Valve Control Module: Xseries, RMC, and Xio
Valve Control Module: Xseries, RMC, and Xio
— —
Overview Wiring requirements
The 2100412 TFIO module is a software-configurable Sufficient gauge wire should be used to handle total load
combination I/O module specifically tailored for valve control current. Use shielded pair or twisted pair conductors to
applications. The module incorporates six general-purpose reduce the possibility of erroneous transitions on the
digital/pulse input/outputs. Two source mode digital outputs inputs in high EMI/RFI environments. (Ground the shield at
and one 4 to 20 mA sink/source mode analog output are also field device only).
provided.
When digital outputs are used to sink current, the sum total
sink current for all points and modules should not exceed
5A total. If more than 5A are required, separate ground
— wires from module output ground to power source ground
Point specifications terminal
(bus bar) are required. Failure to do so may cause erratic
Electrical (each point) system operation.
• Open circuit voltage • 5VDC (Internally up to
• Short circuit leakage current 5VDC Nom.)
• Input capacitance • -430uA typical
• Maximum allowable • 1000pF typical
voltage range on input • -0.5VDC to 26.5VDC
Hot Pluggable
SIG +5
FIELD 24V
INPUT SENSE
WIRING
OUTPUT CONTROL
GND
POINT CONNECTIONS
OPTO 24V
INPUT SENSE
NPN
COUPLER SWITCH OUTPUT CONTROL
OR OR
24 VDC MAX.
3.0 VDC
SIGNAL SIG +5
SIG
OUTPUT
2.0 VDC
0 VDC MIN.
24V
INPUT SENSE
OUTPUT CONTROL
24V
INPUT SENSE
OUTPUT CONTROL
GND GND
BUS
BAR
4 VALVE CONTROL MODULE | XSERIES, RMC, AND XIO | DS/210119-EN
4–20mA
+
VDC INTERNAL
- ioVBB
i SOURCE (Pin 3) i SOURCE (+)
OPTIONAL
50mA
JUMPER
4–20mA
J1 J2 J3 J4
1 Point 1 SIG (DI or DO) AO VDC source Point 3 SIG (DI or DO) Point 5 SIG (DO Output source)
2 Point 1 GND AO I sink Point 3 GND Point 6 SIG (DI or DO) w/o GND
3 Point 2 SIG (DI or DO) AO I source Point 4 SIG (DI or DO) Point 7 SIG (DO Output source)
4 Point 2 GND AO VDC common Point 4 GND Point 6 SIG (DI or DO) w/o GND
6 VALVE CONTROL MODULE | XSERIES, RMC, AND XIO | DS/210119-EN
—
Notes
—
ABB Inc. Kansas Office Texas Office – Pleasanton
Measurement & Analytics 2705 Centennial Boulevard 150 Eagle Ford Road
Quotes: [email protected] Liberal, KS 67901 Pleasanton, TX 78064
Orders: [email protected] Ph: +1 620 626 4350 Ph: +1 830 569 8062
Training: [email protected]
Support: [email protected] Texas Office – Odessa
+1 800 442 3097 (opt. 2) 8007 East Business 20
Odessa, TX 79765
Main Office Ph: +1 432 272 1173
7051 Industrial Boulevard Texas Office – Houston
Bartlesville, OK 74006 3700 West Sam Houston
Ph: +1 918 338 4888 Parkway South, Suite 600
Houston, TX 77042
Ph: +1 713 587 8000
www.abb.com/upstream
—
DS/2101109-EN Rev. AG 03.2020
We reserve the right to make technical changes or modify the contents of this document
without prior notice. With regard to purchase orders, the agreed particulars shall prevail.
ABB does not accept any responsibility whatsoever for potential errors or possible lack of
information in this document.
We reserve all rights in this document and in the subject matter and illustrations contained
therein. Any reproduction, disclosure to third parties or utilization of its contents – in whole or
in parts – is forbidden without prior written consent of ABB.