Onsite Calibration of Flow Meters by ATT Reference With Wetted Transducers
Onsite Calibration of Flow Meters by ATT Reference With Wetted Transducers
Abstract
South-to-North Water Diversion Project aims to channel billions of cubic meters of fresh water annually from the Yangtze
River in southern China to the more arid and industrialized north through canal systems. Water transfer billing from South-
to-North Company to local companies depends on flow rate measurements and they show considerable inconsistency. A
typical branch pipeline from the main channel to a water factory includes a sluice chamber, a short square closed fully
filled channel, a balance tank, and several kilometers of circular pipe with some valves and other pipe fittings. There are at
least three flowmeters installed: 2-path ultrasonic flowmeter on square channel owned by the South-to-North Company,
two or three magnetic or ultrasonic flowmeters on different positions of circular pipe by the local water transportation
company and water factory. More than ten percent of the water imbalance exists among those flowmeters. We have installed
8-path acoustic reference flowmeter with 16 wetted ultrasonic transducers on a circular tube and used state-of-the-art
techniques to make an accurate and traceable flowrate reference accepted by the three parties mutually. The installation
and data analysis of our reference flowmeter is described in detail, and troubleshooting of other flowmeters will be done
based on the reference flowrate.
1 Introduction
With the development of society and economy, water resources have been being strategically important in China. To
alleviate the mismatch of regional economic development and water resources distribution in China, a large amount of
studies, researches and projects were conducted and a series of great hydraulic projects, such as Three Gorges Project and
Inter-Basin Water Transfer Project, were finished.
The South-to-North Water Diversion Project is a multi-decade infrastructure mega-project in China. Ultimately it aims to
channel 44.8 billion cubic meters of fresh water annually from the Yangtze River in southern China to the more arid and
industrialized north through three canal systems. The central route runs from Danjiangkou Reservoir on the Han River, a
tributary of the Yangtze River, to Beijing and Tianjin. This project involved raising the height of the Danjiangkou dam by
increasing the dam crest elevation from 162 m to 176.6 m above the sea level. And this allowed the flow into the water
diversion canal to begin "downhill", pulled by gravity, to the lower elevation of the canals, without the need for pump
stations. The whole project was completed around 2014. Fig. 1 shows the headwork project and Yellow river crossing
project separately.
(b) main channel (c) intake gate flowmeter (d) local branch flowmeters
Fig. 2: Flow measurement for a typical water delivery branch line
2 NIM reference
2.1 Laboratory test of NIM reference flowmeter
The reference ATT flow meter of NIM is a 8 path meter in 2 crossed planes. The uncertainty of the ATT method used for
large pipe flow measurement stems mainly from the fact, that there is: 1) not a high enough precision of the transit time
measurement, and uncorrected zero point especially for low velocity measurement; 2) not an accurate enough geometric
parameter measurement; 3) a flow field influence related to transducer protrusion / recession and not enough upstream /
downstream straight pipe length. To provide an accurate reference flow rate value, all above three points have to be dealt
with carefully. A FARO arm (Figure 3b) was used to get accurate geometric parameters, several experiments were carried
out to test the transducer protrusion effect using a gravimetric flow rate facility (Figure 3a).
The gravimetric method is used to get a reference flow rate, and the NIM ATT flow meter with a DN400 pipe is tested at
three different transducer positions. Figure 4 shows the differences of flow rate deviation at the three positions. It is clear
that the recessed position can provide a stable flow rate without influence of the velocity. So it was decided to use the
recessed positions as the best choice for the onsite installation positions of the transducers.
To get an accurate correction factor for larger pipe, an experiment was conducted for a DN1000 pipe using the same
gravimetric facility. The result shows a stable bias of negative 1.6%. After the implementation of a correction factor of
1.016, the flow rate error of this DN1000 flow meter is in Figure 5. There are four circles for each velocity step, and we
calculate the standard deviation for each step. They are all smaller than 0.5%. We will use this corrector factor for the
onsite flow calibration because they have the similar pipe diameter.
It can be seen, that the ATT meter at the intake gate has a deviation of around 20% compared to the other two MID meters.
The parties involved in the billing of the water quantities were not satisfied with his situations and asked therefore a third
party (NIM) to carry out a reference measurement. The regular flow rate is about 0.7 m3/s, so the flow velocity is 0.35 m/s
in the square pipe with a dimension of 1.4m*1.4m and 0.62 m/s in the circular pipe with a diameter of 1.2 m. low velocity
should be one of the reasons for bad performance of the three flowmeters.
3.2 Comparison with the reference measurements
The reference measurement section was located close to the pipeline magnetic flow meter (Figure 2a). The exact
parameterization of the geometrical quantities was done as described in section 2.2. The result for the actual path heights
are given in Table 1. The design value and practical value of the path heights usually have non-negligible difference. It’s
neccessary to use the practical path heights to calculate the optimized weights.
Table 1: integration weights correction based on practical path heights
path no. A1 A2 A3 A4 B1 B2 B3 B4
ideal path height 0.8090 0.3090 -0.3090 -0.8090 0.8090 0.3090 -0.3090 -0.8090
practical path height 0.8140 0.3141 -0.3092 -0.8116 0.8079 0.3069 -0.3076 -0.8112
default wi 0.21708 0.56832 0.56832 0.21708 0.21708 0.56832 0.56832 0.21708
optimized wi 0.20928 0.57216 0.57434 0.21245 0.21702 0.56641 0.57044 0.21428
With the reference meter in place and correctly parameterized, a series of operating points were set with increasing flow
rate as can be seen in Figure 8. All the flow rates were kept constant for about 15min with the exception of one. The flow
varied between 300 and 3200m3/h in steps of ~500 m3/h. The flow rate data between each pair of dotted vertical lines will
be used to calculate averaged flowrate and its standard deviation for each step. The intake gate ATT in square pipe shows
much larger oscillation than the NIM reference in the circular pipe. The reason may be the small change of water level in
balance tank which connects the square pipe and circular pipe. From Figure 8 it can be concluded, that the installed ATT
flow meter of the water seller is constantly above the reference ATT meter by about 20% with a small decrease with
increasing velocity.
Figure 9 shows the relative deviations in % of the three installed flow meters, the ATT meter of the installer and the two
magnetic flow meters with respect to the NIM reference. It is interesting to note that one magnetic flow meter has nearly a
constant deviation of about 4% over the whole range, while the other magnetic flow meter has a typical decaying trend of
1/velocity, starting with a very high value of +40% and then going down towards the first magnetic flow meter. The two
magnetic meters are from different companies. The discrepancy of this behavior is not yet clear. The ATT flow meter
performs better than one of the two magnetic flow meters for small velocities, while for higher velocities the deviations are
much higher (~20%) than the reference value. This behavior cannot fully be explained at the moment and must be
investigated further. Non optimal parametrization of the flow meter is one of the possible reason.
Figure 10a & 10b show the velocity distribution obtained by the NIM ATT reference flow meter for the different velocities.
In Fig. 10a the individual path velocities (totally 8) are shown, indicating small cross flow components for the higher
velocities while in Figure 10b the averaged layer velocities (totally 4) are displayed in a relative way normalized with the
average velocity. The relative flow profile changes a little for the condition of the lowest velocity.
4 Case 2: Delivery branch line with ATT 2-path/ MID/ATT 1-path meters in series
4.1 History
The second case deals with a similar situation as the first one. The difference from the flow measuring point of view is the
1E1P ATT flow meter of the water factory. The detailed installation is shown in Figure 11. From the main canal the
delivery branch square shaped channel leads to the water tank. At the entrance to the delivery channel there are a
maintenance gate and a control gate, which is in normal operation at 60% open. Before the water enters the water tank
there is a trash rack, which has additionally a fine mesh reducing sand deposits in the tank (see Figure 12). The deposits
stick however to the mesh and get also deposited near the trash rack. The trash rack itself is located only a short distance
down-stream of the 1E2P ATT flow meter. The locations of the MID, the reference flow meter of NIM and the 1E1P ATT
meter can be read out from Figure 11. All three meters are downstream of the tank, while the ATT 1E2P meter is upstream
of the tank. The influence of the tank is considered to be small, as in steady state the height of canal and tank are nearly
identical. Unfortunately, the water level measurement of tank and canal were not available at the time of the investigation.
The velocity covers a small range of values from around 0.15m/s to 0.35m/s, that means really small flow rates. The pump
station was put into operation in 2016 and in 2017 complaints from the companies were reported that the meters are drifting
away, especially the 1E2P ATT flow meter.
Fig. 13: historical flow rate before and after deposit cleaning
Figure 14 shows the readings of all four flow meters for the measurements in May and 3 readings (reference, 1E2P ATT
and MID) for the July measurements. The deviations in % are displayed with the reference meter as the zero line. The
figure shows some interesting findings:
The 1E2P ATT flow meter at the inlet to the tank shows for both measurement campaigns (May 25 th and July 20th)
very large deviations of over 100%. As mentioned before, in between these two dates the meter showed readings
which were very close to the reference (~2-3%), after the cleaning.
The other flow meters are all very close together, but their readings are ~10% under the reference values of the NIM
meter.
5 Conclusions
1. Water resource is very important and expensive in some cities in China. Many large flowmeters are used for trade.
Although the claimed accuracy is very high, the practical data from onsite flow meters often show considerable
inconsistencies. Those flowmeter users have the motivation to seek effective and realizable online calibration method
regardless of cost.
2. There are many reasons for those large inconsistencies including low velocity, complex flow field, sand deposit, and
so on. Every case has its unique condition. Wet ATT method with precise installation is a feasible way to calibrate
other flowmeters online. More experiments and practices will be carried out to optimize and extend the application of
this method.
Acknowledgments
This paper is currently supported by The National Key R&D Program of China “Research and application of national
quality infrastructure” (project/subject SN. 2018YFF0216001)
References
[1] IEC 60041. (1991). International Code for the Field Acceptance Test to determine the hydraulic performance
of hydraulic turbines, storage, pumps and pump turbines.
[2] ISO 6416. (2005). Hydrometry– Measurement of discharge by the ultrasonic (acoustic) method. BS EN
[3] Hu Y, Zhang T, Zheng D, et al. (2013). Estimation on influence of probe protrusion length of ultrasonic
flowmeteron measurement. Journal of Tianjin University (Science and Technology), 46(9): 776-783. (in
Chinese)
[4] Tresch T, Luescher B, Staubli T. Gruber P. (2008). Presentation of optimized integration methods and
weighting corrections for the acoustic discharge measurement. IGHEM 2008, Milano, Italy.
[5] Voser A, Staubli T. (1996). CFD calculations of the protrusion effect and impact on the acoustic discharge
measurement accuracy. IGHEM 1996, Montreal, Canada.