MODEL 5128/29: Installation Manual
MODEL 5128/29: Installation Manual
Trim Line
Content
Section 1
Introduction .........................................................................................................................................................1
1.1 Features ...............................................................................................................................................................1
1.2 Optional Devices .................................................................................................................................................2
1.3 UL Fire Listed Receivers Compatible with the 5128/29 ....................................................................................2
1.4 How to Use this Manual ......................................................................................................................................2
1.5 How to Contact Silent Knight .............................................................................................................................3
Section 2
Agency Requirements ..........................................................................................................................3
Section 3
Panel Description and Installation .......................................................................................5
150805 i
Model 5128/29 Fire Slave Communicator Installation Manual
Section 4
Normal Operation ......................................................................................................................................18
Section 5
Programming ...................................................................................................................................................21
5.1 Programming with the 5230 Remote Annunciator ...........................................................................................21
5.2 Programming with the 5541 Downloading Software ........................................................................................22
5.3 Programming Options .......................................................................................................................................22
Section 6
Reporting ..............................................................................................................................................................29
Section 7
Troubleshooting ..........................................................................................................................................31
7.1 System Messages ...............................................................................................................................................31
7.2 Silencing Troubles .............................................................................................................................................31
ii 150805
SECTION 1
INTRODUCTION
The Silent Knight Model 5128/29 is a low-cost slave communicator that meets the requirements for UL 864,
NFPA 72 Fire Alarm Systems for Central Station Service and NFPA 72 Remote Supervising Station Fire
Alarm Systems.
1.1 Features
• Compatibility with the Security Industry Association (SIA) reporting format and several other standard
reporting formats.
• Four channel (zone) inputs for system status reporting: fire alarm (channel or zone 1); system trouble–
channel 2 (or zone 2); supervisory–channel 3 (or zone 3); and miscellaneous–channel 4 (or zone 4).
• Optional two-number dialing with same or different account codes and reporting formats. Alarms,
troubles, and tests can be programmed to be reported to either or both numbers.
• Programmable as rotary-only or as Touch-Tone/rotary dialing.
• Built-in dual phone line-seizure circuit.
• Dual phone line monitor circuits.
• Transient voltage protection of phone lines.
• Built-in audible trouble buzzer.
• One relay output, programmable for alarm or trouble conditions.
• Light-emitting diodes (LEDs), visible from front of enclosure, indicating: trouble condition (yellow);
presence of DC power (green), phone line 1 trouble (red); and phone line 2 trouble (red).
• Easy, English-language programming using Model 5230 Remote Annunciator.
• Fuseless design, 24 VDC.
• Electrically erasable read-only memory (EEPROM) for nonvolatile storage of all programmable option
data. Eliminates the need to reprogram the communicator if power is lost.
• Built-in watchdog circuit that monitors the operation of the 5128/29 and resets the communicator if a fault
is detected.
• Active high or contact closure input.
• Model 5129 can directly monitor control panel’s primary power.
• Compatibility with many Underwriters Laboratories (UL) Fire Listed receivers. (See Section 1.3 for list.)
• Model 5128 housed in 8-5/8" x 4" x 1-3/8" enclosure for mounting inside control panel.
• Model 5129 housed in a 10" x 10" metal enclosure.
150805 1
Model 5128/29 Fire Slave Communicator Installation Manual
The following accessories are available for use with the 5128/29:
• Model 5230 Remote Annunciator for programming, troubleshooting, and system operation. Only one
model 5230 can be used.
• Cable for 5230, P/N 130294.
• 5541 Downloading Software for remote programming. (Must be Revision 3.7 or later.)
• 5530 Modem. Required if the 5541 downloading software is used.
1.3 UL Fire Listed Receivers Compatible with the 5128/29
The following UL Listed receivers are compatible with the 5128/29:
RECEIVER FORMATS
Silent Knight Model 9000, 9500, or 9800 BFSK14
Note: The Model 9000 receiver does not BFSK23
accept CID format. SK 3/1
SK 4+2
SIA8
SIA20
Contact ID (CID)
Osborn & Hoffman Quickalert SK 3/1
SK 4+2
SIA8
SIA20
BFSK14
BFSK23
Ademco 685 SK 3/1
SK 4+2
FBI CP220 SK 3/1
SK 4+2
Radionics D6500 BFSK 1400
BFSK 2300
2 150805
Agency Requirements
SECTION 2
AGENCY REQUIREMENTS
2.1 Telephone Requirements
1. If requested by the telephone company, the following information must be provided before connecting this
device to the phone lines:
A. Manufacturer: Silent Knight
B. Model Number: 5128/29
C. FCC Registration Number: AC6USA-75160-AL-E
Ringer equivalence: 0.1B
D. Type of jack (to be installed by the telephone company): RJ31X
2. This device may not be directly connected to coin telephone or party line services.
3. This device cannot be adjusted or repaired in the field. In case of trouble with the device, notify the install-
ing company or return:
Silent Knight
7550 Meridian Circle
Maple Grove, MN 55369
763-493-6455
800-328-0103
4. If the Model 5128/29 causes harm to the telephone network, the telephone company will notify the user in
advance that temporary discontinuance of service may be required. If advance notice is not practical, the
telephone company will notify the user as soon as possible. The user has the right to file a complaint with
the Federal Communications Commission if he or she believes it is necessary.
5. The telephone company may make changes in its facilities, equipment, operations, or procedures that
could affect the operation of the equipment. If this happens, the telephone company will provide advance
notice so that you can make the necessary modifications to maintain uninterrupted service.
150805 3
Model 5128/29 Fire Slave Communicator Installation Manual
WARNING:
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions: (1) This device may
not cause radio interference, and (2) This device must accept any interference received, including interference that may cause
undesired operation.
Signaling device subassembly for use in Fire Alarm Systems for Central
Station Service.
5128
Signaling device subassembly for use in Remote Supervising Fire Alarm
Systems.
Signaling device for use in Fire Alarm Systems for Central Station Service.
5129
Signaling device for use in Remote Supervising Fire Alarm Systems.
All UL installations must comply with the requirements described below. Refer to the control unit’s installation
manual for complete information.
5128 Requirements:
The 5128 must be mounted within a UL listed compatible fire control panel.
5129 Requirements:
The 5129 and the UL listed compatible fire control must be installed in the same room. All wiring between the
5129 and the UL Listed compatible fire control panel must be enclosed in conduit.
Requirements for both 5128 and 5129:
All electrical connections must comply with the ratings shown in section 3.2.4. In a remote signaling
installation, the control unit, slave dialer, and receiver at the remote site must all be UL listed for remote
signaling.
4 150805
Panel Description and Installation
SECTION 3
PANEL DESCRIPTION AND INSTALLATION
CAUTION:
To avoid the risk of electrical shock, make sure the main control power is OFF when wiring. DO NOT apply power until
wiring is completed following the procedures described in this manual.
3.1.4 EEPROM
The electrically erasable read-only memory (EEPROM) is used to store specific information such as system
configuration, telephone numbers, reporting format, and account numbers. The EEPROM retains the
programmed information even when all electrical power is removed. It can be programmed more than 1,000
times without losing its ability to store information.
150805 5
Model 5128/29 Fire Slave Communicator Installation Manual
3.1.5 DC Power
The 5128/29 operates on 18-40 VDC rectified power from the main fire control panel.
6 150805
Panel Description and Installation
3.2 Wiring
3.2.1 Wiring Precautions
High and low voltage must be separated by at least one-quarter inch. See Section 3.2.5 for more information.
High current input/output: AC monitoring (if monitored directly)
Low current input/output: 24 VDC power and channel (zone) wiring
Audio input/output: Telephone wiring
High frequency noise, such as that produced by the inductive reactance of a bell, can also be reduced by
running the wire through ferrite shield beads or by wrapping it around a ferrite toroid.
150805 7
Model 5128/29 Fire Slave Communicator Installation Manual
Earth Ground
DC Power
(See Section 3.3)
Silence Button
(See Section 7.2)
5230 Connector
(See Section 3.9.1) All Circuits Supervised
Power Limited except
Direct AC Monitoring,
To Telco
Channel Inputs which is supervised only
Lines (See
(See Section 3.5) Section 3.8)
Low AC Channel
(See Section 3.6)
Relay Terminals
Contact Rating
1A @ 24VDC or 24VAC
(See Section 3.7)
Direct AC Monitoring
(See Section 3.6.3)
8 150805
Panel Description and Installation
Cable Clamp
See instructions
Below
Board Ground
To Telco
Lines
Cable Tie
Must be enclosed
in conduit.
From AC
150805 9
Model 5128/29 Fire Slave Communicator Installation Manual
Red
Black
Positive Negative
Power from Power from
Control Panel Control Panel
10 150805
Panel Description and Installation
150805 11
Model 5128/29 Fire Slave Communicator Installation Manual
Dry Contact
Example
Voltage Input
Example Supervised
Power Limited
12 150805
Panel Description and Installation
3.6 AC Monitoring
The 5128/29 features an AC monitoring circuit. The communicator will report AC trouble when AC has been
below 85 percent of nominal for a programmed amount of time. The 5128 AC monitoring can be performed
with a dry contact active high voltage input (see Section 3.6.1). The Model 5129 can monitor AC voltage
directly (see Section 3.6.3).
Supervised Supervised
Power Limited Power Limited
150805 13
Model 5128/29 Fire Slave Communicator Installation Manual
Supervised
14 150805
Panel Description and Installation
150805 15
Model 5128/29 Fire Slave Communicator Installation Manual
16 150805
Panel Description and Installation
To 5128/29
P4 Connector
(See Section 3.2.2)
150805 17
Model 5128/29 Fire Slave Communicator Installation Manual
SECTION 4
NORMAL OPERATION
This section describes normal system operations using the 5230 remote annunciator.
4.1 5230 Operation
The 5230 is equipped with an LCD (liquid crystal display) that displays English-language messages. If the
5128/29 is not being programmed, the LCD cycles through all messages that are applicable at the time,
showing a different one every 1.5 seconds. The messages are listed in the troubleshooting section of this
manual (Section 7.2).
4.1.2 Buzzer
An audio transducer buzzer is built into the 5230 annunciator. It produces short beeps to annunciate keystrokes.
It also emits a long, high-pitched tone to indicate a trouble condition or when an annunciator function has been
entered incorrectly.
18 150805
Normal Operation
150805 19
Model 5128/29 Fire Slave Communicator Installation Manual
20 150805
Programming
SECTION 5
PROGRAMMING
The Model 5128/29 provides a wide variety of features that can be selected for use depending on your needs.
These features are stored in an EEPROM (Electrically Erasable Programmable Read-Only Memory) chip
which has been factory-programmed. Section 5.1 describes how to change programming options using the
5230 Remote Annunciator. Section 5.2 explains using the Model 5541 Downloading Software for
programming. All programmable options are described in Section 5.3.
5.1 Programming with the 5230 Remote Annunciator
Note: The system will automatically time out of programming mode if no keys are pressed for four minutes. If you press
function keys very quickly, you may get ahead of the LCD display. Wait for the appropriate message to be dis-
played before you press ENTER .
TO: KEYSTROKES:
ENTER PROGRAMMING MODE 2 7 ENTER [Installer’s Code]
The first line of the LCD will show the programming option for
Step 1, “ZONE ACTIVE.” The second line will show the most recently programmed
value for that option.
PROGRAM AN OPTION Type in your new data and then press ENTER .
SKIP A STEP Press ENTER .
The data in the skipped step will not change. The LCD will show the next option.
GO TO A SPECIFIC STEP Press STEP . The first line of the LCD will show “ENTER THE STEP #” and the
current step number. Type in the new step number, then press ENTER . Line 1 of
the LCD will show the option name; line 2 will show the programmed data for the
step. (If you try to go to a step that does not exist, the display will go back to the
previous step.)
SELECT YES OR NO Press any digit to toggle Yes and No.
SELECT AN OPTION FROM A MENU Press the option number. (Option numbers appear next to the option name in Section
5.3.)
ENTER ALPHABETIC DATA OR SHIFT 1 for A or 10
NUMBERS LARGER THAN 9
SHIFT 2 for B or 11
SHIFT 3 for C or 12
SHIFT 4 for D or 13
SHIFT 5 for E or 14
Note that only the alphabetic characters appear on the display.
CORRECT AN ERROR Press CLEAR . Then type in the correct data and press ENTER .
(If you have not pressed the ENTER key.)
LEAVE PROGRAMMING MODE Press STEP STEP CLEAR CLEAR .
AT ANY TIME
150805 21
Model 5128/29 Fire Slave Communicator Installation Manual
22 150805
Programming
Step # /
Your Choice
From Option Description
(D) = Default
Menu
1 ZONE ACTIVATION Select input type. r Dry contact (D)
System 0 = Dry contact input r Active high
Menu 1 = Active high input
2 = Currently not available. Do not select.
2 ZONE SUPERVISED Yes = All zones supervised r Yes
System No = All zones unsupervised r No (D)
Menu
3 LATCH SPRINKLER Yes = When the sprinkler zone shorts for a duration longer than the Zone r Yes
System Response (set in steps 7 through 10), the annunciator remains active until r No (D)
Menu reported or manually silenced.
No = When the sprinkler zone shorts for a duration longer than the Zone
Response (set in steps 7 through 10), the zone will follow system status
and indicate a supervisory on that zone for the duration of the faulted
condition.
4 CHANNEL #1 TYPE Alarm input r Fire (D)
System 0 = Fire r Sprinkler
Menu 1 = Sprinkler
5 CHANNEL #2 TYPE Trouble input r Fire (D)
System 0 = Fire r Sprinkler
Menu 1 = Sprinkler
6 CHANNEL #3 TYPE Supervisory input r Fire
System 0 = Fire r Sprinkler (D)
Menu 1 = Sprinkler
NOTES FOR STEPS 7-10:
Channel response time speeds are not intended to be used as a smoke verification feature. Possible choices for channel response times are
0-3 (described below).
7 ZONE RESPONSE #1 0 = 0.3 to 0.4 seconds 1 = 3 to 4 seconds r 0.3 to 0.4 sec (D)
System 2 = 15 to 20 seconds 3 = 30 to 40 seconds r 3 to 4 sec
Menu NOTE: If you make a mistake and program a number other than 0-3, the r 15 to 20 sec
resulting zone speed will be: r 30 to 40 sec
4 = 0.3 to 0.4 seconds 5 = 3 to 4 seconds
6 = 15 to 20 seconds 7 = 30 to 40 seconds
8 = 0.3 to 0.4 seconds
9 = 3 to 4 seconds
150805 23
Model 5128/29 Fire Slave Communicator Installation Manual
Step # /
Your Choice
From Option Description
(D) = Default
Menu
8 ZONE RESPONSE #2 Factory programmed as “1” (3 to 4 seconds). Cannot be changed. No selection.
System
Menu
9 ZONE RESPONSE #3 (See step 7.) r 0.3 to 0.4 sec (D)
System r 3 to 4 sec
Menu r 15 to 20 sec
r 30 to 40 sec
10 ZONE RESPONSE #4 (See step 7.) r 0.3 to 0.4 sec (D)
System r 3 to 4 sec
Menu r 15 to 20 sec
r 30 to 40 sec
11 RELAY #1 0 = Relay activates on alarm r Alarm
System 1 = Relay activates on system trouble r Trouble (D)
Menu
12 INSTALLER’S CODE Installer’s code [4 digits]. For programming and other system control ________________
System functions. Can also perform all the same operations as the operator’s code. Default = 5128
Menu (See Section 4.2 for specific information about which functions the code
can perform.)
13 OPERATOR’S CODE Operator’s code [4 digits]. Used for basic operation. (See Section 4.2 for ________________
Dialer specific information about which functions the code can perform.) This Default = 1111
Menu code must be different from the installer’s code.
24 150805
Programming
Step # /
Your Choice
From Option Description
(D) = Default
Menu
18 MUST REPORT #1 Yes = Reports must always be sent to central station phone #1. r Yes (D)
Dialer No = If another phone number is available first, no report to phone #1. r No
Menu Note: If must report is selected for #1 or #2 then the event will report to
that account.
19 MUST REPORT #2 Yes = Reports must always be sent to central station phone #2. r Yes (D)
Dialer No = If another phone number is available first, no report to phone #1. r No
Menu Note: If must report is selected for #1 or #2 then the event will report to
that account.
20 AC ACTIVATION 0 = Active high r Active high
Dialer 1 = Active low r Active low
Menu 2 = AC Monitored r Monitor AC (D)
21 AC LOSS HOURS Enter the number of hours before AC power loss is reported. Set to 6-12 _______
Dialer hours for NFPA 72 Fire Alarm Systems for Central Station Service Default = 6
Menu (Chapter 4-3). Set to 15 hours for NFPA 72 Remote Supervising Station
Fire Alarm Systems. Set to 0 if you are using a fire control panel that has a
built-in delay. (Refer to the panel manual for details.)
150805 25
Model 5128/29 Fire Slave Communicator Installation Manual
Step # /
Your Choice
From Option Description
(D) = Default
Menu
26 150805
Programming
Step # /
Your Choice
From Option Description
(D) = Default
Menu
31 ACCOUNT #1 Account # for central station phone #1 (6 digits; leading zeros if shorter). ________________
Dialer Default = 105128
Menu
32 ATTEMPTS #1 Number of times phone line #1 will try to dial each central station acct. # ____
Dialer before “DIALER FAILED” displays on the 5230 LCD. Range is 3 to 5. Default = 3
Menu
33 FORMAT #1 Select reporting format for phone line #1. r SIA8
Dialer See Section 6 for descriptions of these formats. r Reserved
Menu 0 = SIA8 r SK4+2
1 = Reserved r BFSK14
2 = SK4+2 r BFSK23
3 = BFSK14 r SIA20 (D)
4 = BFSK23 r 3/1 14
5 = SIA20 r 3/1 23
6 = 3/1 14 r CID
7 = 3/1 23
8 = Contact ID
34 CIC #1 Carrier Identification Code is the prefix that needs to be dialed before a ________________
Dialer phone number to access a particular long distance carrier. Use special [blank - no default]
Menu characters to add pauses, #, *, and "look for second dial tone" characters
into the phone number. See STEP 35 for list of special characters.
35 PHONE #1 Enter the phone number for phone line #1 (up to 16 digits). The ________________
Dialer following special options and characters can be part of a phone [blank - no default]
Menu number: pause; look for second dial tone; * (asterisk); and #
(number or pound symbol). For “pause”, press SHIFT 1 . (“A”
displays on LCD.) For “*”, press SHIFT 2 . (“B” displays on the
LCD.) For “#”, press SHIFT 3 . (“C” displays on LCD.) For “look
for second dial tone”, press SHIFT 4 . (“D” displays on LCD.)
36 ACCOUNT #2 Account number for central station phone #2 (6 digits; leading zeros if ________________
Dialer shorter). Default = 205128
Menu
37 ATTEMPTS #2 Number of times phone line #2 will try to dial each central station acct. # ____
Dialer before “DIALER FAILED” displays on the 5230 LCD. Range is 3 to 5. Default = 3
Menu
150805 27
Model 5128/29 Fire Slave Communicator Installation Manual
Step # /
Your Choice
From Option Description
(D) = Default
Menu
38 FORMAT #2 Select reporting format for phone line #2. r SIA8
Dialer See Section 6 for descriptions of these formats. r Reserved
Menu 0 = SIA8 r SK4+2
1 = Reserved r BFSK14
2 = SK4+2 r BFSK23
3 = BFSK14 r SIA20 (D)
4 = BFSK23 r 3/1 14
5 = SIA20 r 3/1 23
6 = 3/1 14 r CID
7 = 3/1 23
8 = Contact ID
39 CIC #2 Carrier Identification Code is the prefix that needs to be dialed before a ________________
Dialer phone number to access a particular long distance carrier. Use special [blank - no default]
Menu characters to add pauses, #, *, and "look for second dial tone" characters
into the phone number. See STEP 35 for list of special characters.
40 PHONE #2 Enter phone #2 (up to 16 digits). ________________
Dialer (See Step 33 for more information.) Default = 2
Menu
41 COMPUTER Enter the account number for the downloading computer ________________
Dialer ACCOUNT (6 digits; leading zeros if shorter). Default = 005128
Menu
42 COMPUTER CIC See Step 34 for description. ________________
Dialer [blank - no default]
Menu
43 COMPUTER PHONE Enter the phone number for the downloading computer (up to 16 digits). ________________
Dialer (See Step 33 for more information about entering phone numbers.) Default = 2
Menu
44 TEST TIME Enter the test report time using the 24-hour military format (include ________________
Dialer leading zeros). Default = 0130
Menu
45 CURRENT TIME Set the current time using the 24-hour military format (include leading
Dialer zeros).
Menu (NOTE: It is recommended that you check the system time every few
months and reset it if necessary.)
28 150805
Reporting
SECTION 6
REPORTING
The Model 5128/29 can transmit information in several different formats (including two types of BFSK and
SIA formats). The type of format you select is determined by the type of receiver used at the central station.
Note that the SIA formats are recommended for use with the 5128/29. (All formats listed below are compatible
with the Silent Knight model 9000, 9500, and 9800 receivers.)
Note: Some formats do not distinguish between certain types of reports, such as between waterflow and fire alarms or
between supervisory and trouble reports. Central station personnel must keep records of how the various zones
are programmed at each account, so they can determine what condition is being reported for a particular zone.
FORMAT DESCRIPTION
SIA8 Security Industry Association standard communication format which send a maximum
of 8 events per call. Used with the Silent Knight model 9000 Digital Alarm Receiver
and model 9004 or model 9004I SIA line card.
SIA20 Security Industry Association standard communication format which send a maximum
of 20 events per call. Up to a 6-digit account number. Used with the Silent Knight
model 9000 receiver, with a 9004I SIA line card and a 9200 CPU card, Revision E.
SK4+2 Tone burst format, transmits a 4-digit account code and 2-digit alarm code at 20 pps.
Transmissions are acknowledged at 1400 Hz.
BFSK14 Radionics format which transmits a high-speed, single-round, 3-digit account number,
followed by report information. Transmissions are acknowledged at 1400 Hz.
BFSK23 Radionics format which transmits a high-speed, single-round, 3-digit account number,
followed by report information. Transmissions are acknowledged at 2300 Hz.
SK3/1 14 Used with older Silent Knight, Ademco, or Sescoa receivers that can receive at 20 pps
and send a 1400-Hz acknowledgment tone.
Sescoa 3/1 23 Used with older Sescoa or other receivers that can receive at 20 pps and send a 2300-
Hz acknowledgment tone.
Contact ID Ademco Contact ID format. DTMF (Dual Tone Multiple Frequency) format. Send a 4-
digit account number. Transmission are acknowledged at both 1400 and 2300 Hz.
The tables in the subsections that follow show the digits that are transmitted for each event reported by the
5128/29 dialer, and the message that is printed if the central station uses the Silent Knight model 9000, 9500, or
9800 receiver. A separate table is shown for each format.
150805 29
Model 5128/29 Fire Slave Communicator Installation Manual
Event SIA8 & 20 SK4/2 3/1 1400 &2300 BFSK14 & 23 Contact ID
Fire Alarm 1-6 FA1 - FA4 *01 - 04 Alarm Code 01 - 04 1 110 001 - 1 110 004
Fire Alarm Restore 1-6 FH1 - FH4 *21 - 24 Restore Code E1 - E4 3 110 001 - 3 110 004
Fire Trouble 1-6 FT1 - FT4 61 - 64 Trouble Code F1 - F4 1 373 001 - 1 373 004
Fire Trouble Restore 1-6 FJ1 - FJ4 71 - 74 Restore Code E1 - E4 3 373 001 - 3 373 004
Sprinkler Supervisory 1-6 SS1 - SS4 01 -04 Sprinkler Code 01 - 04 1 203 001 - 1 203 004
Sprinkler Supervisory Restore 1-6 SR1 - SR4 21 - 24 Restore Code E1 - E4 3 203 001 - 3 203 004
Sprinkler Trouble 1-6 ST1 - ST4 61 - 64 Trouble Code F1 - F4 1 203 001 - 1 203 004
Sprinkler Trouble Restore 1-6 SJ1 - SJ4 71 - 74 Restore Code E1 - E4 3 203 001 - 3 203 004
AC Trouble AT0 60 Trouble Code FA 1 301 000
AC Restore AR0 70 Restore Code EA 3 301 000
Trouble Phone Line #1 LT1 31 Trouble Code FB 1 351 000
Restore Phone Line #1 LR1 35 Restore Code EB 3 351 000
Trouble Phone Line #2 LT2 32 Trouble Code FC 1 352 000
Restore Phone Line #2 LR2 36 Restore Code EC 3 352 000
Communications Failure Line #1 YC1 31 Trouble Code FB 1 351 000
Communications Restore Line #1 YK1 35 Restore Code EB 3 351 000
Communications Failure Line #2 YC2 32 Trouble Code FC 1 352 000
Communications Restore Line #2 YK2 36 Restore Code EC 3 352 000
Manual Test RX0 30 Test Code EE 1 601 000
Automatic Test RP0 30 Test Code EE 1 602 000
Downloading Passed RS0 30 Test Code EF 1 412 000
Downloading Failed RU0 30 Test Code FF 1 413 000
Data Lost RT0 39 Trouble Code FE 1 354 000
* “02” and “22” will never be reported. Channel/Zone 2 is a trouble indication only that will transmit only “62” and “72.”
30 150805
Troubleshooting
SECTION 7
TROUBLESHOOTING
7.1 System Messages
Table 7-1 shows the messages that could appear on the LCD of the model 5230 annunciator. If you have a
problem that is not covered here, contact Technical Support at 800-328-0103 for assistance.
Table 7-1: Explanations of Display Messages
Line 2: CALLING COMPUTER System is calling remote computer (for up- or downloading).
Line 2: REPORTING The system is reporting to the central station.
REPORTING An event is being reported to the central station.
SYSTEM NORMAL No trouble, alarm, or other condition exists.
TIME? The 5128/29 is in Time Set mode.
TROUBLE (line 1) Sprinkler supervisory trouble.
TROUBLE ZONE # (line 2)
TROUBLE (ZONE 1-4) A trouble condition exists in the indicated zone.
TROUBLE DIALER After making the programmed number of attempts, the dialer has not been able to
communicate with the central station. (This is a dialer failed condition.)
TROUBLE LINE 1 A trouble condition exists on phone line 1.
TROUBLE LINE 2 A trouble condition exists on phone line 2.
TRY AGAIN A keystroke error has been made. Press CLEAR and enter the correct keystrokes.
Note: When step programming mode is in use and the 5230 annunciator powers up, the LCD displays messages that
describe conditions currently in effect.
7.2 Silencing Troubles
The built-in audible trouble buzzer can be silenced by pressing the silence button (see Figure 3-1).
Note: Silencing a trouble condition does not correct the trouble condition. The trouble buzzer will re-activate every 24
hours if the trouble condition remains uncorrected or if a new trouble condition occurs.
150805 31
Model 5128/29 Fire Slave Communicator Installation Manual
32 150805
Silent Knight Fire Product Warranty and Return Policy
150805 33
Model 5128/29 Fire Slave Communicator Installation Manual
• Customers without a Silent Knight account must use a MasterCard, Visa, or American
Express credit card to get an advance replacement.
• A new or refurbished board will be shipped to the customer. The customer will initially be
billed for the replacement board but a credit will be issued after the repairable board is
received at Silent Knight. All returned products must comply with the guidelines described
under “General Terms and Conditions”.
• The defective board must be returned within 30 days of shipment of replacement board for
customer to receive credit. No credit will be issued if the returned board was damaged due to
misuse or abuse.
• Repairs and returns should be sent to:
Silent Knight
Attn: Repair Department
7550 Meridian Circle Suite 100
Maple Grove, MN 55369-4927
RA Number:___________________
Limited Warranty
Silent Knight warrants that the products of its manufacture shall be free from defects in materials
or workmanship for 18 months from the manufacturing date code on the printed circuit board, if
such goods have been properly installed, are subject to normal proper use, and have not been
modified in any manner whatsoever. Upon return of the defective product, Silent Knight will at its
sole discretion, either repair or replace, at no cost, such goods as may be of defective material or
workmanship. Customers outside the United States are to return products to their distributor for
repair.
SILENT KNIGHT SHALL NOT UNDER ANY CIRCUMSTANCES BE LIABLE FOR ANY
INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING FROM LOSS OF PROPERTY
OR OTHER DAMAGE OR LOSSES OWING TO THE FAILURE OF SILENT KNIGHT
PRODUCTS BEYOND THE COST OF REPAIR OR REPLACEMENT OF ANY DEFECTIVE
PRODUCTS.
SILENT KNIGHT MAKES NO WARRANTY OF FITNESS OR MERCHANTABILITY AND
NO OTHER WARRANTY, ORAL OR WRITTEN, EXPRESS OR IMPLIED, BEYOND THE 18
MONTH WARRANTY EXPRESSLY SPECIFIED HEREIN.
34 150805
7550 Meridian Circle
Maple Grove, MN 55369-4927
763-493-6455
1-800-328-0103
Fax: 763-493-6475
Trim Line