the ECU is powered.
Check that the configuration correspond to the engine/ECU.
Check that the wiring is correct. Refer to the Appendix.
Power cycle UNIGEN 2.0 and ECU.
Check that the ECU and its settings are consistent with the J1939 standard.
Note: Some ECUs do not provide information if the engine is on stop.
68
A51 V0 9 0020 A EN User manual – technical documentation
69
User manual – technical documentation A51 V0 9 0020 A EN
Warnings do not prevent the module to work but inform the user of a potential problem in his
configuration file.
70
A51 V0 9 0020 A EN User manual – technical documentation
10 APPENDIX
UNIGEN 2.0
Through the K1 connection box, the bus connects ECU8, Smart Connect and UNIGEN 2.0: one bus
between ECU8 and Smart Connect, one bus between Smart Connect and UNIGEN 2.0. X4 is the Smart
Connect J1939 CAN port.
71
User manual – technical documentation A51 V0 9 0020 A EN
72
A51 V0 9 0020 A EN User manual – technical documentation
WARNING
RISK OF EQUIPMENT DAMAGE
Switch off the unit before plugging or unplugging the CAN bus connector or disconnecting the wires
Failure to follow this instruction can damage the CAN transmitter/receiver
Cables used must be selected to respond to CAN bus specificities. Always use shielded twisted wire
pairs. Deploy the CAN bus in a bus (no mesh, ring or star topology) as shown below:
Both ends of the CAN bus must be terminated with a 120Ω resistor.
The next figure gives the example of three units connected through a CAN bus. Do NOT install any
resistor in the middle unit and connect the incoming wire and the outgoing wire on the same
terminal (max 1.5 mm² or AWG16; use preferably the same section for both).
120Ω
H H H
RES RES RES
GND GND GND
73
User manual – technical documentation A51 V0 9 0020 A EN
CRE Technology provides a complete range of products aimed at installing your CAN bus
(cords, wires, connectors…). Please read the document Harness information or contact
your local CRE Technology distributor to help you choose equipment that fits your needs.
Note: If you disconnect a UNIGEN 2.0 from the inter UNIGEN 2.0 CAN bus, change the count of
generators on ALL other UNIGEN 2.0 units of the power plant.
74
A51 V0 9 0020 A EN User manual – technical documentation
+
Set point + G Command
–
I
Measurement
G: global gain
P: proportional gain
I: integral gain
P adjusts the rise time (time needed for the system to reach its set point for the first time). Using
only the P factor always leaves a static error between the set point and the actual value.
I reduces the deviation between the set point and the actual value.
By increasing P or I, the rise time decreases. However, the overshoot increases and may also make
the system unstable (P: fast hunting, I: slow hunting).
G is a sensitivity adjustment for the other settings.
Empirical tuning:
A. First set G to 50%
B. Set the parameters P, and I to 0
C. Increase the value of P until the system becomes unstable. From this position, decrease the
value of P to 60% of the previous value
D. If the system is unstable, decrease G; if it is too slow, increase G.
75
User manual – technical documentation A51 V0 9 0020 A EN
HH
LL
LL
H
H
HH
HH
L
LL
H
L
Generator Underfrequency (81L)
Generator Overfrequency (81H)
Notes :
1) CAN bus inter-UNIGEN faults are not shown.
2) H = level 1, HH = level2
76
A51 V0 9 0020 A EN User manual – technical documentation
CRE TECHNOLOGY
Website: http://www.cretechnology.com
Email: [email protected]
Technical support: +33 (0)4 92 38 86 86 (office hours: 8.30AM - 12AM / 2PM - 6PM GMT +1)
Email: [email protected]
Check our entire distributors list around the world on our Web site http://www.cretechnology.com.
77
User manual – technical documentation A51 V0 9 0020 A EN
www.cretechnology.com
78