Modification & Repair of Gantry Control Room: Doc No. 2838-CAL-001 Revision No. 0 Calculation For Room Pressurization

This document provides calculations for room pressurization for control rooms at various Shell Pakistan Limited locations. It calculates factors such as room volume, air flow rates, return air, exhaust air, room pressure and additional air flow needed to positively pressurize each room. All locations were found to meet the condition for positive pressurization of having the total air flow be greater than the volume based on the provided pressure ratings. Return air was set to zero to ensure no vapor return.

Uploaded by

azhar islam
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
158 views

Modification & Repair of Gantry Control Room: Doc No. 2838-CAL-001 Revision No. 0 Calculation For Room Pressurization

This document provides calculations for room pressurization for control rooms at various Shell Pakistan Limited locations. It calculates factors such as room volume, air flow rates, return air, exhaust air, room pressure and additional air flow needed to positively pressurize each room. All locations were found to meet the condition for positive pressurization of having the total air flow be greater than the volume based on the provided pressure ratings. Return air was set to zero to ensure no vapor return.

Uploaded by

azhar islam
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

MODIFICATION & REPAIR OF GANTRY CONTROL ROOM

SHELL PAKISTAN LIMITED

Doc No. 2838-CAL-001 Calculation for Room Pressurization Revision No. 0

Exhaust Air to
Proposed Additional
Air Change Total Outlet Return Air Exhaust Atmospheri Total Room Total Additional Additional Time to Additional Outside Air
Length (L) - Width (W) - Height (H) - Volume - Room Leakage (RL) - Return Air (RA) - Room Volume with Total Air flow Pressurized
Location per Hour Air Flow - (V) Ratio Air (EA) - c Pressure - Pressure - (Ptot) Volume - (Vt) - Volume - pressurize (t) - Air Flow (OA) - CFM
ft ft ft (Vr) - ft3 % CFM Pressure - leakage- (Val) - (SA) - CFM (Yes or No)
(ACH) - CFM EA:RA CFM (Patm) kPa kPa ft3 (Va) - ft3 sec (PA) - CFM
(Ppro) kPa ft3
(EARAR)
V = ACH x Vt = Ptot/Patm x Val = Va x PA = Val/t x
Vr = LxWxH EA = V- RA RA = V * EARAR Ptot = Patm + Ppro Va = Vt - Vr OA = V-RA+PA SA = OA + PA SA > V
Vr/60 Vr (1+RL/100) 60

Keamari DP 49.20 8.20 10.00 4034.40 15.00 25.00 1008.60 0.00 1008.60 0.00 101.33 0.02 101.35 4035.20 0.80 1.00 0.10 597.25 1605.85 2203.09 Yes
Keamari TW 14.80 5.79 10.00 856.57 15.00 25.00 214.14 0.00 214.14 0.00 101.33 0.02 101.35 856.74 0.17 0.21 0.10 126.81 340.95 467.76 Yes
Chaklala 25.34 12.68 8.99 2886.82 15.00 25.00 721.71 0.00 721.71 0.00 101.33 0.02 101.35 2887.39 0.57 0.71 0.10 427.36 1149.07 1576.43 Yes
Tarujabba 15.01 8.04 10.00 1205.88 15.00 25.00 301.47 0.00 301.47 0.00 101.33 0.02 101.35 1206.12 0.24 0.30 0.10 178.52 479.99 658.50 Yes
Shershah 14.80 5.79 10.00 856.57 15.00 25.00 214.14 0.00 214.14 0.00 101.33 0.02 101.35 856.74 0.17 0.21 0.10 126.81 340.95 467.76 Yes
Sahiwal 13.94 6.26 7.94 693.20 15.00 25.00 173.30 0.00 173.30 0.00 101.33 0.02 101.35 693.34 0.14 0.17 0.10 102.62 275.92 378.54 Yes
Shikarpur 11.99 9.63 9.54 1101.56 15.00 25.00 275.39 0.00 275.39 0.00 101.33 0.02 101.35 1101.78 0.22 0.27 0.10 163.07 438.47 601.54 Yes
Vehari 15.20 5.82 13.12 1161.26 15.00 25.00 290.32 0.00 290.32 0.00 101.33 0.02 101.35 1161.49 0.23 0.29 0.10 171.91 462.23 634.14 Yes
Machike 25.99 7.31 9.91 1883.36 15.00 25.00 470.84 0.00 470.84 0.00 101.33 0.02 101.35 1883.73 0.37 0.46 0.10 278.81 749.65 1028.46 Yes
Daulatpur 8.23 5.79 12.00 571.94 15.00 25.00 142.98 0.00 142.98 0.00 101.33 0.02 101.35 572.05 0.11 0.14 0.10 84.67 227.65 312.32 Yes

Condition for Positive Pressurization SA > V @ provided pressure rating

*RA = 0 (To ensure zero vapor return)

0 15-08-18 Issued for Review MZK IA SMS


Rev Date Description By Checked Approved