0% found this document useful (0 votes)
68 views6 pages

Pages From Curtain Wall (BD Submission) - 3

This document discusses structural analysis of the Tai Wai Station Property Development project. It examines load cases for wind loads, live loads 1-3, and performs checks for bending and deflection under wind loads. The maximum bending stress and deflection were found to be below specified limits.

Uploaded by

Con Can
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
68 views6 pages

Pages From Curtain Wall (BD Submission) - 3

This document discusses structural analysis of the Tai Wai Station Property Development project. It examines load cases for wind loads, live loads 1-3, and performs checks for bending and deflection under wind loads. The maximum bending stress and deflection were found to be below specified limits.

Uploaded by

Con Can
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Project: Tai Wai Station Property Development

WAH 華東幕牆工程有限公司 in STTL No. 520


Wah Tung facade Company
T&N Limited
Prepared: Date: 19-Jul-18
Checked: File: Page: 8

Load case - WIND


Project: Tai Wai Station Property Development
WAH 華東幕牆工程有限公司 in STTL No. 520
Wah Tung facade Company
T&N Limited
Prepared: Date: 19-Jul-18
Checked: File: Page: 9

Load case - LIVE1


Project: Tai Wai Station Property Development
WAH 華東幕牆工程有限公司 in STTL No. 520
Wah Tung facade Company
T&N Limited
Prepared: Date: 19-Jul-18
Checked: File: Page: 10

Load case - LIVE2


Project: Tai Wai Station Property Development
WAH 華東幕牆工程有限公司 in STTL No. 520
Wah Tung facade Company
T&N Limited
Prepared: Date: 19-Jul-18
Checked: File: Page: 11

Load case - LVIE3


Project: Tai Wai Station Property Development
WAH 華東幕牆工程有限公司 in STTL No. 520
Wah Tung facade Company
T&N Limited
Prepared: Date: 19-Jul-18
Checked: File: Page: 12

* Check for bending (WIND load)

(Refer to appendix A, Load case - WIND)

Max. non-factored bending stress, fb = 23.6 MPa < 50MPa OK


Project: Tai Wai Station Property Development
WAH 華東幕牆工程有限公司 in STTL No. 520
Wah Tung facade Company
T&N Limited
Prepared: Date: 19-Jul-18
Checked: File: Page: 13

* Check for deflection

(Refer to appendix A, Load case - WIND)

Max. deflection, d= 16.2 mm

Limiting deflection, = L / 60
= 2200 / 60
= 36.7 mm > d = 16.2mm OK