1 Description: HP600ULX Access Control Power Supply/Charger PN 52392:B 3/5/13 ECN 13-222
1 Description: HP600ULX Access Control Power Supply/Charger PN 52392:B 3/5/13 ECN 13-222
1 Description
The HP600ULX is a 12VDC or 24VDC power supply with AC fail and Battery fail supervision. The unit has not been
evaluated as elevator equipment, and is not authorized for bell output in Mercantile applications.
2 Specifications
1. Input voltage: 120VAC 60Hz; Current: 2.50A max.
2. Output Voltage: 12VDC or 24VDC, jumper selectable; Current: 6.0A continuous output maximum plus battery
charger (not supervised).
3. Fail safe dry contact output on AC Failure (within one minute).
4. Built-in charger for sealed lead acid or gel cell type batteries.
5. Instantaneous transfer to stand-by battery on AC failure.
6. Battery presence detection (within 1 minute).
7. Battery low disconnect at 9.90VDC or 19.90VDC.
8. High voltage disconnect at 15VDC or 30VDC.
9. Yellow LED (L3) indication for battery disconnected and battery low.
10. Fail safe dry contact output for Battery trouble (Fail Safe).
11. Battery polarity reversal protection.
12. Thermal overload and short circuit protection.
13. DC output PTC activated indication by Red LED (L2).
14. DC output failure indication by Red LED ( L4 ).
15. AC presence indication by Green LED ( L1 ).
16. DC output indication by Red LED ( L5 ).
17. Battery Leads included.
18. Power Board Dimensions: 6.2”L x 4.7”W x 2.5”H.
19. Enclosure Dimension: 17.5”H x 13”W x 4.5”D. Accommodates two 12 Volt 12AH batteries. When using larger
batteries, a UL approved enclosure must be used.
3 Installation Instructions
1. Mounting
The power supply should be installed in accordance with all Governing National Electrical and Local Codes. Mount the
power supply securely in the desired location using the four (4) mounting holes.
2. Power Supply Input Connection
WARNING: To reduce risk of electric shock, do not expose unit to rain or excess moisture, and disconnect
!
power before servicing unit.
For continuous protection against hazard, replace fuses only with exact type and rating. A readily accessible
switched circuit breaker must be available to disconnect main power as required. All power limited wiring should
be routed so that it cannot touch non-power limited wiring; minimum spacing 1/4”. Installation and servicing
should only be made by qualified personnel; contains no user-serviceable parts. Install in accordance with all local
regulations and the National Electrical Code.
4 LED Operations
LED Number Power Board (status when lit)
L1 Green LED - AC present
L2 Red LED - PTC activated
L3 Yellow LED - Battery low or disconnected
L4 Red LED - Dc power failure
L5 Red LED - DC output present