Performance of A DC/AC/DC VSC System To Interconnect HVDC Systems
Performance of A DC/AC/DC VSC System To Interconnect HVDC Systems
*Imperial College London, UK, {thomas.luth06, michael.merlin07, t.green}@ic.ac.uk, †Alstom grid, UK, {carl.barker,
fainan.hassan}@alstom.com
Keywords: HVDC, VSC, DC/DC conversion, fault isolation, demand for DC/DC converters in the MW application range
multi-level converter. so far.
Another approach to achieving a DC to DC conversion is the
Abstract “front-to-front” connection of two AC/DC Voltage Source
Interconnection of High Voltage Direct Current (HVDC) Converters (VSC) forming an internal AC-link. This is
links into networks is key to a future HVDC grid spanning illustrated in Figure 1 and was proposed in [4]. An advantage
large regions. Various factors including the evolution of cable of this design is that existing and standard VSC technologies
technology will lead to a variety of DC voltages and a need to that have been proven for the megawatt and kilovolt ranges,
provide a DC/DC step up/down at high power ratings (beyond can be used. The AC/DC converters could be of any topology
but the low switching loss of modular multi-level designs are
ͷͲͲ)ܹܯ. This paper analyses a High Voltage (HV) DC/DC
attractive. An example is the so-called ‘Alternate Arm
converter utilising an intermediate AC link between two
modular multi-level converters (MMC) based on the Converter’ (AAC) [5,6]. This converter is an alternative to the
MMC [7]. The AAC however allows for smaller cell stacks,
Alternate Arm Converter (AAC) topology. System operation
reducing footprint, as the AC voltage for each converter phase
is demonstrated using a detailed Simulink simulation. Power
leg is only generated by one arm for each half-cycle. The
loss estimates derived from the simulation are used to
other arm is disconnected by use of series connected Director
illustrate the dependence of efficiency on design choices and
Switches (DS) during this time. Current is commutated
operating point. Furthermore, the system is shown to block a
between the alternate arms at the end of each half-cycle.
DC-side fault and prevent its affect propagation through the
system.
1 Introduction
The utilisation of offshore wind and the growing electrical
interconnection of the countries surrounding the North Sea
have provoked much interest in voltage source HVDC
transmission and the possible interconnection of DC point-to-
point connections into multi-terminal systems. It becomes Figure 1: Front-to-front connection of two DC/AC VSCs.
apparent that some connections will require DC to DC
conversion where links built with different generations of 2 Schematic and Principles
cable technology are rated and operated at different voltages.
Technological development continues to raise link voltage 2.1 Operating principles
further. The absence of a standard transmission voltage is one
impediment to the interconnection of DC systems [1]. The proposed ‘front-to-front’ topology utilises an AC
Further, DC to DC conversion may be required as part of intermediate conversion step to provide an interconnection
future wind farm interfaces and even as a separation device in between two different DC voltage levels. Using AACs we
networks [2]. propose to connect both DC links to a shared AC connection.
Each phase of an AAC consists of director switches and two
DC/DC conversion is a well studied area for low voltage stacks of cells, one per arm as shown in Figure 2, which are
applications with a range of topologies to suit different used to generate the AC voltage waveforms and control the
voltage step ratios and power ratings. Such designs, however, converter currents. As shown in the schematic (Figure 2), the
do not lend themselves very well to scaling to typical HVDC cells used in the arms can be of either the half- or full-bridge
voltage levels due to a range of voltage stress problems and type. The choice of bridge depends on the AC voltage relative
inefficient use of the semiconductor’s power ratings, as to the respective DC link voltage.
discussed in [3]. One proposition for HV DC/DC conversion
is a resonant DC/DC converter using thyristor valves [3]. To
date no dominant topology has yet emerged because of little
1
Figure 2: Schematic of DC/AC/DC system using AACs.
The cell stack can be controlled to generate a voltage which ߨܸ ܫመ
either subtracts from (both half- and full bridges) or adds to ܧ ൌ
ሺȰ ሻ
ʹ߱
the DC link voltage (only full bridges) as seen from the AC
terminal. Each AAC has an operating point, so called ‘sweet- Equation 2: Energy transferred to cell stack per cycle from
spot’, at which each stack experiences a Zero Net Energy AC side.
(ZNE) exchange. The sweet-spot is at the optimal AC voltage Furthermore the energy exchange between the cell stacks and
defined by Equation 1. the DC link is dictated by the DC link voltage and the AC
ʹܸ current, shown in Equation 3.
ܸ௧ ൌ
ߨ ܸ ܫመ
Equation 1: Optimal AC voltage for AAC sweet-spot ܧ ൌ
ሺȰ ሻ
߱
When operating at the sweet-spot, an AAC will have to over- Equation 3: Energy transferred per cycle out of cell stack to
modulate, meaning that the peak AC voltage is higher than DC link.
half the DC link voltage. Thus the cell stack in each arm has
to have positive and negative voltage generating capabilities. At the aforementioned sweet-spot ܧ ൌ ܧ . At all other
This in turn requires the use of full-bridge cells. Neither AAC operating points however there exists an energy imbalance in
is restricted to the use of one or the other type of cell. each cell stack which has to be counteracted to maintain the
voltages of the cell capacitors.
We chose to investigate a conventional three-phase
arrangement for the AC-link, but the number of phases is not One energy balancing technique, which has previously been
restricted to this. Rather it is a design trade-off between the employed with the AAC, is the introduction of an overlap
device number and their necessary space and investment current [6]. To accomplish this, the arm inductances are used
requirements, which is of particular relevance for off-shore to control a DC current flowing through both arms of the
applications. same AAC to exchange energy between the stacks and the
DC link. For this to occur an overlap period is defined during
2.2 Energy Balance which both Director Switches are closed.
The energy exchange between an AAC and the AC-link is 2.3 AC Link Parameters
dictated by the AC current and voltage as given by Equation 2
(Ȱ is the angle of the AC current with respect to the Because the AC-link is exclusively internal to the DC/DC
voltage). converter, there are no relevant grid codes that must be
2
applied. Thus the AC voltage magnitude and frequency can ܸ Ȱ௩
௦௧ ൌ
ܷ ܸ ڄ൬ ൰
be varied to suit the implementation. Using the AC voltage ʹ ʹ
level we can trade-off a lower AC current magnitude against a
Equation 4: maximum under-modulation voltage to be
larger stack size to support a higher AC voltage. Furthermore,
generated by stack.
we can choose the voltage to achieve an operating point at
which the energy imbalance and the losses associated with the If the AC voltage has a peak magnitude of greater than that of
balancing currents are optimised. half the DC connection voltage, the stack will also have to be
able to over-modulate. Extra cells for this however are only
A higher AC voltage implies a lower current magnitude for a
required if the maximum over-modulation voltage, as given in
given power transfer. This is advantageous for the conduction
Equation 5, is greater than the maximum under-modulation
losses as they increase quadratically with current magnitude.
voltage.
In addition, the energy imbalance experienced by the cell
stacks each cycle is affected by the AC voltage. The ܸ
௦௧ைெ ൌ ܸ െ
ܷ
necessary balancing current magnitudes can thus be ʹ
influenced. Owing to the nature of the conduction losses, it
Equation 5: maximum over-modulation voltage required of
may be advantageous to share the energy imbalance burden
stacks.
between both AACs rather than operate at a sweet-spot of
either AAC. Each director switch contains a number of series-connected
IGBTs which are each rated at a nominal steady-state voltage
The AC frequency can be adjusted to trade-off between
stress of ͳǤͺܸ݇. The maximum blocking voltage of the
switching losses and passive component sizing. Increasing the
director switch is given in Equation 6.
frequency allows the cell level capacitance to be reduced
whilst keeping the same voltage fluctuation. It also allows for Ȱ
ௗ௧ ൌ ܸ ڄ൬ͳ െ ൬ ௩ ൰൰
ܷ
significantly reduced arm and phase inductance ratings ʹ
thereby reducing the capital cost. Such reductions might be
very desirable for applications where physical space is a Equation 6: Maximum director switch blocking voltage.
restricting factor, such as on an off-shore platform. In this paper we show results for an AC peak voltage of
ʹͷܸ݇ and the corresponding stack parameters can be found
3 Simulation in Table 1.
3
required to over-modulate and thus requires full-bridge cells.
The two AACs experience energy imbalances of similar size.
3 Phase AC Currents
1000
Current [A]
0
-1000
0.4 0.405 0.41 0.415 0.42 0.425 0.43
3 Phase AC Voltages (HV AAC side)
20
Voltage [kV]
0
-20
0.4 0.405 0.41 0.415 0.42 0.425 0.43
HV DC Link Currents (unfiltered)
1000
Figure 3: Control Structure of entire system. Current [A]
0
3.3 Normal Operation
-1000
The system was tested under normal operation to verify its
ability to transfer power in either direction and maintain 0.4 0.405 0.41 0.415 0.42 0.425 0.43
nominal cell capacitor voltages. The results in Figure 4 show LV DC Link Currents (unfiltered)
the AC voltages and currents as well as the unfiltered DC link 1000
currents for a peak AC voltage of ʹͷܸ݇. The harmonic
Current [A]
maintain the energy balance in the cells. The HV1 side AAC 0.4 0.405 0.41 0.415 0.42 0.425 0.43
Time [s]
requires around െʹͷͲ ܣand the HV2 side AAC around
െ͵ͷͲܣ. The peaks and troughs seen in the link currents, Figure 4: Voltage and current waveforms of system under
Figure 4, at six times fundamental frequency are largely the normal operation at ܸ ൌ ʹͷܸ݇ and ͵Ͳ ܹܯpower
results of these balancing currents. transfer (from HV1 to HV2 side).
4
scale linearly with AC frequency. This intuitively makes match closely with an error of ǤͷΨ for ͷͲ ݖܪand ͳʹǤʹΨ
sense as the switching of cells is dominated by the generation for ͷͲͲݖܪ. The switching losses are overestimated because
of the step-wave approximation of the sine wave with some of simplifying assumptions about the overlap current control
additional commutation for control of the balancing current switching frequency. Also the switching events due to the cell
and to provide cell rotation. The cell rotation frequency rotations are difficult to predict accurately and are thus over-
cannot be lowered with higher AC frequency as a minimum estimated in the analytical method. This is most notable at
number of cell rotations are required per AC cycle to maintain higher AC frequencies where the switching losses dominate
the cell voltages. due to a higher switching frequency.
LV DC Link Currents (unfiltered)
3.5 DC Side Fault Response
1,000
During a fault on one of the DC connections, the system
Current [A]
works to prevent the fault current from travelling through the 0
system and affecting the other DC connection. This is done
by effectively shutting down the AC-link, keeping control of -1,000
the AC currents, and opening the Director Switches on the 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
unaffected side as soon as the arm currents have been HV DC Link Currents (unfiltered)
regulated down to an acceptable level.
1000
Following fault detection, the AC current reference is set to
zero and all energy balancing mechanisms are disabled until Current [A] 0
the fault is cleared. The latter is done as there cannot be an
energy exchange between the stacks and the DC connection if -1000
the link voltage has collapsed. The non-faulty side’s energy 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
balancing is also disabled to help keep the AC side stable and 3 Phase AC Currents
switched off. In the simulation a detection time of ͷ݉ ݏand a 1000
fault clearance time of ͳͺͲ݉ ݏis assumed. At ͲǤʹ ݏthe HV2
Current [A]
5
Such a system was not built in Simulink as the cell stacks suggesting it may be a feasible option for the interconnection
become prohibitively large (Table 4) to simulate effectively of HVDC system. Further work will also investigate different
using a detailed model. application areas of this circuit with varying step-ratios.
AAC ࡺ Cells Cell type ࡺ IGBT in DS
6 Acknowledgement
HV1side 373 Half-bridge 183
HV2 side 262 Full-bridge 183 The authors gratefully acknowledge the permission from
Alstom Grid to publish this paper and the financial support
Table 4: Cell stack and director switch parameters per arm of
provided by them. The authors also acknowledge the support
scaled up system for ܸ ൌ ͷͲͲܸ݇.
of the EPSRC (www.epsrc.ac.uk) under grant number
Loss Category ࢌ ൌ Hz ࢌ ൌ Hz EP/G066477/1 for some of the analytical work on which this
HV1 AAC [MW] 2.754 5.526 study was based.
Conduction Loss 2.442 2.442
Switching Loss 0.312 3.084 References
HV2 AAC [MW] 4.090 10.412
Conduction Loss 3.372 3.372 [1] D. Jovcic, D. van Hertem, K. Linden, J.P. Taisne, W.
Switching Loss 0.718 7.040 Grieshaber. “Feasibility of DC Transmission Networks”,
Total Losses [MW] 6.844 15.938 International Conference and Exhibition on Innovative
System Efficiency (%) 98.9 97.4 Smart Grid Technologies (ISGT Europe), 2nd IEEE
PES,(2011)
Table 5: Analytical semiconductor losses for scaled up system
[2] D. van Hertem, M. Ghandhari, M. Delimar. „Technical
at ܸ ൌ ͷͲͲܸ݇.
Limitations Towards a Supergrid, a European
The losses shown in Table 5 are for a system with the Prospective”, Energy Conference and Exhibition
following parameters: (EnergyCon), IEEE International, (2010)
+600 MW power transfer capability [3] D. Jovcic. “Bidirectional, High-Power DC
HV1 DC link voltage: ±500 kV Transformer”, IEEE Transactions on Power Delivery,
HV2 DC link voltage: ±300 kV 24, (4), pp. 2276-2283 (2009)
DC/DC step ratio: 1.67 [4] C.D. Barker, C.C. Davidson, D.R. Trainer, R.S.
Phase inductance: 0.2 PU Whitehouse. “Requirements of DC-DC Converters to
Arm inductance: 0.02 PU facilitate large DC Grids”, Cigre, SC B4 HVDC and
Cell Capacitance: 7mF at 1.8 kV Power Electronics, (2012)
Overlap period: ʹߨൗͻ ݀ܽݎ [5] D.R. Trainer, C.C. Davidson, C.D.M. Oates, N.M.
ܸ ൌ ͷͲͲܸ݇ Macleod, D.R. Critchley, R.W. Crookes. “A new Hybrid
Voltage-Sourced Converter for HVDC Power
5 Conclusion Transmission”, Cigre, B4-111, HVDC and Power
Electronics, (2010)
This paper has introduced an HV DC/AC/DC system suitable
for the interconnection of HVDC systems of different [6] M.M.C. Merlin, T.C. Green, P.D. Mitcheson, D.R.
nominal DC voltages. A scaled-down sample system was Trainer, D.R. Critchley, R.W. Crookes. “A New Hybrid
modelled in Simulink to test its operation under normal and Multi-Level Voltage-Source Converter with DC Fault
DC-side fault conditions. The importance of a carefully Blocking Capability”, 9th IET International Conference
chosen AC voltage was highlighted as this will strongly affect on AC and DC Power Transmission, (2010)
the system’s efficiency. The system is also capable of [7] A. Lesnicar, R. Marquardt. “An Innovative Modular
preventing the affects of a DC side pole-to-pole fault from Multilevel Converter Topology Suitable for a Wide
spreading to the other DC link. Power Range”, Power Tech Conference Proceedings,
Furthermore, a scaled-down Simulink model was used to IEEE Bologna, (2003)
verify the accuracy of an analytical loss model for full scale [8] R. Theodorescu, F. Blaabjerg, M. Liserre, P.C. Loh,
systems. The error between the two approaches was ǤͷΨ at “Proportional-resonant controllers and filters for grid-
an AC frequency of ͷͲݖܪ. An overestimation in the connected voltage-source converters”, IEE Proceedings
switching losses in the analytical method has been identified – Electric Power Applications, 153, pp. 750-762, (2006)
as a main source for the error. Further work will aim to fix
this and reduce the error of the analytical method, particularly
at higher AC frequencies to improve the accuracy of loss
estimates for to scale systems.
The analytical model shows that such a system for a step ratio
of ͷǣ ͵ can be operated with an efficiency of ͻͺǤΨ at ͷͲݖܪ