Product Information: Type: RCCB 2 and 4 Poles Reference: CD / Cds / CDJ / CF / CFJ / CDC

This document provides product information for Hager Eletromar's range of RCCB (residual current circuit breakers), including their general characteristics, standards and specifications, ratings, breaking capacity, test button features, terminal information, and installation guidelines. It lists the company's address and contact details at the beginning.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
104 views4 pages

Product Information: Type: RCCB 2 and 4 Poles Reference: CD / Cds / CDJ / CF / CFJ / CDC

This document provides product information for Hager Eletromar's range of RCCB (residual current circuit breakers), including their general characteristics, standards and specifications, ratings, breaking capacity, test button features, terminal information, and installation guidelines. It lists the company's address and contact details at the beginning.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Hager Eletromar

Av. Comandante Guaranys, 525


Jacarepaguá – Rio de Janeiro - RJ
22775-610 – Brasil
Tel.: 21 3504-9500

Product Information
Type : RCCB 2 and 4 poles
Reference : CD / CDS / CDJ / CF / CFJ / CDC

General Characteristics

Standards and specifications: EN 61008-1 and IEC 61008-1

Range
Two pole (2x17.5mm) and four pole (4x17.5mm)

Rated current In
16A, 25A, 40A, 63A

Rated fault current


30mA/300mA/300mA[S]/500mA

Type
AC Class

Rated voltage Un
Two pole 230V ∼ Four pole 230/400V ∼

Rated Frequency
60Hz, neutral on the left or right
Hager Eletromar
Av. Comandante Guaranys, 525
Jacarepaguá – Rio de Janeiro - RJ
22775-610 – Brasil
Tel.: 21 3504-9500

Breaking capacity:

Rated conditional short-circuit 6kA according to EN 61008-1


current (Inc)
Rated conditional residual short- 4.5kA according to EN 61008-1
circuit current (IΔc)

Test button

Rated residual making and breaking capacity I∆m


1500A

Rated making and breaking capacity Im


1500A

Peak withstand current


Lightning : Wave 8/20 μs
A and AC type : 250A
A[S] type : 3000A
HI : 5000A

Rated impulse withstand current


Wave 1.2/50 μs
6000A

Tripping time
In <300ms which is the standard.

Mechanical characteristics(service life)

Electrical endurance in number 1000 cycles on load with In x cosϕ 0.9 (each operating cycle
of cycles consisting of a closing operation followed by an opening
operation).
500 cycles by test button / 500 cycles by fault current
Mechanical endurance in 2000 cycles
number of operations

Insulation voltage
2P 500V∼
4P 900V∼

Dielectric
2500V∼
Hager Eletromar
Av. Comandante Guaranys, 525
Jacarepaguá – Rio de Janeiro - RJ
22775-610 – Brasil
Tel.: 21 3504-9500

Power loss at In in W

Tightening torque
Recommended terminal torque
On the Top terminals: 2.8 Nm
Bi-connect terminals : 2.8 Nm
Maximum terminal torque :
On the Top terminals: 3.45 Nm
Bi-connect terminals : 3.45 Nm

Terminal depth
On the top terminals: 13.5mm
On the bottom terminals : 13.5mm

Terminal capacity
Flexible with ferrule cable: 16mm²
Rigid cable: 25mm²

Test of resistance to fire IEC 60965


For externals parts: 960°C
For all others parts: 650°C

Dimensions, weight and packaging


Hager Eletromar
Av. Comandante Guaranys, 525
Jacarepaguá – Rio de Janeiro - RJ
22775-610 – Brasil
Tel.: 21 3504-9500

Installation

Diagram connection

Type of cable :
Copper
No Usable with Aluminium cable

Sealable :
The locking kit (MZN 175) allows locking of the device toggle in the “off” position.
The Iocking kit is sealable. .

Flag indicator :
for the contact position : Red / Green
for the Earth Fault tripping :Yellow
Temperature :
Ambient temperature : -25°C to + 40°C
Storage temperature : - 55°C to + 70°C

Installation altitude :
2000 meters max

Working position :
Performances not affected if installed vertically, horizontally or flat

Tropicalisation :
All climates*
*No compatible salt works and chlorinated environment