Seven-Storey Office Building: 1 1.1 Arrangement and Loading
Seven-Storey Office Building: 1 1.1 Arrangement and Loading
1
Example 2 Seven storey office building Sheet 2 of 26 Rev
2
A B C D E F
9000 9000 9000 9000 9000
Figure 1.1
1
6000
4000 4000
356x171x57 UB
356x171x57 UB
356x171x57 UB
356x171x57 UB
305 x 165 x 46 UB
2
3000
9000
457x191x98 UB
457x191x98 UB
457x191x98 UB
457x191x98 UB
6000
3
356x171x57 UB
356x171x57 UB
356x171x57 UB
356x171x57 UB
4
N.B. All secondary beams 305 x 165 x 46 UB
The Steel Construction Institute Seven Storey Building FMS 11766 10/12/04
Silwood Park Ascot Berks SL5 7QN Typical Steelwork Layout WIS
Tel (01344) 623345 Fax (01344) 622944
Floors 1 - 6 and Roof
BCF951/03
Sheet
3 of 26
Rev
1 2 3 4
6000 9000 6000
26.25 m
Figure 1.2
22.53 m
18.81 m
15.09 m
11.37 m
7.65 m
4
3.93 m
0.0 m 500
Figure 1.3
9000 9000 9000 9000 9000
6000
5
6000
Figure 1.4
22.53 m 900
900 2820
18.81 m
15.09 m
Elevation on gridline 4
11.37 m
Example 2 Seven storey office building
7.65 m
6
3.93 m
3030
0.00 m
7
Example 2 Seven storey office building Sheet 8 of 26 Rev
The expression for fi depends on which expression in EN 1990 has been used
to calculate the design value of the combination of actions. In this example,
expression 6.10 will be used, and therefore expression 2.5 of EN 1993-1-2 must
be used to calculate fi.
According to expression 6.10, the design value of the combination of actions is EN 1990
given by: Expression 6.10
Ed = 1.35 × 4.41 + 1.5 × 3.3 = 10.9 kN/m2
Gk fiQk,1 4.41 0.5 3.3 EN 1993-1-2
and fi = = = 0.556 2.4.2(2)
G Gk Q,1Qk,1 1.35 4.41 1.5 3.3
Expression 2.5
Thus the design effects in fire are given by:
Ed,fi = fi Ed = 0.556 × 10.9 = 6.1 kN/m
In this instance, the two alternative approaches to determine the design load in
fire produce the same result.
The design value of the point load applied by the secondary beams at the mid
span of the primary beam is given by:
6.1 × 3 × 9 = 164.7 kN
Design bending moment at mid span of the primary beam:
MEd = 164.7 6/4 = 247.1 kNm
Design shear force at the support:
VEd = 164.7 /2 = 82.4 kN
1.3.3 Critical temperature of the protected beam
The critical temperature for the beam may be calculated and a protection
system chosen to ensure that the steel remains below this temperature. This
approach is simple and conservative. This example demonstrates the calculation
of the critical temperature, but then continues to determine the actual
temperature of the beam with a specific protection system and to calculate the
resistance of the beam at that temperature.
The critical temperature, a,cr is given by: EN 1993-1-2
4.2.4(2)
1
a,cr = 39.19 ln 3.833
1 + 482
0 .9674 0
where the degree of utilisation, o, is given by:
E fi, d EN 1993-1-2
o = but not less than 0.013 4.2.4(3)
R fi, d,0
M,fi
0 fi
M0
8
Example 2 Seven storey office building Sheet 9 of 26 Rev
9
Example 2 Seven storey office building Sheet 10 of 26 Rev
For this fire protection board selected, the manufacturer provided the
following data:
Thermal conductivity p = 0.2 W/mK
Thickness dp = 20 mm
Density p = 850 kg/m3
Specific heat cp = 1700 J/kgK
internal surface area of boarding EN 1993-1-2
Ap 172.2 2 358
= = = 122.3 m–1 4.2.5.2(4)
V volume of member 7.26
10
Example 2 Seven storey office building Sheet 11 of 26 Rev
Figure 1.5 Variation of gas and steel temperatures with time – protected beam
11
Example 2 Seven storey office building Sheet 12 of 26 Rev
12
Example 2 Seven storey office building Sheet 13 of 26 Rev
bo hsc
kl 0.6 1 but ≤ 1.0
hp hp
where
bo is the distance between ribs, in this case 110 mm
hp is the height of the profile, in this case 51 mm
hsc is the height of the shear connector, in this case 95 mm
110 95
Then k l 0.6 1 = 1.11, but limited to 1.0
51 51
Thus the minimum resistance, at ambient temperature, = 1.0 × 73.1 = 73.1 kN
13
Example 2 Seven storey office building Sheet 14 of 26 Rev
0.8 450 π 19 2 4
Thus Pfi,Rd = 0.8 × 0.846 × 10 3 = 69.1 kN
1.0
The temperature of the concrete = 0.4 × 588 = 235°C
Although clause 4.3.4.2.2(16) indicates that no reduction is required for
temperatures less than 250°C, Table 3.3 indicates a small reduction.
From Table 3.3, kc, = 0.915 EN 1994-1-2
Table 3.3
0.29 1 19 2 25 30500
Thus Pfi,Rd = 0.915 10 3 = 83.5 kN
1.0
Thus the minimum resistance, at elevated temperature, = 69.1 kN
The number of studs over half the span, allowing for 300 mm at the ends of the
beam = (3000-300)/150 = 18 studs
Thus the maximum force that can be transferred by the studs is
18 69.1 = 1244 kN
Thus the maximum force in the concrete is the minimum of 1244 kN and
1012 kN.
Therefore the force in the concrete = 1012 kN
14
Example 2 Seven storey office building Sheet 15 of 26 Rev
where:
0.5
250
d slab
51 is the temperature at 51 mm within a rib
dslab is the slab depth
At other locations, the concrete temperature is given by: PN005c-GB
Table 2.11
x = 0.0162.8(x – dp) – 6.51.28(x – dp) + 700
where:
dp is the height of the profile, in this instance 51 mm
The graph of these expressions is shown in Figure 1.6.
Concrete Slab Temperatures
90 Minutes, Normal Weight Concrete
1200
1000
Within rib
Concrete Temperature (0C)
Other locations
800
600
400
200
0
0 20 40 60 80 100 120 140
Distance from soffit (mm)
A reduction factor, kc, may be obtained from Table 3.3 of EN 1994-1-2 EN 1994-1-2
3.2.2(4)
The concrete temperature, and the reduction factor kc,, for concrete strips at Table 3.3
distances measured from the top surface of the slab, are shown in Table 1.3. The
datum used when calculating the temperature is taken as the mid-height of the
strip. The temperatures in Table 1.3 are the higher values shown in Figure 1.6,
indicated as “other locations”. These are temperatures in the slab above the
dovetail void, and correspond to positions P4 to P5 in PN005c-GB, Figure 2.4.
15
Example 2 Seven storey office building Sheet 16 of 26 Rev
Table 1.4 Resistance of the concrete slab, in strips from the upper surface
Strip Resistance (kN) Cumulative resistance (kN)
0 – 10 mm 318.8 318.8
10 – 20 mm 318.8 637.5
20 – 30 mm 276.3 913.8
30 – 40 mm 257.3 1171.1
In this example, only 33.8 mm of the concrete slab is required to equate to the
tension force previously determined as 1012 kN.
Thus the plastic neutral axis is at 33.8 mm from the top surface of the slab.
The design moment resistance of the composite beam at elevated temperature is EN 1994-1-2
given by the summation of the design forces, multiplied by their lever arms, as 4.3.1(5)
shown in Figure 1.7.
16
Example 2 Seven storey office building Sheet 17 of 26 Rev
33.8mm
275.2 mm
1012 kN
Most of the required information has been determined for the primary beam,
which is utilised within the following verification of a secondary beam.
17
Example 2 Seven storey office building Sheet 18 of 26 Rev
Following the pattern of Sections 1.3.2 and 1.3.4, an incremental process may be
used to determine the temperature of the steel beam after 90 minutes. Like the
primary beams, 20 mm of identical fire protection has been assumed. The results
of this incremental process are shown in Figure 2.1. At 90 minutes, the
temperature of the steel beam is 606°C.
This is higher than the critical temperature calculated in Section 1.3.3 as 567°C
and would indicate that the chosen protection is not adequate. However, the
critical temperature approach is conservative, and this example continues in
order to demonstrate that the calculated resistance of the composite beam with
the selected protection system is adequate.
1200
Gas temperature
1000 Steel temperature
Required fire period
Gas and Steel temperatures (oC)
800
600
400
200
0
0 10 20 30 40 50 60 70 80 90 100
Minutes
Figure 2.1 Variation of gas and steel temperatures with time – protected beam
18
Example 2 Seven storey office building Sheet 19 of 26 Rev
When the decking is transverse to the span, the calculated resistances must be EN 1994-1-1
multiplied by the reduction factor kt, as given by: 6.6.4.2
0.7 bo hsc
kt 1
nr hp hp
where:
nr is the number of studs in one rib (assumed here to be 1)
bo is the clear distance between ribs, given by the manufacturer as
110 mm
hsc is the height of the stud (95 mm in this instance)
hp is the height of the profile, given by the manufacturer as 51 mm
0.7 110 95
Then k t 1 = 1.3
1 51 51
kt is also limited by the maximum value given in Table 6.2, and for the deck EN 1994-1-1
(assumed to be less than 1 mm thick), for through-deck welding, the maximum Table 6.2
value is 0.85
Thus the revised values of resistance are:
From expression 6.18, PRd = 81.7 × 0.85 = 69.5 kN
From expression 6.19, PRd = 73.1 × 0.85 = 62.1 kN
19
Example 2 Seven storey office building Sheet 20 of 26 Rev
Thus the maximum force in the concrete is the minimum of 1639 kN and
959 kN.
Therefore the force in the concrete = 959 kN
Table 2.1 Resistance of the concrete slab, in strips from the upper surface
Strip Resistance (kN) Cumulative resistance (kN)
0 – 10 mm 478.1 478.1
10 – 20 mm 478.1 956.3
20 – 30 mm 414.5 1370.7
20 mm
263.3 mm
959 kN
20
Example 2 Seven storey office building Sheet 21 of 26 Rev
21
Example 2 Seven storey office building Sheet 22 of 26 Rev
The reduction factor for design load level in the fire situation is given by: EN 1993-1-2
2.4.2(3)
Gk fiQk,1
fi = Expression 2.5
G Gk Q,1Qk,1
Hence:
Nfi,Ed = 0.55 NEd = 0.55 4429 = 2436 kN
235 235
Thus 0.85 0.85 0.7 (fy = 345 N/mm2, since 16 < tf < 40)
fy 345
22
Example 2 Seven storey office building Sheet 23 of 26 Rev
For intermediate storeys of a braced frame with separate fire compartments, the EN 1993-1-2
buckling length may be taken as lfi = 0.5L. Therefore: 4.2.3.2(5)
where:
1 93.9 93.9 235 / 355 = 76.4
θ
k y,θ / k E,θ 0.5
Reduction factor fi
The reduction factor for buckling at elevated temperature, fi, is given by:
fi = min (y,fi, z,fi)
For this section, with the same buckling length and restraint conditions in both EN 1993-1-2
axis, it is clear by inspection that buckling in the minor axis will be critical and 4.2.3.2
only this axis needs to be considered. To determine the reduction factor:
1. The non-dimensional slenderness is calculated (at ambient temperature).
2. The reduction factors ky, and kE, are determined from Table 3.1 of
EN 1993-1-2.
3. The non-dimensional slenderness at elevated temperature is calculated:
z,θ z k y,θ / k E ,θ 0.5
4. ϕθ is calculated, given by:
ϕθ = 1
2
1 θ θ
2
where 0.65 235/ f y
23
Example 2 Seven storey office building Sheet 24 of 26 Rev
24
Example 2 Seven storey office building Sheet 25 of 26 Rev
1200 6000
1000 5000
Gas and Steel temperatures (0C)
800 4000
Design resistance (kN)
600 3000
Gas temperature
Steel temperature
400 Point of failure 2000
Critical temperature
Design resistance (kN)
200 1000
Fire load (kN)
0 0
0 10 20 30 40 50 60 70 80 90 100
Minutes
Figure 2.3 Variation of gas temperature, steel temperature and design resistance with time
– unprotected column
25
Example 2 Seven storey office building Sheet 26 of 26 Rev
1000 5000
Gas and Steel temperatures (oC)
800 4000
Design resistance (kN)
600 3000
Figure 2.4 Variation of gas temperature, steel temperature and design resistance with time
– unprotected column
26