RET670 Typical Functions: Sample Specifications
RET670 Typical Functions: Sample Specifications
SA M P LE SP E C I FI CAT I O N S
RET670
RET670 typical functions
The IED shall comprise hardware, time synchronization, monitoring, communication capabilities and other
specifications as described in the 1MRG033843_en_Sample_specification_General_specifications_Relion_670
document. For the common protection, control, monitoring functionalities please refer to
1MRG033842_en_Sample_specification_Common_functions_Relion_670 document.
The IED shall support protection and control functionality. Control functionalities are described in
1MRG033840_en_Sample_specification_Bay_control_REC670.
For a complete overview of the functions available in this device, please refer to the Product Guide. For more
details about the design of the functions and their applications, please refer to the Technical Manual and the
Application Manual respectively.
The functions listed below are most typically specified in RET670, but are available for selection in other types
as well, as per the comments under each description.
The bias current shall be the highest measured current in case of a single breaker arrangement, or the highest
measured or calculated – as a vector summation from the CTs on the same side of the transformer – in case of
a multi-breaker arrangement.
The differential operate characteristic shall have two main areas: the restrained area, and the unrestrained
area.
The restrained area shall contain three sections. The first section shall have the constant operating
level independent of the bias current; the remaining two sections shall have settable slopes.
The unrestrained level shall have a constant pickup value, irrespective of the bias current, and shall be
selectable from 1 up to 100 times of the base current.
If a substantial amount of the second or fifth harmonic is detected, the restrained operation of the
function shall be blocked; levels of second or fifth harmonic required for blocking the operation shall
be settable by the end user.
If the operating point is above the unrestrained level, the function shall issue a trip signal without
consideration of any type of restrain. It shall be possible for the unrestrained characteristic to be re-
leased or blocked by any kind of logic created by the end user.
The function shall include the capacity to recognize a switch-onto-fault condition inside the differen-
tial protection zone, in which case it shall allow the differential protection to trip, even if the second
or fifth harmonic content of the differential currents is enough to block the operation of the func-
tion. This switch-onto-fault option shall be configurable by the end user.
If any blocking condition is detected in one phase, then the end user shall have the flexibility to block
the operation of the differential protection only in that phase, or in all three phases. This feature shall
be settable by a parameter setting.
1 MRG0338 47 B 1 /8
R ET67 0
In addition, the transformer differential protection shall include the following features:
It shall be possible for the differential protection to temporarily desensitize during external faults, by
adding a DC component to the pickup level of the protection. The DC component shall be extracted
from the measured instantaneous differential currents, and the highest DC in all three phases shall
be selected for addition to the pickup level; this feature shall be settable by a parameter setting.
The function shall be able to calculate the fundamental frequency negative sequence differential cur-
rent, and it shall be possible to record this in the disturbance recorder, reported as a service value.
The function shall include an internal/external fault discriminator based on the negative sequence currents.
This feature shall be settable by the end user. It shall have a settable minimum amount of the negative se-
quence current required for the calculation, as well as the angle defining the area in which negative sequence
current phasors have to be positioned in order to declare an internal or external fault. This function shall be
well coordinated with other features of the differential protection, in order to provide more stability and de-
pendability for internal faults, external faults, and evolving faults.
This function shall include an additional feature for detecting low turn-to-turn faults based on nega-
tive sequence current, and this feature shall be able to issue a trip without the operating point being
in the restrained or unrestrained area.
The function shall be able to detect an open CT circuit, and consequently block the operation of the
transformer differential protection; it shall be possible for this signal to be recorded in the disturb-
ance recorder and reported, a functionality that shall be settable by the user. The configuration shall
also enable the end user to trip the breaker with the CT open detection signal, while blocking the dif-
ferential protection.
The function shall be able to receive the position of the on-line tap changer (OLTC), for all OLTCs
used for voltage regulation on the power transformer, in order to dynamically adjust the ratio of the
power transformer inside the differential protection algorithm. If there is an internal failure in the
OLTC, or an error in reporting the correct OLTC position, differential protection shall be able to rec-
ognize this and revert to a safe pickup level.
The function shall continuously monitor the fundamental frequency differential current level, and in
the event all three differential currents are above the set threshold, and after a set time delay, an
alarm shall be issued. The value of the threshold and the time delay for the differential protection
alarm shall be settable by the end user.
[OPTIONAL] The IED can be specified with up to two transformer differential protection functions, in order to
protect two transformers with one IED.
In 670 series, this function is available in the following product types: REG670 and RET670.
It shall be possible to release or to block the function by any kind of logic created by the end user.
The operating characteristic shall contain three sections. In the first, the constant operating level shall be inde-
pendent from the bias current, while the remaining two sections shall have slope.
The protection shall have an internal/external fault discriminator based on zero-sequence currents, and this
functionality shall be automatically activated if the residual current measured is at least 3% the base current. It
shall have a settable angle defining an area in which zero sequence current phasors have to be positioned in
order to declare an internal or external fault.
The protection shall be able to cause a trip if the differential current is in the operating area while residual cur-
rent is less than 3% the base current.
The REF protection shall be able to calculate the second harmonic content of the neutral current. If the ratio
between second harmonic and fundamental frequency exceeds 60%, REF protection shall be blocked.
In 670 series, this function is available in the following product types: RED670, REG670 and RET670.
1 MRG0338 47 B 2 /8
R ET67 0
The function shall be provided with three-phase currents from both sides of the protected transformer, as well
as with a single-phase or three-phase voltage input, from each side of the protected transformer.
The function shall be self-adaptive in a way that it shall be able to calculate and use the actual transformation
ratio and phase-angle shift across the protected PST/PAR, by using current and voltage measurements only.
The function shall be able to operate correctly without receiving the position of built-in on-load tap changers,
as well as without any external auxiliary (interposing) current transformers.
The differential operate characteristic of the protection shall have two main areas: the restrained area, and the
unrestrained area. The restrained area shall contain three sections. The first section shall have the constant
operating level independent of the bias current; the remaining two sections shall have settable slopes.
It shall be possible for the protection to temporarily desensitize during external faults, by adding a DC compo-
nent to the pickup level of the protection. The DC component shall be extracted from the measured instanta-
neous differential currents, and the highest DC in all three phases shall be selected for addition to the pickup
level; this feature shall be settable by a parameter setting.
This function shall include an additional feature for detecting low turn-to-turn faults based on negative se-
quence current, and this feature shall be able to issue a trip without the operating point being in the re-
strained or unrestrained area.
Overexcitation protection
The function shall be able to measure voltage and current, and shall have settable leakage reactance in primary
ohms, in order to be able to calculate induced voltage.
The function shall be capable of working without current measurement, in which case measured voltage shall
be assumed induced voltage.
The function shall have the option to choose an IEEE-defined curve that relates V/Hz ratio to operate time de-
lay, or alternatively, to create an arbitrary or tailor-made curve. The minimum trip time delay, maximum trip
time delay, transformer magnetic core cooling time constant, alarm level and alarm time delay shall be setta-
ble by the end user.
For the IEEE curve, the time multiplier shall be settable by the end user.
For the tailor-made curve, six separate time delays shall be settable by the end user.
In 670 series, this function is available in the following product types: RED670, REG670, REL670 and RET670.
The function shall include the following built-in features. It shall be possible to enable or disable each one, and
to release or block each one separately, by any kind of logic created by the end user:
overcurrent stage, with a settable level for the pickup level and the operation time delay
undercurrent stage, with a settable level for the pickup level and the operation time delay
reconnection inhibit, with a settable value of current below which the SCB is considered discon-
nected, and the time delay for the capacitor bank voltage to discharge to <5% of the base voltage
1 MRG0338 47 B 3/ 8
R ET67 0
harmonic overload with two stages; the first stage shall be based on inverse time delay (IDMT) with a
settable time multiplier, and the second stage shall be based on definite time delay (DT), with a set-
table time delay; each stage shall have a settable pickup level
reactive power overload, with a settable level for the reactive power overload pickup and the opera-
tion time delay
For the overcurrent, undervoltage, harmonic overload and reactive power protection features, the function
shall be able to report pickup/start signals per phase.
This function is available in the following product types: REB670, REC670, and RET670.
It shall be possible to block the calculation of the function, for example during the internal faults, or during
transformer energization inrush.
Function shall also report last fault duration, overall number of faults detected, maximum through fault I2t in %
of set limit, and maximum cumulative through fault I2t in % of set limit.
The function shall have an external input, which can be used as a trigger in order to capture the instantaneous
values in the system.
It shall be possible to export the report from the function in XML format.
This function is available in the following product types: REC670, RED670, REG670, REL670 and RET670.
The function shall be able to receive information about pressure and temperature of the gas medium directly
from the circuit breaker sensors, using mA inputs. The function shall be able to issue temperature and pres-
sure alarms, as well as lockout, based on evaluation of measured values and the settable thresholds. The func-
tion shall be able to receive binary information about pressure alarms and lockouts.
In 670 series, this function is available in the following product types: REB670, REC670, RED670, REG670, REL670, RES670 and
RET670.
The function shall be able to receive information about temperature of the oil medium directly from the trans-
former sensors, using mA inputs. The function shall be able to issue temperature and pressure alarms, as well
as lockout, based on evaluation of measured values, input values, and the settable thresholds. The function
shall be able to receive binary information about temperature alarms and lockouts.
In 670 series, this function is available in the following product types: REB670, REC670, RED670, REG670, REL670, RES670 and
RET670.
It shall be possible for the function to calculate the oil and winding time constants based on settable trans-
former parameters, or to insert the oil and winding time constants directly as the parameter settings.
1 MRG0338 47 B 4/8
R ET67 0
Ambient temperature shall be provided to the function through a sensor, or it shall be settable as a monthly
average ambient temperature.
The function shall calculate loss-of-life in the form of days and years. This information shall be updated at set-
table intervals, hourly or daily. The transformer winding percentage loss-of-life shall be calculated every day,
and the information shall be provided as a total percentage loss-of-life from the installation date, and as a
yearly percentage loss-of-life.
It shall be possible for the function to use transformer parameters defined according to IEC 60076-7 standard
or IEEE C57.96-1995 standard. This selection shall be settable by the end user.
This function is available in the following product types: REC670, REG670 and RET670.
The IED shall have the functionality of automatic voltage control for the single transformer. The main principle
of this function shall be to measure the voltage, compare it to the set voltage, and then take appropriate ac-
tion.
by a parameter setting
The function shall be able to measure any phase or line voltage, or positive sequence voltage. This selection
shall be available via a parameter setting. The voltage deadband values, based on the difference between
measured and the set voltage, shall be settable by the end user.
The control mode of the voltage control shall be manual and automatic. The switching between manual and
automatic control shall be possible from:
LHMI
In the event of manual control, the tap changer shall be operated from the LHMI or from a remote place, re-
specting the hierarchy of the control in the bay.
The function shall include automatic overcurrent blocking of the automatic voltage control. The threshold used
for blocking shall be settable by the end user.
The undervoltage limit for blocking the operation shall be settable by the end user.
Blocking due to a reverse action of the tap changer, with the respective time setting for the duration of the
blocking signal, shall be settable by the end user.
Functionality shall be available to generate an alarm when voltage control gives an abnormal number of com-
mands or an abnormal sequence of commands within a predefined period of time (hunting detection), with
available settings for the number of operations in one hour, the number of operations in one day, time window
for detection, and the maximum number of the operations within the time window.
The function shall include alarms for a settable amount of active and reactive power in both directions, with a
settable time delay for an alarm.
The function shall include two separate time stages, defining the time that elapses between the moment when
the measured voltage exceeds the deadband interval, until the appropriate command is initiated. The first
time stage shall define the time delay for the first command to occur in one direction. It shall have a definite or
inverse time characteristic, and shall be settable by the end user. The second time stage shall be used for the
consecutive commands in the same direction as the first command. The characteristic and the time setting for
the second stage shall be settable by the end user.
1 MRG0338 47 B 5 /8
R ET67 0
The function shall include line voltage drop compensation to control the voltage closer to the load point, utiliz-
ing the measured voltage and current from the low voltage side of the power transformer in the combination
with line reactance and resistance. Setting for the capacitive load shall also be available, in the event voltage
closer to the load has a higher magnitude than the voltage on the secondary side of the power transformer.
The function shall include load voltage adjustment functionality with two alternatives. One alternative shall
offer automatic load voltage adjustment proportional to the load current, with the available setting for the
automatic load voltage adjustment in a percentage of the base voltage. The other alternative shall offer a con-
stant load voltage adjustment with four different adjustment factors that are settable by the end user, applied
via binary inputs, through the local LHMI or customized logic, or by an IEC 61850 MMS client.
It shall be possible for the end user to define alarms or the blocking of OLTC control for the following condi-
tions:
command error
overcurrent detection
overvoltage detection
reverse action
undervoltage detection
The function shall be able to receive the position of the OLTC via mA input, or via binary inputs. If the position
is received via binary inputs, the following types of code conversion shall be available to the end user: BIN,
BCD, Gray, and Single.
The pulse duration for the command to the tap changer shall be settable by the end user.
A counter that represents the remaining number of operations (decremental counter) at rated load and the
number of operations shall be available within the function. Both counters shall be stored in non-volatile
memory and include the times and dates of their last reset. These dates shall be stored automatically when the
command to reset the counter is issued.
The IED shall be capable of providing control for up to four parallel tap changers in one single device. The IED
shall be capable of providing control for up to eight parallel tap changers in a group using between two and
eight devices of the same type, applying IEC 61850-8-1 GOOSE communication between the devices. In case of
different set voltages, the IEDs shall be able to calculate the mean set voltage value, or use the respective set
voltage values. This shall be available via a parameter setting.
The function shall have three alternative parallel control methods, settable by the end user: master-follower,
circulating current, and the reverse reactance method.
For the master-follower method, a settable parameter shall determine whether the followers follow the posi-
tion or the command of the master.
For the circulating current method, it shall be possible to manually control the transformers as a group, if one
of the transformers in the group is in the manual mode, and the others are in the automatic mode. In this case,
transformers in the automatic mode shall adapt to the manual tapping of the transformer that has been put in
manual mode. The adapt mode shall be settable by a parameter.
For both the circulating current method and the master-follower method, it shall be possible to alarm only, or
block automatic control, or block both automatic and manual control of the tap changer in the event of high
circulating current. The threshold for the circulating current, and the timer delay for alarm or blocking, shall be
settable by the end user.
The function shall be able to alarm or block the automatic control of the tap changer in the event of different
tap positions, if the master-follower method is used.
1 MRG0338 47 B 6/ 8
R ET67 0
It shall be possible for the function to enable or disable simultaneous tapping via a parameter setting.
When the transformer is disconnected on the low-voltage side, it shall be possible for the function to follow
the voltage regulation of loaded parallel transformers, and thus be on a proper tap position when the low-volt-
age circuit breaker closes. This functionality shall be available both for the circulating current method and for
the master-follower method.
It shall be possible for the function to issue an alarm in case the voltage measurement in one transformer bay
deviates to the mean value of all voltage measurements in the parallel group. The deviation of the measured
voltage, as well as the time delay for the alarm, shall be settable by the end user.
For the master-follower method, a predefined offset of the tap position can be defined between the followers
and the master, settable via a parameter. A separate setting shall be available that shall alarm, after the setta-
ble time, in case the offset between a follower and the master is equal or greater than the set value.
In 670 series, this function is available in the following product types: REC670 and RET670.
The automatic voltage control for parallel transformers is available only in 670 series.
1 MRG0338 47 B 7/ 8
q
abb.com/protection-control
1 MRG0338 47 B 8 /8