TBA - Identifying The Fire Resistance of Clay Masonry Walls Factsheet

The document discusses determining the fire resistance level (FRL) of clay masonry walls. The FRL is measured by structural adequacy, integrity, and insulation. Structural adequacy considers how long the wall remains standing in a fire. Integrity prevents fire/heat from passing through. Insulation keeps heat below a threshold on the non-fire side. Determining FRL involves specifying wall dimensions/support and consulting charts that provide FRL values based on thickness and other factors. A worked example demonstrates looking up structural adequacy and insulation values based on wall thickness and support to determine the overall FRL.

Uploaded by

Adrian
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
51 views

TBA - Identifying The Fire Resistance of Clay Masonry Walls Factsheet

The document discusses determining the fire resistance level (FRL) of clay masonry walls. The FRL is measured by structural adequacy, integrity, and insulation. Structural adequacy considers how long the wall remains standing in a fire. Integrity prevents fire/heat from passing through. Insulation keeps heat below a threshold on the non-fire side. Determining FRL involves specifying wall dimensions/support and consulting charts that provide FRL values based on thickness and other factors. A worked example demonstrates looking up structural adequacy and insulation values based on wall thickness and support to determine the overall FRL.

Uploaded by

Adrian
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Identifying the Fire Resistance

of Clay Masonry Walls


The National Construction Code requires walls to meet certain fire
resistance levels (FRL), to protect properties from the risk of fire.

The FRLs for clay masonry walls are expressed as a measure of structural adequacy, integrity, and
insulation, where (in the face of a fire):
• structural adequacy is the minimum time that the wall is expected to remain standing;
• integrity is the ability of the wall to prevent flames or hot gases passing through it; and
• insulation is the ability to keep the heat on the non-fire side of the wall below
a predefined temperature.
When determining the FRL of clay masonry walls, its height and size, proximity to adjacent wall
structure and whether it would be load/non-loadbearing must all be specified.

DETERMINING THE FIRE RESISTANCE LEVEL

This method for determining the FRL of the clay masonry component of a wall is based on the Think
Brick Manual 5 ‘Design of Clay Masonry Walls for Fire Resistance’, which is derived from AS 3700 Section 6
‘Design for Fire Resistance’.

STRUCTURAL ADEQUACY

Structural adequacy is affected by the slenderness ratio of the wall, which dictates its stability
and is calculated by:
1. identifying the length, height, and thickness of the wall, and the type of support
being used;
2. consulting the charts on pages 13-21 of Manual 5. Each chart is calibrated for 18 different
combinations of wall thickness and support types;
3. based on the diagram on each chart (top right of chart), selecting the one which meets
your structure’s specifications; and
4. finding the structural adequacy by tracking the point at which the values for wall height
(y-axis) and length (x- axis) intersect.

INTEGRITY

For the purposes of design, the fire resistance for integrity can be assumed to be the lesser
of the values determined for structural adequacy and insulation.

INSULATION

The FRL for insulation is a function of the material type and thickness of the wall.

For a clay masonry wall, the material thickness (MT) is the overall thickness of the wall
(if the units used are solid, fully grouted, or have coring of less than 30%)
If coring is more than 30% of the units surface area then:

Net Volume of the Unit


Material Thickness (MT) =
Area of exposed vertical face
Where: Net Volume of the Unit = Total Volume – Volume of Voids

Once MT has been identified, use the table below to calculate the FRL

Material Thickness (mm) 60 90 110 130 160 180


FRL for insulation (minutes) 30 60 90 120 180 240

WORKED EXAMPLE

To calculate the FRL for a solid, 110mm thick clay masonry wall, simply supported on all sides:
1. find the relevant chart in Manual 5 (e.g. Chart 2, shown in Figure 1, below);

Structural adequacy FRP (minutes) for 110 mm clay masonry walls with simple supports on four sides.

Figure 1: Chart 2 from TBA Manual 5 ‘Design for Fire Resistance’

2. intersect the wall height (3.5m) with the length (4.2m) to find a structural adequacy
measurement of 60 minutes (as can be seen on the chart);
3. because the unit is solid, MT = 110mm, and thus the FRL for insulation is 90 minutes; and
4. the integrity measure is the lesser of structural adequacy and insulation,
namely 60 minutes.
So the FRL for this wall would be 60/60/90.

Note: if a FRL is on the boundary or in between two values, the conservative, lower value is always taken.