Armorstart LT Distributed Motor Controllers: Selection Guide
Armorstart LT Distributed Motor Controllers: Selection Guide
ArmorStart LT is available with Full Voltage, Full Voltage Reversing, or Variable Speed motor control performance. It is equipped with a UL
Listed at-motor disconnect that supports a lockout tagout (LOTO) provision. ArmorStart LT is listed suitable for group motor installations per
UL and can be applied with either branch circuit breaker protection or fuse protection. It provides a robust IP66/UL Type 4/12 enclosure
suitable for water washdown environments in a single box construction that will minimize inventory needs. All external connections are made
from the bottom of the unit. The power, control, and motor connections are made via a gland plate, as standard.
ArmorStart LT provides several standard features. It can be ordered with EtherNet/IP or DeviceNet network support. Each unit will be
equipped with quick disconnect receptacles for I/O and the network. Users will experience tools such as a Logix Add-On Profile (AOP), setup
wizards, auto-generated tags, and embedded webserver support, that allows access to status and diagnostics from anywhere in the world.
Lastly, the electronic control module (ECM) includes externally accessible node address switches, configurable I/O, and comprehensive
status and diagnostics LEDs.
The ArmorStart LT can also be configured with several options that can further reduce installation and commissioning time. Quick
disconnects are available for power, control, and motor connections, using ArmorConnect cable solutions. A Hand-Off-Auto keypad for local
control is an available option. The optional internal power supply (IPS), eliminates the need to run separate control power. ArmorStart LT
Bulletin 294 can be configured with an electromechanical brake connection for the motor brake.
UL Listed "Suitable for Group Motor Applications" - Where NFPA 70 (NEC) or 79 are required installation standards, this Listing allows two
or more motors to be connected to the same branch circuit without individual motor branch short circuit or ground fault protection.
At-motor disconnect switch - ArmorStart LT offers a local ON/Off motor disconnecting means with lockout-tagout provision. Industrial
standards require a local at-motor disconnect to be within eye sight of the motor for maintenance or other shutdown reasons.
User configureable I/O - ArmorStart LT offers six user configurable I/O points to be used with sensors and actuators. By default all six
points are configured as sinking 24V DC inputs. The user has the option to select any point as a sourcing 24V DC output.
Quick disconnect for I/O and Network - ArmorStart LT offers quick disconnect connectors for I/O and communications.
DeviceNet and EtherNet/IP node address - ArmorStart LT offers externally accessible address switches for node address configuration.
The address can also be set statically or dynamically.
EMI filter - ArmorStart LT Bulletin 294 provides an internal EMI filter and is CE compliant. For CE compliant installations refer to the
recommended EMI/RFI cord grip accessory. For availability of the quick disconnect shielded motor cable contact your local Rockwell
Automation sales office or Allen-Bradley distributor.
Local status and diagnostics - ArmorStart LT offers comprehensive status and diagnostics for I/O, Network, and device health via 12 LEDs
found on the electronic control module (ECM). If a fault occurs, a local fault reset button allows the user to quickly get the process started
after corrective action is taken.
Features (Continued)
Gland plate entrance - ArmorStart LT offers conduit holes or quick-disconnect receptacles for connecting three-phase, control power, and
motor.
Network Options
Native EtherNet/IP - ArmorStart LT supports native EtherNet/IP. EtherNet/IP allows complete integration of control and information.
EtherNet/IP allows users to integrate I/O control, device configuration, and data collection across multiple networks enabling internet
connectivity and information, anytime and anywhere.
Native DeviceNet - ArmorStart LT supports native DeviceNet. DeviceNet is a device-level network for industrial automation. It offers robust
and efficient data handling.
Embedded dual port switch - ArmorStart LT EtherNet/IP version includes an embedded dual port 10/100mb/s ethernet switch that supports
Linear, Star, or Device Level Ring (DLR) topology.
Device Level Ring (DLR) - ArmorStart LT EtherNet/IP version offers DLR support with beacon frame performance. DLR provides a single-
fault tolerant network solution that is self healing.
IEEE 1588 transparent clock - ArmorStart LT EtherNet/IP version supports the IEEE 1588 transparent clock.
Factory-Installed Options
Internal Power Supply (IPS) - ArmorStart LT offers the user an optional 24V DC IPS. The IPS provides all control and I/O power and is
sourced from the incoming 3-phase power. The at-motor disconnect will remove motor and output power when in the OFF position.
Hand/Off/Auto (HOA) keypad - ArmorStart LT offers an optional local Hand- Off-Auto keypad. This key pads allows local start/ stop motor
control regardless of PLC status.
Source brake - ArmorStart LT Bulletin 294 provides an optional internally controlled electromechanical motor brake contactor. The motor
brake power is sourced from 3-phase power. Short circuit and ground fault protection is provided by branch circuit protection; no internal
fuse or circuit breaker is provided.
Quick disconnect - ArmorStart LT offers a plug-n-play solution that simplifies wiring and installation. These factory installed quick disconnect
receptacles provide connectivity to separately selected ArmorConnect media and accessories for three-phase, control, and motor
connections. UL Listing is maintained when used with appropriate ArmorConnect power media and accessories.
Conduit/Blank gland - Two conduit/cord ready gland options are available. This gland will support a trunk and drop or daisy chain option.
Modes of Operation
Percent Voltage
voltage starting, and the Bulletin 291 offers full-voltage starting for reversing
applications.
Time in Seconds
Overload Protection
The Bulletin 290/291 ArmorStart LT Distributed Motor Controller incorporates electronic motor overload protection. This overload protection is
accomplished electronically with an I2t algorithm. The overload protection is programmable with a selectable trip class of 10, 15, or 20.
Ambient insensitivity is inherent in the electronic design of the overload.
% of Speed
100 With Slip
Compensation
Volts per Hertz – Bulletin 294 99
The ArmorStart LT provides a Volts per Hertz variable frequency drive
performance. This control yields the most cost effective performance for 98
material handling applications. The VFD is capable of Open Loop Speed Without Slip
97
Regulation with Slip Compensation. This configuration allows the VFD to Compensation
automatically adjust the output frequency to compensate for speed 96
changes due to motor loading. This feature is used where the motor must
run at a relatively constant speed regardless of torque output. 95
0 10 20 30 40 50 60 70 80 90 100
% of Load
Overload Protection
The Bulletin 294 ArmorStart LT Distributed Motor Controller incorporates programmable electronic motor overload protection. This overload
protection is accomplished electronically with an I2t algorithm. The overload provides Class 10 protection with speed sensitivity and overload
retention. Ambient insensitivity is inherent in the electronic design of the overload.
Certifications
cULus (File No. E3125, Guides
NLDX, NLDX7)
Catalog Number Explanation
Examples given in this section are for reference purposes. This basic explanation should not be used for product selection; not all
combinations will produce a valid catalog number.
a d g
Bulletin Number Overload Selection Option 1
Code Description Code Description Code Description
290 Full-Voltage Starter A 0.24…3.5 A 3 Hand/Off/Auto selector keypad
291 Reversing Starter B 1.1…7.6 A Hand/Off/Auto selector keypad with
3FR
Forward/Reverse
b e
Communications Control Voltage h
Code Description Code Description Option 2
E EtherNet/IP Z External 24V DC control power Code Description
D DeviceNet P Internal power supply blank§ Factory option
c f
Enclosure Type Gland Plate Options
Code Description (Power and Motor)
F Code Description
IP66/UL Type 4/12
G1 Conduit entry
G2 ArmorConnect
G3♣ Gland kits
IP66/UL Type 4 is available with all gland options. UL Type 4/12 is available with G1 and G3 gland option.
♣ See the Accessories section for special gland configurations for daisy chaining.
§ Leave blank unless there is a customer-specific option defined by the factory.
Full-voltage starters ⎯ IP66/UL Type 4 with ArmorConnect power media connections, up to 480Y/277V AC
External 24V DC Internal 24V DC
Current kW Hp Control Voltage Control Voltage
Rating [A] 230V AC, 50 Hz 400/415V AC, 50 Hz 200/230V AC, 60 Hz 460V AC, 60 Hz Cat. No. Cat. No.
0.24…3.5 0.75 1.5 1 2 290E-FAZ-G2 290E-FAP-G2
1.1…7.6 1.5 3 2 5 290E-FBZ-G2 290E-FBP-G2
Reversing starters ⎯ IP66/UL Type 4 with ArmorConnect power media connections, up to 480Y/277V ACC
External 24V DC Internal 24V DC
Current kW Hp Control Voltage Control Voltage
Rating [A] 230V AC, 50 Hz 400/415V AC, 50 Hz 200/230V AC, 60 Hz 460V AC, 60 Hz Cat. No. Cat. No.
0.24…3.5 0.75 1.5 1 2 291E-FAZ-G2 291E-FAP-G2
1.1…7.6 1.5 3 2 5 291E-FBZ-G2 291E-FBP-G2
Full-voltage starters ⎯ IP66/UL Type 4 with ArmorConnect power media connections, up to 480Y/277V AC
External 24V DC Internal 24V DC
Current kW Hp Control Voltage Control Voltage
Rating [A] 230V AC, 50 Hz 400/415V AC, 50 Hz 200/230V AC, 60 Hz 460V AC, 60 Hz Cat. No. Cat. No.
0.24…3.5 0.75 1.5 1 2 290D-FAZ-G2 290D-FAP-G2
1.1…7.6 1.5 3 2 5 290D-FBZ-G2 290D-FBP-G2
Reversing starters ⎯ IP66/UL Type 4 with ArmorConnect power media connections, up to 480Y/277V AC
External 24V DC Internal 24V DC
Current kW Hp Control Voltage Control Voltage
Rating [A] 230V AC, 50 Hz 400/415V AC, 50 Hz 200/230V AC, 60 Hz 460V AC, 60 Hz Cat. No. Cat. No.
0.24…3.5 0.75 1.5 1 2 291D-FAZ-G2 291D-FAP-G2
1.1…7.6 1.5 3 2 5 291D-FBZ-G2 291D-FBP-G2
♣ If required, replace the G1 suffix code with G3 and refer to the User-Installed Options for kit selection.
ECM (Electronic
Control Module)
6 Configurable I/Os
Wiring Access
Dual Port EtherNet/IP
or Single Port DeviceNet
Electrical Ratings
Application Three-phase
Number of Poles 3
Input Power Terminals L1, L2, L3
Motor Power Terminals T1, T2, T3
PE (Earth Ground) Terminal 4 PE terminals
Maximum Rated Operating
400Y/230…480Y/277 (-15%, +10%)
Voltage
Rated Impulsed Voltage (Uimp) 4 kV
Dielectric Withstand UL: 1960V AC, IEC: 2500V AC
Operating Frequency 50/60 Hz (±10%)
Cat. No. Hp (kW) Overload Range
Power Circuit
290_-___-A-*
Maximum Rated Operating 2 (1.5) 0.24…3.5 A
291_-___-A-*
Current
290_-___-B-*
5 (3) 1.1…7.6 A
291_-___-B-*
Overload Type Solid-state I2T
[10], 15, 20 with thermal memory retention
Trip Class
(see Motor Overload Trip Curves)
Trip Rating — Full Load
120% of FLC
Current (FLC))
Reset Mode Automatic or manual
Overload Reset Level 1…100% TCU
Overvoltage Category III
Power Supply NEC Class 2
Rated Operating Voltage 24V DC (+10%, -20%)
Overvoltage Protection Reverse-polarity protected
Voltage 19.2…26.4V DC
Nominal Current 150 mA
Power 3.6 W
Unswitched Power Supply
Input Current (each) 50 mA
Requirements
Maximum Current 450 mA
Maximum Power 14.4 W
Peak Inrush‡ <5 A for 35 ms
Voltage 19.2…26.4V DC
Nominal Current 125 mA
Control Circuit
Power 3W
(External Source) Switched Power Supply
Output Current (each) 500 mA
Requirements
Maximum Current 1.625 A
Maximum Power 42 W
Peak Inrush‡ <5 A for 35 ms
Voltage 19.2…26.4V DC
Nominal Current 275 mA
Power 6.6 W
Switched and Unswitched Number of Inputs (x 50 mA) user defined
Power Supply Requirements Number of Outputs (x 500 mA) user defined
Maximum Current 275 mA + user defined
Maximum Power 6.6 W + (24V DC x user defined), (60 W max.)
Peak Inrush‡ <10 A for 35 ms
Control Circuit
An internal 50 W power supply sources 24V DC for input, outputs, and logic control.
(Internal Source)
Cat. No. Sym. Amps RMS Circuit Breaker Fuse
CC, J, or T fuse
290/1_-*-G1 (or G3) 10 kA @ 480Y/277
Short Circuit Current Rating (maximum 45 A)
(SCCR) When used with Allen-Bradley
290/1_-*-G1 (or G3) 5 kA @ 480Y/277 UL Class fuse (maximum 45 A)
Cat. No. 140U-D6D3-C30
CC, J, or T fuse
290/1_-*G2 10 kA @ 480Y/277
(maximum 40 A)
Type 1
Short Circuit Coordination
Size per NFPA 70 (NEC) or NFPA 79 for Group Motor Applications
I/O is configurable to either input or output.
‡ Assumes zero wire resistance. Wire impedance will reduce current inrush.
Environmental Ratings
Operating Temperature Range -20…+50 °C (-4…+122 °F)
Storage and Transportation
–25...+85 °C (–13…+185 °F)
Temperature Range
Altitude 2000 m
Humidity 5…95% (non-condensing)
Pollution Degree 3
Enclosure Ratings IP66/UL Type 4/12♦
Approximate Shipping Weight 4.6 kg (10 lb)
♦ IP66/UL Type 4 is available with gland options G1-3. IP66/UL Type 4/12 available with G1 and G3 gland option.
Mechanical Ratings
Operational 30 G, exceeds IEC 60947-1
Resistance to Shock
Non-Operational 50 G, exceeds IEC 60947-1
Operational 2.5 G, tested to MIL-STD-810G, exceeds IEC 60947-1
Resistance to Vibration
Non-Operational 5 G, tested to MIL-STD-810G, exceeds IEC 60947-1
Disconnect Lock Out Maximum of 3/8 in. (9.5 mm) diameter lock shackle or hasp
Disconnect LOTO Locks Up to 2 locks or hasps are supported
Disconnect Mechanical Life 200 000 operations
Contactor Utilization Category
AC-1, AC-3, AC-4 (refer to Life Load Curves)
(IEC)
Contactor Opening Delay 8…12 ms
Contactor Closing Delay 18…40 ms
Minimum Off Time 200 ms
Contactor Mechanical Life 15 million operations
Power Terminals Motor Terminals Control Terminals PE/Ground
(2) #18…#10 AWG #18…#10 AWG (2) #18…#10 AWG (2) #16…#10 AWG
Wire Size
(0.8…5.2 mm2) per terminal (0.8…5.2 mm2) per terminal (0.8…5.2 mm2) per terminal (1.3…5.2 mm2) per terminal
Wire Type Multi-strand/solid copper wire
Tightening Torque 10.6 ± 2 lb•in (1.2 ± 0.2 N•m ) 18 ± 2 lb•in (2 ± 0.2 N•m )
Wire Strip Length 0.35 ± 0.01 in. (9 ± 2 mm)
Power Rating 600V AC/25 A 600V AC/10 A 600V AC/10 A —
When two wires are used in a terminal block, both wires must be the same wire AWG.
Communication Ratings
Rated Insulation Voltage 250V
Operating Dielectric Withstand UL/NEMA: 1500V AC, IEC: 2000V AC
DeviceNet Supply Voltage Rating Range 11…25V DC, 24V DC nominal
DeviceNet Input Current 50 mA @ 24V DC
DeviceNet Input Current Surge 500 mA peak inrush
Baud Rates 125, 250, 500 kbps
500 m (1630 ft) @ 125 kbps
Distance Maximum 200 m (656 ft) @ 250 kbps
100 m (328 ft) @ 500 kbps
Auto-Baud Rate Identification Yes
Class 10
Class 15
Approximate Trip Time [s]
Hot
Cold
Class 20
Approximate Trip Time [s]
Hot
Cold
10
Contact Life (millions of operations)
100-K09
(Used with ArmorStart LT)
0.1
0.01
1 10 100
Rated Current Ie AC-3 [A]
10
(Used with ArmorStart LT)
100-K09
Contact Life (millions of operations)
0.1
0.01
0.1 1 10
Rated Current Ie AC-4 [A]
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to
change.
Front View
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to
change.
Line Control
Motor
Line
Line
Motor Control
Motor
Source Brake
a d f
Bulletin Number Output Current Gland Plate Options (Power and Motor)
Code Description Code Description Code Description
294 VFD Starter D1P5 1.5 A (0.37 kW), 0.5 Hp G1 Conduit entry
D2P5 2.5 A (0.75 kW), 1.0 Hp G2 ArmorConnect
D4P2 3.6 A (1.5 kW), 2.0 Hp G3♣ Gland kits
b
Communications
Code Description e
E EtherNet/IP Control Voltage g
D DeviceNet Code Description Option 1
Z External 24V DC control power Code Description
P Internal power supply Hand/Off/Auto selector keypad with Jog
3
c function
Enclosure Type
Code Description
F
h
IP66/UL Type 4/12
Option 2
Code Description
SB Source brake
blank§ Factory option
IP66/UL Type 4 is available with all gland options. UL Type 4/12 is available with G1 and G3 gland option.
♣ See the Accessories section for special gland configurations for daisy chaining.
§ Leave blank unless there is a customer-specific option defined by the factory.
♣ If required, replace the G1 suffix code with G3 and refer to the User-Installed Options for kit selection.
On/Off Switch
Wiring Access
Lockout/Tagout Provision
HOA Keypad (optional)
Electrical Ratings
Application Three-phase
Number of Poles 3
Input Power Terminals L1, L2, L3
Motor Power Terminals T1, T2, T3
Power Circuit PE (Earth Ground) Terminal 4 PE terminals
Maximum Rated Operating Voltage 400Y/230…480Y/277 (-15%, +10%)
Rated Impulsed Voltage (Uimp) 4 kV
Dielectric Withstand UL: 1960V AC, IEC: 2500V AC
Operating Frequency 50/60 Hz (±10%)
Electrical Ratings
Power Supply NEC Class 2
Rated Operating Voltage 24V DC (+10%, -20%)
Overvoltage Protection Reverse-polarity protected
Voltage 19.2…26.4V DC
Nominal Current 150 mA
Power 3.6 W
Unswitched Power Supply
Input Current (each) 50 mA
Requirements
Maximum Current 450 mA
Maximum Power 14.4 W
Peak Inrush‡ <5 A for 35 ms
Voltage 19.2…26.4V DC
Nominal Current 125 mA
Control Circuit
Power 3W
(External Source) Switched Power Supply
Output Current (each) 500 mA
Requirements
Maximum Current 1.625 A
Maximum Power 42 W
Peak Inrush‡ <5 A for 35 ms
Voltage 19.2…26.4V DC
Nominal Current 275 mA
Power 6.6 W
Switched and Unswitched Number of Inputs (x 50 mA) user defined
Power Supply Requirements Number of Outputs (x 500 mA) user defined
Maximum Current 275 mA + user defined
Maximum Power 6.6 W + (24 x user defined), (60 W max.)
Peak Inrush‡ <10 A for 35 ms
Control Circuit
An internal 50 W power supply sources 24V DC for input, outputs, and logic control.
(Internal Source)
Cat. No. Sym. Amps RMS Circuit Breaker Fuse
CC, J, or T fuse
294_-*-G1 or (-G3) 10 kA @ 480Y/277
(maximum 45 A)
UL Class fuse
294_-*-G1 or (-G3) 5 kA @ 480Y/277
(maximum 45 A)
Short Circuit Current Rating
(SCCR) When used with Allen-Bradley CC, J, or T fuse
294_-*-G1-SB 10 kA @ 480Y/277
Cat. No. 140U-D6D3-C30 (maximum 40 A)
UL Class fuse
294_-*-G1-SB 5 kA @ 480Y/277
(maximum 40 A)
CC, J, or T fuse
294_-*-G2* 10 kA @ 480Y/277
(maximum 40 A)
Type 1
Short Circuit Coordination
Size per NFPA 70 (NEC) or NFPA 79 for Group Motor Applications
I/O is configurable to either input or output.
‡ Assumes zero wire resistance. Wire impedance will reduce current inrush.
Environmental Ratings
-20…+40 °C (-4…+104 °F)
Operating Temperature Range 50 °C (122 °F) without derating, when properly rated line reactors are installed
in branch circuit.
Storage and Transportation
–25...+85 °C (–13…+185 °F)
Temperature Range
Altitude 1000 m
Humidity 5…95% (non-condensing)
Pollution Degree 3
Enclosure Ratings IP66/UL Type 4/12♦
Approximate Shipping Weight 7.3 kg (16 lb)
♦ IP66/UL Type 4 is available with gland options G1-3. IP66/UL Type 4/12 available with G1 and G3 gland option.
Mechanical Ratings
Operational 30 G (exceeds IEC 61800-5-1)
Resistance to Shock
Non-Operational 50 G (exceeds IEC 61800-5-1)
Operational 2.5 G, MIL-STD-810G, (exceeds IEC 61800-5-1)
Resistance to Vibration
Non-Operational 5 G, MIL-STD-810G, (exceeds IEC 61800-5-1)
Disconnect Lock Out Maximum of 3/8 in. (9.5 mm) diameter lock shackle or hasp
Disconnect LOTO Locks Up to 2 locks or hasps are supported
Disconnect Mechanical
200 000 operations
Life
Power Terminals Motor Terminals Control Terminals PE/Ground Source Brake
(2) #18…#10 AWG #18…#10 AWG (2) #18…#10 AWG (2) #16…#10 AWG #16 …#10 AWG
Wire Size (0.8…5.2 mm2) per (0.8…5.2 mm2) per (0.8…5.2 mm2) per (1.3…5.2 mm2) per (1.0…4.0 mm2) per
terminal terminal terminal terminal terminal
Wire Type Multi-strand/solid copper wire
18 ± 2 lb•in 4.8 ± 2 lb•in
Tightening Torque 10.6 ± 2 lb•in (1.2 ± 0.2 N•m )
(2 ± 0.2 N•m ) (0.5 ± 0.2 N•m )
Wire Strip Length 0.35 ± 0.01 in. (9 ± 2 mm)
Power Rating 600V AC/25 A 600V AC/10 A 600V AC/10 A — 600V AC/10 A
When two wires are used in a terminal block, both wires must be the same wire AWG.
Communication Ratings
Rated Insulation Voltage 250V
Operating Dielectric Withstand UL/NEMA: 1500V AC, IEC: 2000V AC
DeviceNet Supply Voltage Rating Range 11…25V DC, 24V DC nominal
DeviceNet Input Current 50 mA @ 24V DC
DeviceNet Input Current Surge 500 mA peak inrush
Baud Rates 125, 250, 500 kbps
500 m (1630 ft) @ 125 kbps
Distance Maximum 200 m (656 ft) @ 250 kbps
100 m (328 ft) @ 500 kbps
Auto-Baud Rate Identification Yes
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to
change.
Front View
Important: For maximum product life and maximum heat sink efficiency,
mount the device vertically as shown.
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to
change.
Line
Motor
Line
Line Control
Control
Motor
Motor
Source Brake
Dia. 25.5 mm
0.75 in. Dia. 20.5 mm
290-G3-A3
Source Brake (19.05 mm)
No Internal Power Supply
Dia. 25.5 mm
Dia. 20.5 mm
1.00 in. 290-G3-A4
Internal Power Supply
(25.4 mm)
No Source Brake
0.75 in.
(19.05 mm)
Dia. 25.5 mm
Dia. 20.5 mm
1.00 in. 290-G3-A5
Internal Power Supply (25.4 mm)
and Source Brake
0.75 in.
(19.05 mm)
45°
290-G3-A1
Gland Plate Clearances
Modifications are not permitted in the keepout region. Fitting(s) should be oriented 66.1 mm 80.7 mm
User Modified so that they do not interfere with the enclosure when the gland plate is installed.
Torque the gland mounting screws to 12…14 in•lb (1.3…1.6 N•m).
Power Connections
ArmorStart LT utilizes an M22 male receptacle for power inputs and an M22 female receptacle for motor or motor brake output.
Pin 1: T1 (black)
Pin 2: T2 (white) Pin 1: Ground (green/yellow)
Pin 3: T3 (red) Pin 2: B1 (black)
Pin 4: Ground (green/yellow) Pin 3: B2 (white)
L1 A1
L2 L3 A2 A3
T1
T2 T3
PE
B1 B2
Single External Power Supply for Switched and Unswitched Control Power Configuration
ArmorStart LT
L1 L2 L3
Switched Control Power
Off
Unswitched Control Power
*
Disconnect
L +
24VDC
N -
Class 2
External
24VDC Power
Supply
Visit our website: www.ab.com/catalogs
30 Publication 290-SG001C-EN-P
Bulletin 290/291, 294
ArmorStart LT Distributed Motor Controllers
Typical Wiring Diagrams
Two External Power Supplies for Switched and Unswitched Control Power Configuration
ArmorStart LT
L1 L2 L3
Switched Control Power
Off
Unswitched Control Power
*
Disconnect
T1 T2 T3
Class 2 L +
External Switched
24VDC
24VDC Power Supply
N -
Class 2
L +
External Unswitched 24VDC
24VDC Power Supply N -
Internal Power Supply for Switched and Unswitched Control Power Configuration
ArmorStart LT
Internal Power
L1 L2 L3 Supply
Off
Disconnect
*
*
T1 T2 T3
DeviceNet Media ∆
Cat. No.
Description Length [m (ft)] Sealed
1 (3.3) 1485P-P1E4-B1-N5
2 (6.5) 1485P-P1E4-B2-N5
KwikLink pigtail drops are Insulation Displacement 3 (9.8) 1485P-P1E4-B3-N5
Connector (IDC) with integral Class 1 round cables
for interfacing devices or power supplies to flat
cable
6 (19.8) 1485P-P1E4-B6-N5
Transition Cable
Sensor Media∆
EtherNet/IP Communications
ArmorStart
I/O
Description Connection Pin Count Connector Cat. No.
Straight Female
889D-F4ACDM-♦
Straight Male
DC Micro
Input/Output 4-pin
Patchcord Straight Female
889D-F4ACDE-♦
Right Angle Male
♦ Replace symbol with desired length in meters (Example: 889D-F4ACDM-1 for a 1 m cable). Standard cable lengths: 1, 2, 5, and 10 m.
∆ See On-Machine Connectivity Catalog for complete cable selection information.
Sealing Caps
Cat. No.
Plastic I/O Sealing Cap — M12 (1 each)♣ 1485A-M12
Motor and Source Brake Connector — Aluminum Sealing Cap (1 each) 1485A-C1
Plastic Node Address Sealing Cap (10 each)♣ 889A-PMCAP
♣ To achieve IP66/UL Type 4 rating, sealing caps must be installed on all unused connections.
Locking Tag
Padlock attachment to the lockable handles 140M-C-M3
Up to three padlocks 4…8 mm (5/16 in.) Ø shackle
Recommendation:
The cable connector selected must provide good 360° contact and low transfer impedance ®
SKINTOP MS-SC/MS-SCL cable
from the shield or armor of the cable to the conduit entry plate at both the motor and the
grounding connectors or NPT/PG
drive or drive cabinet for electrical bonding.
adapters from LAPPUSA
Example of Cordset
Straight Male
Pin Count Assembly Rating‡ Certifications Cat. No.
16 AWG, 600V, 10 A§ UL Listed UL 2237 (File No. 280-PWRM22G-M
4-pin
14 AWG, 600V, 15 A E318496, Guide PVVA) 280-PWRM24G-M
Example of Patchcord
Straight Female
Straight Male
Pin Count Assembly Rating‡ Certifications Cat. No.
16 AWG, 600V, 10 A§ UL Listed UL 2237 (File No. 280-PWRM22A-M
4-pin
14 AWG, 600V, 15 A E318496, Guide PVVA) 280-PWRM24A-M
Male Receptacle (motor side)
16 AWG, 600V, 10 A§ UL Listed UL 2237 (File No. 280-M22M-M1
4-pin
14 AWG, 600V, 15 A E318496, Guide PVVA) 280-M24M-M1
‡ Refer to the Three-Phase Power Media selection guide for details and additional selections.
§ ArmorStart LT is UL Listed for use with 14 AWG power cable. Refer to your local electrical code(s) when applying 16 AWG power cable in a motor circuit.
♦ Required to meet CE compliance for radiated electromagnetic emissions.
Replace symbol with code from table below that represents length desired.
Example of Cordset
Straight Male
Pin Count Assembly Rating Certifications Cat. No.
16 AWG, 600V, 10 A§ UL 2237, UL Listed (File No. 285-BRC22-M
3-pin
14 AWG, 600V, 15 A E318496, Guide PVVA) 285-BRC24-M
Example of Patchcord
Straight Female
Straight Male
Pin Count Assembly Rating Certifications Cat. No.
16 AWG, 600V, 10 A§ UL 2237, UL Listed (File No. 285-BRC22-MD
3-pin
14 AWG, 600V, 15 A E318496, Guide PVVA) 285-BRC24-MD
Male Receptacle (motor side)
UL 2237, UL Listed (File No.
3-pin 14 AWG, 600V, 15 A 285-M24M-M05
E318496, Guide PVVA)
Three-Phase Power Field-Installable Receptacles — For 25, 15, and 10 A Cordsets and Patchcords
Female
Pin Count Assembly Rating‡ Certifications Cat. No.
16 AWG, 600V, 10 A§ UL Listed UL 2237 (File No. 280-FAM22F
4-pin
10 AWG, 600V, 25 A♠ E318496, Guide PVVA) 280-FAM35F
Three-Phase Power Three-Phase Power Three-Phase Power Three-Phase Power Three-Phase Power
Trunk Cable Drop Cable Tees and Reducers Receptacles Accessories
Tee - Connects to a Female receptacles are
single drop line to trunk a panel mount
Sealing Caps offered in
with M35 connectors connector with flying
Cordset - Cable with Cordset - Cable with versions to interface
Reducing Tee - leads
integral female or male integral female or male with female or male
Connects to a single Male receptacles are a
connector on one end connector on one end connectors
Description M22 drop line to trunk motor juction box
PatchCord - Cable with PatchCord - Cable with Locking Clips clamshell
M35 connector mounted connector with
integral female or male integral female or male design clips over three
Reducer - Connects flying leads
connector on each end connector on each end power phase connector
from M35 male Field-installable
to limit customer access
connector to M22 receptacle for custom
female connector length cable
Rated for Motor Branch Rated for Motor Branch
Rated for Motor Branch
Circuits Circuits
Circuits
- Meets UL 2237 for - Meets UL 2237 for Rated for Motor Branch
- Meets UL 2237 for
Industrial Machinery Industrial Machinery Circuits
Industrial Machinery
- 65 kA High fault - 65 kA High fault - Meets UL 2237 for
- 65 kA High fault
rating (SCCR) rating (SCCR) Industrial Machinery Sealing Caps - Available
rating (SCCR)
- Rated for wash - Rated for wash - 65 kA High fault in M35 and M22 styles
- Rated for wash
Features down environments down environments rating (SCCR) Locking Clips -
down environments
Straight or right angle Straight or right angle - Rated for wash Designed for M35 and
Male and female
connectors connectors down environments M22 connectors
configurations
4-pin connector type 4-pin connector type Trunk Tee, Reducing Tee
4-pin connector type
Cable rating: Cable rating: TC- and Reducer
1/2 in. NPT
TC-ER/STOOW ER/STOOW 4-pin connector type
Available in 1 meter
Multiple standard Multiple standard
length
lengths lengths
Rated Voltage 600V 600V 600V 600V ⎯
M22 Female:
Trunk Tee: 33.45 mm x 25.45 mm
Straight: Straight: 108 mm x 73.6 mm M22 Male:
Connector Body 88.9 mm x 38.6 mm 56. mm x 25.4 mm Reducing Tee: 28.04 mm x 25.45 mm
Dimensions Right Angle: Right Angle: 108 mm x 65.5 mm M35 Female: ⎯
75.5 mm x 74 mm 44.9 mm x 40.4 mm Reducer: 71.12 mm x 38.10 mm
112.5 mm x 38.1 mm M35 Male:
63.50 mm x 38.10 mm
Product Selection Page 43 Page 44 Page 45 Page 47, 49 Page 55
Control Power Control Power Control Power Control Power Control Power
Cordsets & Patchcords T-ports Receptacles Shorting Plugs Accessories
Integral connector with
Cable with integral Cable with single male Sealing caps, mounting
Panel mount connector leads shorted for
Description connector on either one or connector attached to nuts, and sealing
with flying leads specific application
both ends two female connectors washers
requirements
6-pin/5-used configuration 6-pin/5-used
6-pin/5-used
Male and female configuration 6-pin/5-used
configuration
Straight or right angle Male and female configuration Rugged durable
Compact design
versions 16 AWG conductors Male construction
Features Color-coded E-stop in
16 AWG conductors, cable 1/2 NPT mounting Multiple versions color Designed to mate with
and E-stop out
dual rated UL TC/Open threads coded for simple control power media
configurations
Wiring and STOOW Multiple standard identification
Multiple standard lengths lengths
Rated Voltage 600V 600V 600V 600V ⎯
Straight:
Connector Body 56 x 25 mm (2.2 x 1 in.)
72 x 64 mm (2.8 x 2.5 in.) 30 x 25 mm (1.2 x 1 in.) 56 x 25 mm (2.2 x 1 in.) ⎯
Dimensions Right Angle:
40 x 45 mm (1.6 x 1.8 in.)
Product Selection Page 50 Page 51 Page 52 Page 53 Page 55
Note: Refer to your local electrical code for proper application and protection of long length
power cable to minimize physical damage and appropriate short-circuit or ground-fault
protection for the assembly. See application note 290-AP001 for additional information.
RESET
OFF
Bulletin 800F
Emergency Stop
Stop
Pushbutton
1. Three-Phase Power Trunk - Patchcord cable with integral female or male connector on each end (Example Cat. No.:
280-PWR35A-M*)
2. Three-Phase Drop Cable - PatchCord cable with integral female or male connector on each end (Example Cat. No.:
280-PWR22A-M*)
3. Three-Phase Power Tees and Reducer - Tee connects to a single drop line to trunk with quick change connectors
(Cat. No.: 280-T35)
Reducing Tee connects to a single drop line (Mini) to trunk (Quick change) connector (Cat. No.: 280-RT35)
Reducer connects from quick change male connector to mini female connector(Cat. No.: 280-RA35)
4. Three-Phase Power Receptacles - Female receptacles are a panel mount connector with flying leads (Cat. No.: 280-
M35F-M1)
RESET
OFF
Bulletin 800F
Stop
Emergency Stop
Pushbutton
6. Control Power Media Patchcords - PatchCord cable with integral female or male connector on each end (Example
Cat. No.: 889N-F65GFNM-*)
7. Control Power Tees - The E-stop In Tee (Cat. No.: 898N-653ST-NKF) is used to connect to the Bulletin 800F On-
Machine E-Stop station using a control power media patchcord. The E-stop Out tee (Cat. No.: 898N-653ES-NKF) is
used with cordset or patchcord to connect to the ArmorStart Distributed Motor Controller.
8. Control Power Receptacles - Female receptacles are a panel mount connector with flying leads (Cat. No.: 888N-
D65AF1-*)
RESET
OFF
Bulletin 800F
Emergency
Stop Stop
Pushbutton
5
1. DeviceNet Trunk Cable - Patchcord trunk cable with integral female or male connector on each end
(example 1485C-P*N5-M5)
2. DeviceNet Mini- T-Port Tap - T-ports are used for connecting drops to the trunk line (example 1485P-P1N5-MN5KM)
3. DeviceNet Drop Cable - Drop cables and patch cords are used to connect devices to the network
(example 1485G-P*M5-Z5)
4. DeviceNet Receptacle - Recepatcles are used when connections present but required (example 1485A–CXN5–M5)
5. DeviceNet Terminator - Properly designed DeviceNet networks require terminating resistors (example 1485A–T1N5)
Note: See the On-Machine Connectivity catalog for specific DeviceNet media components.
Bulletin Bulletin
Note: See the On-Machine Connectivity catalog for specific EtherNet media components.
Product Selection
Cordsets ‡
Cat. No.
Pin Count Assembly Rating Straight Female Right-Angle Female Straight Male Right-Angle Male
4-pin 10 AWG, 600V, 25 A 280-PWRM35E-M 280-PWRM35F-M 280-PWRM35G-M 280-PWRM35H-M
Patchcords ‡
Cat. No.
Straight Female Right-Angle Female Straight Female Right-Angle Female
Pin Count Assembly Rating Straight Male Straight Male Right-Angle Male Right-Angle Male
4-pin 10 AWG, 600V, 25 A 280-PWRM35A-M 280-PWRM35B-M 280-PWRM35C-M 280-PWRM35D-M
‡ Stainless steel version may be ordered by adding S to the cat. no. (Example: Cat. No. 280S-PWRM35A-M*)
1 Replace symbol with code from table below that represents length desired.
Feet 1.62 3.3 4.9 6.5 8.1 9.8 13.1 19.7 26.2 32.8 39.4 45.9
Meters 0.5 1 1.5 2 2.5 3 4 6 8 10 12 14
Code 05 1 015 2 025 3 4 6 8 10 12 14
74.7
38.6 (2.94)
(1.52)
Patchcords ‡
Cat. No.
Straight Female Right-Angle Female Straight Female Right-Angle Female
Pin Count Assembly Rating Straight Male Straight Male Right-Angle Male Right-Angle Male
4-pin 16 AWG, 600V, 10 A 280-PWRM22A-M 280-PWRM22B-M 280-PWRM22C-M 280-PWRM22D-M
4-pin 14 AWG, 600V, 15 A 280-PWRM24A-M 280-PWRM24B-M 280-PWRM24C-M 280-PWRM24D-M
‡ Stainless steel version may be ordered by adding S to the cat. no. (Example: Cat. No. 280S-PWRM22A-M*)
1 Replace symbol with code from table below that represents length desired.
Feet 1.62 3.3 4.9 6.5 8.1 9.8 13.1 19.7 26.2 32.8 39.4 45.9
Meters 0.5 1 1.5 2 2.5 3 4 6 8 10 12 14
Code 05 1 015 2 025 3 4 6 8 10 12 14
25.4 25.4
(1.00) (1.00)
Product Selection
Tees and Reducing Adapters ‡
Description Assembly Rating Color Code Cat. No.
M35, 3-Phase Power Tee, 4-pole 25 A A 280-T35
M35, 3-Phase Power Tee Reducing drop M22, 4-pole Trunk 25 A/Drop 15 A B 280-RT35
M35, 3-Phase Reducing Adapter, 4-pole 15 A C 280-RA35
‡ Stainless steel version may be ordered by adding S to the cat. no. (Example: Cat. No. 280S-T35)
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes and are subject to change.
Reducer
112.5 M35 M22
(4.43)
38.1 MALE FEMALE
(1.50)
#1 BLACK #1
#2 #2
#3 RED #3
#4 GREEN/YELLOW #4
WHITE
25.4
(1.00)
WIRING DIAGRAM
Power Tee
108.0
#1 - BLACK (4.25) #3 RED
#2 - GREEN/YELLOW KEYWAY
FEMALE
#1 BLACK
MALE
EXTENDED PIN 2
GREEN/YELLOW LEAD
#2 GREEN/YELLOW
#4 WHITE
36.8
#2 GREEN/YELLOW
(1.45)
73.7 (2.90)
#1 BLACK
#4 WHITE
#4 - WHITE
#3 RED
#3 - RED
4 mm (#8) or 5 mm (#10)
MOUNTING SCREW
FEMALE
#4 - GREEN/YELLOW
108.0
#3 - RED KEYWAY
(4.25) #3 RED
FEMALE
#1 BLACK
MALE
EXTENDED PIN 2 #2 GREEN/YELLOW
GREEN/YELLOW LEAD
#4 WHITE
36.8
#4 GREEN/YELLOW
(1.45)
#2 - WHITE #1 - BLACK
#1 BLACK
#2 WHITE
65.3 (2.57)
#3 RED
4 mm (#8) or 5 mm (#10)
MOUNTING SCREW
FEMALE
WIRING DIAGRAM
19.0
(0.75)
38.0
(1.50)
Product Selection
Receptacles ‡
Cat. No.
Pin Count Assembly Rating Color Code Female Male
16 AWG, 600V, 10 A A 280-M22F-M 280-M22M-M
4-pin 14 AWG, 600V, 15 A A 280-M24F-M 280-M24M-M
10 AWG, 600V, 25 A B 280-M35F-M 280-M35M-M
‡ Stainless steel version may be ordered by adding S to the cat. no. (Example: Cat. No. 280S-M22F-M1)
Replace symbol with length in meters: 1 for 1 m or 3 for 3 m.
Accessories
Mounting Nuts and Flat Seals
Description Pkg. Quantity Cat. No.
Mounting nuts for 1/2 in.-14 NPT threaded receptacles 889A-U1NUT-10
10
Flat sealing washers for 1/2 in.-14 NPT threaded receptacles 889A-U1FSL-10
Specifications
Mechanical
Insert Black PVC
Receptacle Shell Material Black anodized aluminum (female) and zinc diecast, black E-coat (male)
Electrical
Contacts Copper alloy with gold over nickel plating (Trunk), brass with gold over nickel plating (Drop)
Cable Rating 600V AC/DC
4-pin ⎯ 16 AWG, 600V @ 10 A
Assembly Rating 4-pin ⎯ 14 AWG, 600V @ 15 A
4-pin ⎯ 10 AWG, 600V @ 25 A
4-pin — 10 AWG
Fusing: Suitable for use on a circuit capable of delivering not more than 65 000 RMS symmetrical amperes at 600V AC
maximum when protected by CC, J, and T class fuses
Circuit Breaker: Suitable for use on a circuit capable of delivering not more than 65 000 RMS symmetrical amperes at
480V AC maximum when protected by Bul. 140U-H frame circuit breaker, not rated more than 480V, 100 A and a maximum
Short Circuit Current Rating interrupting of 65 000 RMS symmetrical amperes.
(SCCR) 4-pin — 16 or 14 AWG
Fusing: Suitable for use on a circuit capable of delivering not more than 65 000 RMS symmetrical amperes at 600V AC
maximum when protected by CC, J, and T class fuses, rated 40 A non-time delay or 20 A time delay.
Circuit Breaker: Suitable for use on a circuit capable of delivering not more than 45 000 RMS symmetrical amperes at
480Y/277V AC maximum when protected by Cat. No. 140U-D6D3-C30 circuit breaker, not rated more than 480Y/277V, 30 A,
having an interrupting rating not less than 45 000 RMS symmetrical amperes, 480Y/277V maximum.
Environmental
Enclosure Rating IP67, NEMA 4 & 6P; 1200 psi washdown
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes and are subject to change.
18.49
(0.728)
280-M22F-M1
45.26
(1.782)
280-M35F-M1
3.81
(0.150)
12.09 (0.476)
7.32 1000…3000
(0.288) (39.37…118.11)
15.95
(0.628)
7.62 +/-2.54 11.89 (0.468)
(0.30 +/- 0.10)
6.35 (0.25)
1000…3000
280-M22M-M1 (39.37…118.11)
51.61
(2.032)
280-M35M-M1
28.04
(1.104)
4.75 1000…3000
(0.187) (39.37…118.11) 6.35 (0.25)
11.89 (0.468)
1000…3000
(39.37…118.11)
Product Selection
Receptacles
Cat. No.
Pin Count Assembly Rating Certifications Cable Diameter Female Male
16 AWG, 600V, 10 A
0.28…0.47 in. 280-FAM22F 280-FAM22M
4-pin 14 AWG, 600V, 15 A UL Listed UL 2237 (File No. E318496, Guide PVVA)
10 AWG, 600V, 25 A♦ 0.48…0.81 in. 280-FAM35F 280-FAM35M
♦ For 15 A cable (Cat. No. 280-PWRM24*), use Cat. No. 280-FAM35*
Specifications
Mechanical
Insert Black PVC
Receptacle Shell Material Black anodized aluminum (female) and zinc diecast, black E-coat (male)
Electrical
Contacts Copper alloy with gold over nickel plating (Trunk), brass with gold over nickel plating (Drop)
Cable Rating 600V AC/DC: 14 AWG Listed TC, 16 AWG Listed TC-ER/STOOW, 10 AWG Listed TC-ER/STOOW
4-pin ⎯ 16 AWG, 600V @ 10 A
Note: When applied with 14 AWG or larger wire, this is
Assembly Rating 4-pin ⎯ 14 AWG, 600V @ 15 A
suitable for use on Motor Branch Circuits, per NFPA 79.
4-pin ⎯ 10 AWG, 600V @ 25 A
4-pin — 10 AWG
Fusing: Suitable for use on a circuit capable of delivering not more than 65 000 RMS symmetrical amperes at 600V AC
maximum when protected by CC, J, and T class fuses
Circuit Breaker: Suitable for use on a circuit capable of delivering not more than 65 000 RMS symmetrical amperes at
480V AC maximum when protected by Bul. 140U-H frame circuit breaker, not rated more than 480V, 100 A and a maximum
Short Circuit Current Rating interrupting of 65 000 RMS symmetrical amperes.
(SCCR) 4-pin — 16 and 14 AWG
Fusing: Suitable for use on a circuit capable of delivering not more than 65 000 RMS symmetrical amperes at 600V AC
maximum when protected by CC, J, and T class fuses, rated 40 A non-time delay or 20 A time delay.
Circuit Breaker: Suitable for use on a circuit capable of delivering not more than 45 000 RMS symmetrical amperes at
480V AC maximum when protected by Cat. No. 140U-D6D3-C30 circuit breaker, not rated more than 480Y/277V, 30 A, having
an interrupting rating not less than 45 000 RMS symmetrical amperes, 480Y/277V maximum.
Environmental
Enclosure Rating IP67, NEMA 4 & 6P; 1200 psi washdown
3.63 in.
7/8-16 UN-2B
Ø 1.10 in.
Ø 1.10 in.
1-3/8-16 UN-2A
4.40 in.
Ø 1.52 in.
1-3/8-16 UN-2A
4.40 in.
Ø 1.52 in.
Bulletin 889N ⎯ Control Power Trunk and Drop Cables Table of Contents
6-pin/5-used configuration to prevent mis-wiring with network Accessories.................. 55
connectors
One-piece molded design
16 AWG exposed run (TC-ER) rated cable
Product Selection
Cordsets
Cat. No.
Pin Count Assembly Rating Straight Female Right-Angle Female Straight Male Right-Angle Male
6-pin/5 used 16 AWG 600V, 10 A 889N-F65GF-1 889N-R65GF-1 889N-M65GF-1 889N-E65GF-1
1 Replace symbol with code from the table below that represents the desired length:
Patchcords
Cat. No.
Straight Female Right-Angle Female Straight Female Right-Angle Female
Pin Count Assembly Rating Straight Male Straight Male Right-Angle Male Right-Angle Male
6-pin/5 used 16 AWG 600V, 10 A 889N-F65GFNM- 889N-R65GFNM- 889N-F65GFNE- 889N-R65GFNE-
Replace symbol with code from the table below that represents the desired length:
Approximate Dimensions
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes and are subject to change.
39.6 (1.56) 56.1 (2.21) 40.6 (1.6)
25.4
25.4 (1.0) dia. 25.4
(1.0) dia. 32.5 32.5 (1.0) dia.
(1.28) (1.28) Example of Cordset
7/8 in.
Female Straight 7/8 in.
16 UN-2B 16 UN-2B
59.4 (2.34)
Product Selection
T-Ports
Configuration Assembly Rating Overmold Color Wiring Diagram Cat. No.
1 1
2 2
3 3
E-stop out 600V, 10 A Red 5 5 898N-653ES-NKF
6 6
1 2 3 5 6
1 1
2 2
3 3
E-stop in 600V, 10 A Black 5 5 898N-653ST-NKF
6 6
1 2 3 5 6
ArmorStart
600V, 8 A Black 898N-543ES-NKF
auxiliary
Product Selection
Receptacles
Cat. No.
Pin Count Assembly Rating Female Male
6-pin/5 used 16 AWG 600V, 10 A 888N-D65AF1-1 888N-M65AF1-1
1 Replace symbol with length in meters (0.3 or 1 standard)
Approximate Dimensions
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes and are subject to change.
28.1 (1.11)
177.8 (7.0)
12.2 (0.48) 3.81 (0.15)
3.81 (0.15)
1/2 in. 14 NPT Thread 7.32 (0.28)
21.3 (0.84)
25.07 Dia.
(0.98)
Dia. Epoxy Filled
4.78 (0.18) 11.1
7/8 in. 16 UNS-2A 7/8 in. 16 UNS-2A (0.44)
thread 152.4/203.2 (6.0/8.0) thread 30.5 (1.2) 1/2 in. 14 NPT
Product Selection
Shorting Plugs
Configuration Assembly Rating Overmold Color Wiring Diagram Cat. No.
1.
2. N/C
3. N/C
E-stop out Red Blank 889A-M65SP61
4.
5. N/C
6.
600V, 10 A
1. N/C
2. N/C
3. N/C
E-stop in Black 889A-M65SP65
4. Blank
5.
6.
Approximate Dimensions
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes and are subject to change.
25.4
(1.0)
Dia.
50.1 (1.97)
Locking Clips
Sealing Caps
Enclosure Type
Connector Style Material Rating Thread Configuration Dimensions Cat. No.
7/8 in. -16 UN
2 A Threads
Gasket
Control Power (M22)
7/8 in. -16 UN
2 B Threads
Gasket
Internal, female 889A-NCAP
Aluminum grey,
anodized
1-3/8 in. -16 UN
IP67, NEMA 4 & 6P: 2A Threads
1200 psi washdown External, male Gasket 889A-QMCAP
Enclosure Type Quick Connect Knockout Type Operator Illumination Voltage Contact Configuration Cat. No.
Plastic Twist-to-Release 800F-1YMQ4
Mini Receptacle Metric 24V AC/DC 1 N.O./1 N.C.
Metal 40 mm 800F-1MYMQ4
Customer Supplied
Pin 1 Red A3
Pin 2 Black A2 (-)
Pin 3 Green PE
Pin 4 Blank Not used
Pin 5 Blue A1 (+)
Pin 6 White Not Used E-Stop Station
8
Customer Supplied
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect
support programs. For more information, contact your local distributor or Rockwell Automation representative,
or visit http://www.rockwellautomation.com/support/.
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual.
You can contact Customer Support for initial help in getting your product up and running.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain
one) to your distributor to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document,
complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
Trademark List
Allen-Bradley, ArmorConnect, ArmorStart LT, ControlLogix, CompactLogix, PowerFlex, RSLinx, StepLogic, DeviceLogix, On-
Machine, RSNetWorx, and RSLogix 5000, are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell
Automation are property of their respective companies