Building Energy Modeling: An ASHRAE Certification Study Guide
Building Energy Modeling: An ASHRAE Certification Study Guide
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson Reuters (S
courses, and a certification program.
Excerpts of the relevant publications are included in the study guide, along with
the program’s full detailed content outline (DCO), which is a blueprint for the
certification examination, and a DCO matrix that serves as a road map for identifying
the essential resources for ASHRAE’s BEMP certification program. It lays out in a
single table which sections of the resources are applicable to the different sections
of the examination. As much as possible, this study guide identifies the specific
areas on the program’s DCO that each reference helps support.
This publication is also a valuable resource for any individual in the building
energy modeling field, whether aiming to be ASHRAE certified or not. Full of a
• Road map to prepare for ASHRAE’s BEMP certification
multitude of references, this guide serves as an indispensable source of information • Excerpts from ASHRAE resources for energy modeling
related to building energy modeling.
• Where to find other essential energy modeling guidance
• How each resource impacts energy modeling
ISBN 978-1-936504-19-0 • Review of resources needed for energy modeling practitioners
ASHRAE
1791 Tullie Circle
Atlanta, GA 30329-2305
Phone: (404) 636-8400 (worldwide)
www.ashrae.org 9 7 8 1 9 3 65 0 4 1 90 ASHRAE
Product code: 90287 1/12
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Building
Energy
Modeling
An ASHRAE Certification
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
Study Guide
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
Authors
Sean Harleman, PE
kW Engineering, Inc.
Member ASHRAE
Jonathan Schoenfeld, PE
kW Engineering, Inc.
Member ASHRAE
Warren Seto, PE
kW Engineering, Inc.
Member ASHRAE
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Building
Energy
Modeling
An ASHRAE Certification
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
Study Guide
ASHRAE
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
ISBN 978-1-936504-19-0
© 2011 ASHRAE
1791 Tullie Circle, NE
Atlanta, GA 30329
www.ashrae.org
Although the information and materials provided in ASHRAE publications have been prepared and selected
with care, ASHRAE has not investigated, and ASHRAE expressly disclaims any duty to investigate any
product, service, process, procedure, design, or similar aspects of a system that may be described therein.
The appearance of any technical data or editorial material in this publication does not constitute endorse-
ment, warranty, or guaranty by ASHRAE of any product, service, process, procedure, design, or the like.
ASHRAE does not warrant that the information in the publication is free of errors, and ASHRAE does not
necessarily agree with any statement or opinion in this publication. The entire risk of the use of any infor-
mation in this publication is assumed by the user.
No part of this publication may be reproduced without permission in writing from ASHRAE, except by a
reviewer who may quote brief passages or reproduce illustrations in a review with appropriate credit, nor
may any part of this publication be reproduced, stored in a retrieval system, or transmitted in any way or by
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
any means—electronic, photocopying, recording, or other—without permission in writing from ASHRAE.
Requests for permission should be submitted at www.ashrae.org/permissions.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Contents
Preface vii
Introduction ix
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
for Buildings Except Low-Rise Residential Buildings 7
ANSI/ASHRAE/IES Standard 100-2006, Energy Conservation
in Existing Buildings 27
ANSI/ASHRAE Standard 140-2007, Standard Method
of Test for the Evaluation of Building Energy Analysis
Computer Programs 31
ASHRAE Guideline 14-2002, Measurement of Energy
and Demand Savings 35
2009 ASHRAE Handbook—Fundamentals 41
Building Energy and Environmental Modelling, Applications
Manual AM11: 1998 (CIBSE) 51
IESNA Lighting Handbook, 9th Edition (IES) 55
Solar Radiation and Daylight Models, Second Edition, by T. Muneer
(Butterworth-Heinemann) 59
Heat and Mass Transfer in Building Services Design
by Keith J. Moss (Spon Press) 61
Mechanical and Electrical Equipment for Buildings, 11th Edition,
by Walter T. Grondzik, Alison G. Kwok, John S. Reynolds,
and Benjamin Stein (Wiley) 63
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Introduction
As interest in building sustainability has increased, so has interest in energy modeling as a
tool for achieving building energy savings. ASHRAE recognizes the importance of energy
modeling to the processes for designing, building, operating, and maintaining buildings and
facilities and thus has attempted to create a comprehensive package of resources that includes
publications, educational courses, and a certification program.
ASHRAE’s Building Energy Modeling Professional (BEMP) program was developed in
collaboration with the U.S. Affiliate of the International Building Performance Simulation
Association (IBPSA-USA) and the Illuminating Engineering Society of North America
(IES). It was designed and developed by subject matter experts and other stakeholders to
assess an individual’s mastery of the body of knowledge reflecting the best practices that a
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
competent professional obtains through education and experience. The purpose of the pro-
gram is to certify an individual’s ability to evaluate, choose, use, calibrate, and interpret the
results of energy modeling software when applied to building and systems energy perfor-
mance and economics and to certify an individual’s competence to model new and existing
buildings and systems with their full range of physics/operations.
While the best teacher of best practices is hands-on work experience, even the most sea-
soned professionals may want additional resources to support their knowledge bases. Building
Energy Modeling: An ASHRAE Certification Study Guide supplies this additional information
by delineating for practitioners the current editions of standards and other references neces-
sary for building energy modeling and assists in preparation for ASHRAE’s BEMP certifica-
tion. Note that purchasing this publication is not required for participation in the BEMP
certification program, and studying the materials in this publication will not guarantee that a
BEMP candidate will earn the certification.
Excerpts of the relevant publications are included in the study guide. For instances in
which a whole publication or a significant amount of published material is relevant to a topic,
the study guide provides an explanation of the publication’s relevance but does not reproduce
it in its entirety. Appendix A of this study guide provides the BEMP certification program’s
full detailed content outline (DCO), which is a blueprint for the certification examination. The
DCO identifies not only the tasks that a competent energy modeler should have mastered but
also how many examination items (out of 100) covering each task area will appear on the
examination. A DCO Matrix is included on the following pages. It serves as a road map for
identifying the essential resources for ASHRAE’s BEMP certification program. It lays out in a
single table which sections of the resources are applicable to the different sections of the
examination.
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Of course, each certification candidate has a unique combination of academic and work
experience. ASHRAE encourages each candidate to review the DCO and DCO Matrix to
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
viii
The following DCO Matrix is a road map for identifying the standards, guidelines, and other publications essential for practicing
building energy modeling. It lays out in a single table which sections of the resources are applicable to the different sections of
ASHRAE’s BEMP certification examination.
55-2010
62.1-2010
Standard 90.1-2010
Standard 100-2006
140-2007
14-2002
2009 ASHRAE Handbook
—Fundamentals
CIBSE Building Energy and
Environmental Modelling
IESNA Lighting
Handbook
Solar Radiation and
Daylight Models
Heat and Mass Transfer
in Building Service
Mechanical and
Electrical Equipment
No. of refs
Total items
ASHRAE Standard
ASHRAE Standard
ASHRAE/IES
ASHRAE/IES
ASHRAE Standard
ASHRAE Guideline
© ASHRAE (www.ashrae.org). For personal use only.
I. ESTABLISHING THE
17
MODELING SCOPE
A. Sect 11; Ch 1.2,
Modeling Objectives 3 Ch 19 Sect 2 4
App G 1.4
B. Sect
Sect 11;
Analysis Methodologies 8 5.1.1, Ch 19 Sect 4.1 4
App G
5.1.7
C. Sect 11;
Software and Tool Selection 4 Ch 19 Sect 4.1 3
App G
D. Project Scheduling and
2 0
Budget Considerations
II. COMPONENTS OF
BUILDING AND 48
ENERGY SYSTEMS
A. Location and
4 Sect 5.1.4 Ch 14 Ch 1 Ch 6 4
Climate Definition
B. Sect Ch 15,
Building Envelope Sect 5.1-5.6; Sect Sect
6 5.2.1, 25, 26, Ch 2-4 Ch 6, 7 7
and Partitions App C 6.2, 7.1 3.2.1
5.4 27
The items listed here may be abbreviated; refer to full DCO in Appendix A for detailed descriptions.
Building Energy Modeling: An ASHRAE Certification Study Guide
ix
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
x
DCO Matrix for ASHRAE’s BEMP Certification Examination
55-2010
62.1-2010
Standard 90.1-2010
Standard 100-2006
140-2007
14-2002
2009 ASHRAE Handbook
—Fundamentals
CIBSE Building Energy and
Environmental Modelling
IESNA Lighting
Handbook
Solar Radiation and
Daylight Models
Heat and Mass Transfer
in Building Service
Mechanical and
Electrical Equipment
No. of refs
Total items
ASHRAE Standard
ASHRAE Standard
ASHRAE/IES
ASHRAE/IES
ASHRAE Standard
ASHRAE Guideline
C. Sect
Sect 6.8; Sect Ch 16, Ch 9,
Building HVAC Systems 9 5.8, Sect 3.4 Ch 7-9 7
App G 6.3, 7.5 19 10
6.1-6.5
D. Sect 9.4, Ch 26, Ch 12,
Lighting Systems 3 Sect 6.6 Sect 3.3 Ch 8 6
9.5, 9.6 27 14
© ASHRAE (www.ashrae.org). For personal use only.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
DCO Matrix for ASHRAE’s BEMP Certification Examination
55-2010
62.1-2010
Standard 90.1-2010
Standard 100-2006
140-2007
14-2002
2009 ASHRAE Handbook
—Fundamentals
CIBSE Building Energy and
Environmental Modelling
IESNA Lighting
Handbook
Solar Radiation and
Daylight Models
Heat and Mass Transfer
in Building Service
Mechanical and
Electrical Equipment
No. of refs
Total items
ASHRAE Standard
ASHRAE Standard
ASHRAE/IES
ASHRAE/IES
ASHRAE Standard
ASHRAE Guideline
C. Evolution of Simulation Sect
Sect 11.3;
Techniques to Meet Project 2 4.4.3; Sect 6.3 Sect 5 4
App G
Methods and Objectives Annex 2
© ASHRAE (www.ashrae.org). For personal use only.
IV. INTERPRETATIONS OF
ENERGY MODEL 23
RESULTS
A. Verification and
Sect 11.3;
Troubleshooting of 7 Sect 4.4 Sect 6 Ch 19 Sect 5.5 5
App G
Simulation Results
B. Analyzing and Comparing Sect
8 Sect 5.5 Sect 4.1 Ch 19 Sect 5.5 5
Modeling Results 6.3.3.6
C. Sect Sect
Economic Analyses 3 6.8.4, 5.4.3, Ch 25 3
6.8.5 6.3.3.2.2
D. Sensitivity Analyses 2 Sect 6.3 Ch 19 Sect 2.4 3
E. Sect 11.1.5;
Project Deliverable 3 Sect 2 2
App G.1.4
The items listed here may be abbreviated; refer to full DCO in Appendix A for detailed descriptions.
Building Energy Modeling: An ASHRAE Certification Study Guide
xi
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
ANSI/ASHRAE
Standard 55-2010
Thermal Environmental Conditions
for Human Occupancy
RESOURCE DESCRIPTION
The 2010 edition of ANSI/ASHRAE Standard 55 combines Standard 55-2004 and the ten
approved and published addenda to the 2004 edition into one easy-to-use, consolidated stan-
dard. The standard outlines conditions for environmental thermal acceptability. It is intended
for use in design, commissioning, and testing of buildings and other occupied spaces and
HVAC systems and for the evaluation of thermal environments.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
on six key parameters: metabolic rate, clothing insulation, air temperature, radiant tem-
perature, air speed, and humidity. Although the metabolic rate and clothing insulation are
not generally inputs to most energy models, the energy modeler must make assumptions
about these values for the building or space of interest in order to estimate the bounds of
the other four parameters. Building energy models must then show that the air tempera-
ture, humidity, and sometimes radiant temperature and air speed in the occupied space
meet the specifications of this standard to ensure occupant thermal comfort is achieved.
DCO Item(s):
II.B. Building Envelope and Partitions
ASHRAE Standard 55-2010 discusses the effect of the interior surface temperature on
occupant comfort. Section 5.2.1 defines the comfort zone, given various parameters as the
bounds of the operative temperature. The operative temperature as described in Section 5.4 “is
the average air temperature and the mean radiant temperature weighted, respectively, by the
heat transfer coefficient for the occupant.” The mean radiant temperature, also defined in Sec-
tion 5.4, is akin “to a spatial average of the temperature of the surfaces surrounding an occu-
pant weighted by their view factors with respect to the occupant.” The building energy
modeler must not ignore interior surface temperatures, because they impact the thermal com-
fort of the occupants.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
DCO Item(s):
II.H. Controls
Standard 55-2010 has identified six primary factors that affect occupant comfort. Three of
these factors are controlled to some extent in most occupied spaces: air temperature, humidity,
and air speed.
As described previously, Section 5.2.1 defines the comfort zone, given various parameters as
the bounds of the operative temperature. The operative temperature is described in Section 5.4 as
“the average air temperature and the mean radiant temperature weighted, respectively, by the
heat transfer coefficient for the occupant.” Air temperature is described in Section 5.4 as “the
average temperature of the air surrounding the occupant.” To maintain occupant comfort, the
operative temperature should be maintained within the bounds established using the predictive
mean vote (PMV) model described in Section 5.2.12. Output of the model is shown in
Figure 5.2.1.1 for typical parameters of clothing insulation, air speed, and metabolic rate. The
building energy modeler must be able to understand and interpret Standard 55-2010 to ade-
quately determine the bounds of the operative temperature required for the building of interest.
Section 5.2.5 governs the change in air temperature over time. Standard 55-2010 sets an
allowable cyclic variation (at periods less than 15 minutes) of no greater than 2°F
(Table 5.2.5.1). In addition, this section also defines the maximum temperature drift over time
in Table 5.2.5.2. The temperature change depends on the total time in which the change
occurs. The building energy modeler must not only ensure the HVAC system can control the
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
air temperature within the bounds specified by Standard 55-2010 but also ensure that the
cyclic variation and temperature drift do not exceed the specifications described previously.
As shown in Figure 5.2.1.1, humidity also has an impact on thermal comfort. The higher
the humidity, the lower the operative temperature must be to maintain thermal comfort. Sec-
tion 5.2.2 defines the humidity ratio upper limit for thermal comfort as 0.012 grams water/
grams dry air under the same typical parameters used to define Figure 5.2.1.1. There is no
lower limit defined for thermal comfort; however, there are several nonthermal comfort issues
that do provide a lower limit, which are not discussed in any detail in this standard. The build-
ing energy modeler must ensure the HVAC system can adequately control humidity to a level
below the upper limit specified by Standard 55-2010.
Finally, elevated air speeds, within practical limitations, will increase the maximum operative
temperature for thermal comfort under some conditions. The Standard Effective Temperature
(SET) model as defined in Section 5.2.3.2 uses a thermophysiological simulation of the human
body to equate the occupants’ skin heat loss at different air speeds, temperatures, and other param-
eters. Two graphical representations of the model are shown in Figures 5.2.3.1 and 5.2.3.2. These
representations illustrate particular combinations of the governing parameters. The difference
between the mean radiant and air temperatures, clothing insulation, and metabolic rate all impact
the effect air speed has on the operative temperature range required for thermal comfort. To ade-
quately calculate unique conditions, the SET model should be used directly. Most building energy
models do not have the capability to estimate air speeds in an occupied space. However, reasonable
assumptions about air speeds can be made based on zone airflow rates and the size and shape of the
occupied space. The building energy modeler should be conscious of the dependence of the opera-
tive temperature bounds on air speeds. In some cases, elevating airflow rates may allow for opera-
tive temperatures higher than typical while still meeting Standard 55-2010 requirements.
Relevant Sections of ASHRAE Standard 55-2010: Sections 5.2.1, 5.2.2, 5.2.3, 5.4
2
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
DCO Item(s):
III.A. Simulation Comparisons
Section 6 discusses compliance with Standard 55-2010. Compliance with this standard
requires that building systems maintain conditions within the range specified in this standard
during all combinations of expected conditions, except for extremes. The documentation
requirements for compliance are described in Section 6.2 and include the design operative
temperature and humidity; the design outdoor conditions and the total indoor loads; values
used for the comfort parameters clothing, metabolic rate, and indoor-air speed; a narrative
explanation of why local discomfort will not exceed Section 5 limits; and system input and
output capacities necessary to meet design indoor thermal comfort conditions at design out-
door conditions. The building energy modeler must be able to show that, during design out-
door conditions and internal loads, the operative temperature is within the bounds established
by Standard 55-2010.
Relevant Sections of ASHRAE Standard 55-2010: Sections 6.1, 6.2
DCO Item(s):
III.B. Modeling Energy Performance
As described previously, Section 5.2.1.2 defines the PMV model used to determine the
thermal comfort bounds of an occupied space. Standard 55-2010 defines the acceptable ther-
mal environment for general comfort as a predicted percent of dissatisfied (PPD) occupants of
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
10%. The building energy modeler could use the PPD as a metric for comparison of a build-
ing’s envelope and systems.
Relevant Sections of ASHRAE Standard 55-2010: Section 5.2.1.2
3
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
ANSI/ASHRAE
Standard 62.1-2010
Ventilation for Acceptable
Indoor Air Quality
RESOURCE DESCRIPTION
ANSI/ASHRAE Standard 62.1-2010 is ASHRAE's standard for indoor air quality (IAQ)
for commercial buildings. The 2010 revision adds new minimum filtration/air-cleaning
requirements, minimum requirements for when ventilation systems must be operated, and a
natural ventilation procedure. Other revisions include a more robust IAQ Procedure, demand-
controlled ventilation system design requirements, requirements for separation of intakes and
exhausts, and ventilation rates and occupancy categories.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
The ASHRAE 62.1 iPhone, iPod touch, and iPad application allows users to perform ven-
tilation calculations for commercial buildings based on Standard 62.1 (www.ashrae.org/
iphone).
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
in which the building outdoor air intake rates and other system design parameters are based on an
analysis of contaminant sources, contaminant concentration limits, and level of perceived indoor
air acceptability, shall be permitted to be used for any zone or system.
“6.1.3 Natural Ventilation Procedure. The prescriptive design procedure presented in
Section 6.4, in which outdoor air is provided through openings to the outdoors, shall be per-
mitted to be used for any zone or portion of a zone in conjunction with mechanical ventilation
systems as required in Section 6.4.”
Exhaust airflow rates, which impact ventilation rates, are covered in Standard 62.1-2010,
Section 6.5.
Relevant Sections of ASHRAE Standard 62.1-2010: Sections 5.8, 6.1, 6.2, 6.3, 6.4, 6.5
DCO Item(s):
II.H. Controls
Some building energy models are capable of calculating relative humidity levels within
the spaces. According to Standard 62.1-2010, Section 5.9, “Mechanical air-conditioning sys-
tems with dehumidification capability shall be designed to comply with the following….
Occupied space relative humidity shall be limited to 65% or less when system performance is
analyzed with outdoor air at the dehumidification design condition (that is, design dew point
and mean coincident dry-bulb temperatures) and with the space interior loads (both sensible
and latent) at cooling design values and space solar loads at zero.”
Fan system schedules defined in the energy model should conform to Standard 62.1-2010,
Section 5.3: “Mechanical ventilation systems shall include controls, manual or automatic, that
enable the fan system to operate whenever the spaces served are occupied. The system shall be
designed to maintain no less than the minimum outdoor airflow as required by Section 6 under
any load condition.”
Relevant Sections of ASHRAE Standard 62.1-2010: Sections 5.3, 5.9
6
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
ANSI/ASHRAE/IES
Standard 90.1-2010
Energy Standard for Buildings Except
Low-Rise Residential Buildings
RESOURCE DESCRIPTION
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
detailed requirements, as well as incorporating changes from more than 100 addenda. New
content in the 2010 edition includes the following:
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
The building industry is rapidly moving toward sustainable design and net zero
energy buildings. The U.S. Green Building Council (USGBC) has taken the lead
through its Leadership in Energy and Environmental Design (LEED) Green Building
Rating System and requires whole-building, fully integrated design, construction, oper-
ation, and maintenance. The LEED rating system is one of the largest drivers for the use
of building energy modeling as described in Appendix G of Standard 90.1. The LEED
rating system has established various prerequisites and credits for various aspects of
new construction projects, including the site, design, and construction materials. The
first credit under the Energy and Atmosphere category is the Optimize Energy Perfor-
mance credit, which establishes a point system for exceeding Standard 90.1 energy cost.
To achieve the points under this credit, the team seeking LEED certification must show,
using the modeling techniques described in Appendix G, that the proposed building
design has a lower energy cost than a Standard 90.1 baseline building.
DCO Item(s):
I.B.3 Translate a Building into an Energy Model
I.C.1 Purpose of Modeling
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
An energy model must be developed to address the needs of the clients and assist the client
in making well-informed decisions about an investment in their project as well as the life-
cycle cost (LCC) benefit from the proposed capital expenditure. Although the responsibility
for accuracy of the model lies with the modeler, the responsibility for the accuracy of inputs
used to develop the model resides with the various team members, design professionals, archi-
tect, and owner of the building. The modeler must collect pertinent information regarding
location, orientation, and features such as shading of the building by topography, vegetation,
or adjacent buildings. This information must be provided to the modeler along with occu-
pancy, plug loads, lighting loads, HVAC system type, and operating schedules in order for the
modeler to develop a robust and useful model.
Generally, this information should be relatively easy to obtain for an existing building. Typi-
cally, a set of “as built” drawings is available from facility personnel and includes the input val-
ues required for the model. In the event that certain information is not available, the energy
modeler can, with the assistance of facility personnel, take measurements and make observations
that can be incorporated into the model. For yet-to-be-built projects, this information may not be
made available to the energy modeler well in advance of the design development phase. In fact,
the client or architect may wait for the results from an energy model to finalize envelope choices
(e.g., a particular glass type) before finalizing the design. As a result, the modeler is forced to
make certain assumptions about the building in order to determine its performance.
One of the first steps in energy modeling is classifying the building based on usage type
categories specified in Section 9.5.1 or 9.6.1 of Standard 90.1-2010. The modeler must use
either the building type category method or the space type category method but must not use a
combination of the two. If the space type category is used, the modeler may simplify the placement
of the various spaces in the model, provided that the total building area remains the same. It is
acceptable to develop models of a building that exclude parts of the building provided that the
8
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
excluded parts are served by independent HVAC systems and the design space temperatures
on either side of the boundary separating the included and excluded parts of the building are
essentially the same.
Standard 90.1-2010makes a clear distinction between thermal blocks and HVAC
zones that must be understood by any energy modeler. A thermal block is an area that
shares similar loads and is served by similar HVAC systems. For instance, the interior
HVAC zones of a multistory building, which have the same space classification and simi-
lar internal loads, may be considered a thermal block even though the area is physically
divided into several HVAC zones. This grouping method helps reduce the effort required
to model similar spaces in a building. It is also important, when comparing options in
which HVAC zones may change, that the thermal blocks remain the same to provide a fair
comparison of HVAC system performance.
The model must incorporate lighting power usage and lighting controls. Where existing
data are not available, the modeler can use the building area or space-by-space method out-
lined in Section 9.0 to determine the LPD of the building. The model must also account for
variations in the schedule for occupancy, lighting, thermostat setpoints, and HVAC system
operation.
It is important for the modeler who is not a mechanical, electrical, and/or plumbing engi-
neer to realize the difference between typical use and design or rated use. A simulation seeks
to model the typical performance of equipment over the course of a year (8760 h). This is very
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
different from the design or rated use of a piece of equipment that has been sized to handle the
expected peak conditions. This is especially true for heating and cooling equipment, which is
normally designed for peak conditions that occur for a very small percentage of time over a
given year. Oversizing of equipment not only penalizes the owner of the building during the
construction phase by increasing the capital costs but, more importantly, penalizes the build-
ing owner over the life of the building. Appendix G of Standard 90.1 assists the modeler in
checking and/or verifying the reasonableness and energy impacts of the systems and equip-
ment selected by the various team members.
Not every mechanical or HVAC system can be modeled in every energy-modeling pro-
gram. ASHRAE’s 90.1 User’s Manual provides an example of how to approach modeling
program limitations by creating thermodynamically similar models. The example provided
explains how one can approximate the energy usage of a dual-fan, dual-duct HVAC system
even when only a single fan system can be modeled. The suggested approach is to run the
model twice each time with the single-fan, dual-duct system, once with the economizer con-
trolled to the cold-deck supply temperature, and once with the economizer at its minimum
position. The HVAC systems actual energy usage will be equal to the cooling energy from the
first run and the heating energy from the second.
There are two related but distinct purposes for building an energy model that are described
in Standard 90.1. The first is to show compliance with the standard through the Energy Cost
Budget method (Section 11). The second is to quantitatively compare the energy costs of a
proposed and a 90.1-compliant building through the Performance Rating Method described in
Appendix G. Through this method, the percent reduction in energy cost can be measured for a
proposed building. This is necessary when seeking LEED certification as described previ-
ously.
Relevant Sections of ASHRAE/IES Standard 90.1-2010: Sections 9.5.1, 9.6.1, 11, Appendix G
9
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
DCO Item(s):
I.C. Software and Tool Selection
There are well over 50 software tools available for use by energy modelers. These include
commercially available packages developed as licensed software, others developed by vendors
of HVAC equipment, and free tools from the government or electric utilities. None of these are
perfect, and it is important for the modeler to know which software is appropriate for the
building that is to be simulated.
ASHRAE does not endorse any particular tool; however, Standard 90.1 does set certain
minimum performance criteria for particular software, and those criteria should be used by
the modeler. The simulation program must be able to perform load calculations in accor-
dance with generally accepted engineering standards and handbooks (e.g., ASHRAE Hand-
book—Fundamentals) and must have been tested in accordance with ANSI/ASHRAE
Standard 140-2007. The program must be able to perform annual hourly calculations for
various geographic and climatic conditions. The software will account for hourly variations
in occupancy and scheduling of the lights, HVAC system, plug load or miscellaneous equip-
ment, as well as thermostat or control setpoint. The program must account for thermal mass
effects for a minimum of 10 zones and be able to accurately estimate the part-load perfor-
mance for mechanical equipment.
In the event that no simulation program is readily available that adequately models a par-
ticular component or system of a building, an Exceptional Calculation Method, as described in
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
section 11.2.5 of Standard 90.1, can be used.
Whether the modeler uses a readily available and tested simulation tool or one devel-
oped as an exceptional calculation, it is imperative that the same program be used to evalu-
ate a baseline building as well as the proposed design. The software must be able to
generate reports that include a breakdown of energy usage by at least the following compo-
nents:
• Lighting
• Internal equipment
• Service-water-heating equipment
• Space-heating equipment
• Space-cooling equipment and heat-rejection equipment
• Fans
• Auxiliary equipment such as pumps
The software must also show the amount of time any loads are not met by the HVAC
system and provide an explanation of any error message noted in the output report. The
output reports will help the modeler validate the results and check them for reasonable-
ness.
II. COMPONENTS OF BUILDING AND ENERGY SYSTEMS
The simulation must be consistent with either the design documents or the as-is stand-
ing structure. It must account for the fenestration; envelope; interior lighting power and
controls; HVAC system types, sizes, and controls; and service-water-heating systems and
controls.
10
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
It is important to produce a model that either reflects the actual operating pattern and
energy use of the existing structure that is being evaluated or, in the event of a yet-to-be-built
structure, reflects compliance with Standard 90.1. This is particularly true for any new con-
struction project that seeks LEED certification.
For a model of an existing building, the inputs are readily available from facility personnel
in the form of as-built drawings or by actual physical verification. For yet-to-be-built struc-
tures, the standard provides most of the inputs required to establish a good baseline model.
Since the inputs are well documented and familiar to the building energy modeling industry, it
is easy to compare the results to known benchmarks and judge against previous experience. A
good baseline model will lay the foundation for all the work yet to come.
The following are key inputs for developing energy models:
• Location
• Envelope
• Internal gains
• Systems
• Schedules
Building schedules have a large impact on energy consumption and must be given adequate
attention in order to have an accurate model. The modeler must know or assume the weekday,
weekend, and holiday schedules for the all of the following components of the building model:
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
• Occupancy
• Lighting power
• Miscellaneous equipment power (plug loads)
• Thermostat setpoints
• HVAC systems
• Any other significant loads
The following sections describe the relevance of Standard 90.1 to the key input parameters
for developing accurate energy models.
DCO Item(s):
II.A. Location and Climate Definitions
ASHRAE’s 90.1 User’s Manual discusses various aspects of the climate data that
should be considered by the energy modeler. Most importantly, the climatic data used in an
energy model must represent both average and design conditions. Average conditions alone
will not provide the data needed for equipment-sizing calculations. Second is selecting the
appropriate weather station. Because, in some cases, weather data is not available for the
exact location of the building, data for the station that shares the most comparable climate
should be chosen. This does not always mean the closest station; for example, elevation as
well as proximity to mountains and bodies of water must be considered.
Standard 90.1’s Normative Appendices B and D provide climatic information for various
domestic and international locations. Its Figure B-1 (reproduced on p. 12) shows climate zones for
the United States. Table B-1 (see sample, p. 13) lists the climate zone number and letter for each
11
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Figure B-1 U.S. map showing DOE climate zones (excerpt from ASHRAE/IES Standard 90.1-2010 [Briggs et al. 2003]).
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
12
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
Wade Hampton (CA) 8 San Mateo 3C Rio Blanco 6B Clinch 2A
13
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
U.S. state and the major counties within each state. Climate zone information for a wide variety of
Canadian and international locations is shown in Tables B-2 and B-3 (see samples, pp. 15–16). Table
B-4 (reproduced on p.19) provides a summary of the eight international climate zone definitions.
Tables D-1, D-2, and D-3 (see sample, p. 18) contain climatic data necessary to determine building
envelope and mechanical requirements for various U.S., Canadian, and international locations.
Relevant Sections of ASHRAE/IES Standard 90.1-2010: Section 5.1, Appendix B, Appendix D
DCO Item(s):
II.B. Building Envelope and Partitions
It is important that the thermal properties of the building envelope are captured accurately
in the building model; however, it is usually necessary to make some simplifications for the
sake of time and budget. Standard 90.1 establishes guidelines for envelope simplifications that
can and should be performed, including the following:
• Minor assemblies that cover less than 5% of a given assembly type, such as an exte-
rior wall or roof, may be ignored when preparing the building model.
• Complicated surfaces, such as curved or domed roofs, may be modeled as a pitched
roof as long as the tilt and azimuth of the surface are within 45° of each other.
• Exterior roof surfaces shall be modeled using the aged solar reflectance and thermal
emittance determined in accordance with Section 5.5.3.11(a).
• Manually operated fenestration shading devices, such as blinds or shades, are not to
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
be modeled.
The building envelope requirements, including U-factors and R-values for roofs, walls
above and below grade, floors, slab-on-grade floors, opaque doors, and fenestration for all of
the eight climate zones are shown in Tables 5.5-1 to 5.5-8 (see sample, p. 19).
Although the properties of an existing structure are readily available from the plans or
from a site audit, for yet-to-be-built structures this information might not be available, or the
design team might be looking to an energy model to guide their selection process. LEED cer-
tification requires an energy model to compare the performance of the design to a minimally
code-compliant base-case building. The material selection for minimally compliant buildings
for various climate zones is found in Section 5 of Standard 90.1.
Relevant Sections of ASHRAE/IES Standard 90.1-2010: Sections 5.1–5.6, Appendix C
DCO Item(s):
II.C. Building HVAC Systems
The HVAC system is typically the single largest energy user in a building, accounting for
40% to 60% of a building’s energy use. The HVAC system type will vary based on the use and
size of the building. A high-rise office building will probably be equipped with a central chilled-
water and boiler plant, whereas a high-rise residential tower will have various packaged terminal
air conditioners and heat pumps. Standard 90.1’s Table G3.1.1A (reproduced on p. 20) provides
guidelines for the types of systems that should be used for different building types.
From a long-term operations perspective, the ability to test configurations or improvements
of the HVAC system can be invaluable not only to the design team but also to the building’s
owner. A system that might be marginally expensive during the construction phase might pay for
itself within a year in reduced utility costs.
14
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
International A
The Pas A 7
15
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
Bahamas Mannheim 5 Penang/Bayan Lepas 1 Johannesburg 4
16
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
3A and 3B Warm–Humid (3A), Dry (3B) 4500 < CDD50°F < 6300
4A and 4B Mixed–Humid (4A), Dry (4B) CDD50°F < 4500 and 3600 < HDD65°F < 5400
5A, 5B and 5C Cool–Humid (5A), Dry (5B), Marine (5C) 5400 < HDD65°F < 7200
6A and 6B Cold–Humid (6A), Dry (6B) 7200 < HDD65°F < 9000
The energy modeler should be familiar with the zoning patterns and occupancy schedules
of various areas in a building. The modeler must use engineering judgment to create thermal
zones in order to simplify the model without compromising the accuracy of the results. One of
the most significant sources of heat gain in a building is the windows. Generally, most of this
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
heat is concentrated along the perimeter of the building. As a result, perimeter spaces require
more cooling than interior spaces. The energy modeler should create thermal blocks that sepa-
rate the perimeter and interior spaces.
Additional sources of heat gain in a space are overhead lights and electrical equipment.
All the heat gained in a space through the windows, lights, and equipment must be removed
by the cooling system. If a building energy model can show the effects of altering the build-
ing’s orientation and/or window glazing, the design engineer can examine these effects on
heat load and possibly make recommendations for reducing the lighting and equipment elec-
trical loads as well as the size of the cooling equipment, fans, and pumps. The results from the
energy model can help the design team in selecting appropriately sized equipment to meet the
space’s HVAC needs.
Once the equipment size and capacity are known, the efficiency rating of the equipment
installed or from design documents can be compared to minimum efficiency ratings specified
in Standard 90.1’s Tables 6.8.1A to 6.8.1K (see sample, pp. 20–22).
Standard 90.1 requires that, when entering HVAC system performance metrics, the energy
modeler separate fan energy from cooling energy. This is important because supply fans do
not always operate on the same schedule as the cooling system. In fact, the supply fan will
typically operate continuously while the building is occupied, whereas the cooling system will
only operate when needed to cool the space. Standard 90.1 provides detailed calculations for
determining the fan and cooling power input requirements from typical rated energy perfor-
mance metrics such as energy efficiency ratio (EER).
The size of the HVAC equipment can have a significant impact on the energy usage of the
building because of part-load performance. Therefore, it is important to take a standard approach
to equipment sizing when comparing HVAC systems through energy models. Standard 90.1 has
17
Table D-1 U.S. and U.S. Territory Climatic Data (ASHRAE/IES Standard 90.1-2010)
18
Cooling Design Temperature
Heating Design No. Hrs.
State Dry-Bulb Wet-Bulb
Latitude Longitude Elev., ft HDD65 CDD50 Temperature 8 a.m.–4 p.m.
City
Talladega 33.43 N 86.08 W 555 2790 5097 N.A. N.A. N.A. N.A.
Tuscaloosa FAA AP 33.23 N 87.62 W 169 2661 5624 20 94 77 N.A.
Alaska (AK)
Anchorage WSCMO AP 61.17 N 150.02 W 114 10,570 688 –14 68 57 521
Barrow WSO AP 71.30 N 156.78 W 31 20,226 0 –41 52 49 N.A.
Fairbanks WSFO AP 64.82 N 147.87 W 436 13,940 1040 –47 77 59 682
Juneau AP 58.37 N 134.58 W 12 8897 559 4 69 58 540
Kodiak WSO AP 57.75 N 152.50 W 111 8817 451 7 65 56 384
Nome WSO AP 64.50 N 165.43 W 13 14,129 274 –31 65 55 210
Arizona (AZ)
Douglas FAA AP 31.47 N 109.60 W 4098 2767 4786 N.A. N.A. N.A. N.A.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Table 5.5-1 Building Envelope Requirements for Climate Zone 1 (A, B)*
(ASHRAE/IES Standard 90.1-2010)
Nonresidential Residential Semiheated
Assembly Insulation Assembly Insulation Assembly Insulation
Opaque Elements Max. Min. R-Value Max. Min. R-Value Maxi. Min. R-Value
Roofs
Insulation Entirely U-0.063 R-15.0 c.i. U-0.048 R-20.0 c.i. U-0.218 R-3.8 ci
above Deck
Metal Buildinga U-0.065 R-19.0 U-0.065 R-19.0 U-0.167 R-6.0
Attic and Other U-0.034 R-30.0 U-0.027 R-38.0 U-0.081 R-13.0
Walls, Above-Grade
Mass U-0.580 NR U-0.151b R-5.7 c.i.b U-0.580 NR
Metal Building U-0.093 R-16.0 U-0.093 R-16.0 U-0.113 R-13.0
Steel-Framed U-0.124 R-13.0 U-0.124 R-13.0 U-0.352 NR
Wood-Framed and Other U-0.089 R-13.0 U-0.089 R-13.0 U-0.292 NR
Walls, Below-Grade
Below-Grade Wall C-1.140 NR C-1.140 NR C-1.140 NR
Floors
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
Mass U-0.322 NR U-0.322 NR U-0.322 NR
Steel-Joist U-0.350 NR U-0.350 NR U-0.350 NR
Wood-Framed and Other U-0.282 NR U-0.282 NR U-0.282 NR
Slab-On-Grade Floors
Unheated F-0.730 NR F-0.730 NR F-0.730 NR
Heated F-1.020 R-7.5 for 12 in. F-1.020 R-7.5 for 12 in. F-1.020 R-7.5 for 12 in.
Opaque Doors
Swinging U-0.700 U-0.700 U-0.700
Nonswinging U-1.450 U-1.450 U-1.450
Assembly Assembly Max. Assembly Assembly Assembly Assembly Max.
Fenestration Max. U SHGC Max. U Max. SHGC Max. U SHGC
Vertical Glazing, 0%–40% of Wall
Nonmetal framing (all)c U-1.20 U-1.20 U-1.20
Metal framing
U-1.20 U-1.20 U-1.20
(curtainwall/storefront)d
SHGC-0.25 all SHGC-0.25 all SHGC-NR all
Metal framing U-1.20
U-1.20 U-1.20
(entrance door)d
Metal framing (all other)d U-1.20 U-1.20 U-1.20
*The following definitions apply: c.i. = continuous insulation (see Section 3.2), NR = no (insulation) requirement.
aWhen using R-value compliance method, a thermal spacer block is required; otherwise use the U-factor compliance method. See Table A2.3.
bException to Section A3.1.3.1 applies.
cNonmetal framing includes framing materials other than metal with or without metal reinforcing or cladding.
dMetal framing includes metal framing with or without thermal break. The “all other” subcategory includes operable windows, fixed windows, and non-entrance doors.
19
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Nonresidential and 3 Floors or Less and <25,000 ft2 System 3—PSZ-AC System 4—PSZ-HP
2
Nonresidential and 4 or 5 Floors and <25,000 ft or
System 5—Packaged VAV System 6—Packaged VAV
with Reheat with PFP Boxes
5 Floors or Less and 25,000 ft2 to 150,000 ft2
Table 6.8.1A Electronically Operated Unitary Air Conditioners and Condensing Units—
Minimum Efficiency Requirements (ASHRAE/IES Standard 90.1-2010)
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
Test
Equipment Heating Subcategory or Minimum
Size Category Proce-
Type Section Type Rating Condition Efficiencya
dureb
Air conditioners, Split system 13.0 SEER
<65,000 Btu/hc All
air cooled Single package 13.0 SEER AHRI
Through-the-wall Split system 12.0 SEER 210/240
30,000 Btu/hc All
(air cooled) Single package 12.0 SEER
Electric resistance Split system and 11.2 EER
65,000 Btu/h and (or none) single package 11.4 IEER
<135,000 Btu/h Split system and 11.0 EER
All other
single package 11.2 IEER
Electric resistance Split system and 11.0 EER
135,000 Btu/h and (or none) single package 11.2 IEER
<240,000 Btu/h Split system and 10.8 EER
All other
Air conditioners, single package 11.0 IEER AHRI
air cooled Electric resistance Split system and 10.0 EER 340/360
240,000 Btu/h and (or none) single package 10.1 IEER
<760,000 Btu/h Split system and 9.8 EER
All other
single package 9.9 IEER
Electric resistance Split system and 9.7 EER
(or none) single package 9.8 IEER
760,000 Btu/h
Split system and 9.5 EER
All other
single package 9.6 IEER
20
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Table 6.8.1A Electronically Operated Unitary Air Conditioners and Condensing Units—
Minimum Efficiency Requirements (ASHRAE/IES Standard 90.1-2010) (continued)
Test
Equipment Heating Subcategory or Minimum
Size Category Proce-
Type Section Type Rating Condition Efficiencya
dureb
Split system and 12.1 EER AHRI
<65,000 Btu/h All
single package 12.3 IEER 210/240
11.5 EER (before 6/1/2011)
Electric resistance Split system and 12.1 EER (as of 6/1/2011)
(or none) single package 11.7 IEER (before 6/1/2011)
65,000 Btu/h and 12.3 IEER (as of 6/1/2011)
<135,000 Btu/h 11.3 EER (before 6/1/2011)
Split system and 11.9 EER (as of 6/1/2011)
Air conditioners, All other
single package 11.5 IEER (before 6/1/2011)
water
12.1 IEER (as of 6/1/2011) AHRI
cooled
11.0 EER (before 6/1/2011) 340/360
Electric resistance Split system and 12.5 EER (as of 6/1/2011)
(or none) single package 11.2 IEER (before 6/1/2011)
135,000 Btu/h and 12.5 IEER (as of 6/1/2011)
<240,000 Btu/h 10.8 EER (before 6/1/2011)
Split system and 12.3 EER (before 6/1/2011)
All other
single package 11.0 IEER (before 6/1/2011)
12.5 IEER (before 6/1/2011)
11.0 EER (before 6/1/2011)
Electric resistance Split system and 12.4 EER (as of 6/1/2011)
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
(or none) single package 11.1 IEER (before 6/1/2011)
Air conditioners, 240,000 Btu/h and 12.6 IEER (as of 6/1/2011) AHRI
water cooled <760,000 Btu/h 10.8 EER (before 6/1/2011) 340/360
Split system and 12.2 EER (as of 6/1/2011)
All other
single package 10.9 IEER (before 6/1/2011)
12.4 IEER (as of 6/1/2011)
11.0 EER (before 6/1/2011)
Electric Resis-
Split system and 12.2 EER (as of 6/1/2011)
tance
single package 11.1 IEER (before 6/1/2011)
(or None)
Air conditioners, 12.4 IEER (as of 6/1/2011) AHRI
760,000 Btu/h
water cooled 10.8 EER (before 6/1/2011) 340/360
Split system and 12.0 EER (as of 6/1/2011)
All other
single package 10.9 IEER (before 6/1/2011)
12.2 IEER (as of 6/1/2011)
21
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Table 6.8.1A Electronically Operated Unitary Air Conditioners and Condensing Units—
Minimum Efficiency Requirements (ASHRAE/IES Standard 90.1-2010) (continued)
Test
Equipment Heating Subcategory or Minimum
Size Category Proce-
Type Section Type Rating Condition Efficiencya
dureb
Split System and 12.1 EER AHRI 210/
< 65,000 Btu/h All
single package 12.3 IEER 240
11.5 EER (before 6/1/2011)
Electric
Split system and 12.1 EER (as of 6/1/2011)
Resistance
single package 11.7 IEER (before 6/1/2011)
(or None)
65,000 Btu/h and 12.3 IEER (as of 6/1/2011)
<135,000 Btu/h 11.3 EER (before 6/1/2011)
Split system and 11.9 EER (as of 6/1/2011)
All other
single package 11.5 IEER (before 6/1/2011)
12.1 IEER (as of 6/1/2011)
11.0 EER (before 6/1/2011)
Electric
Split system and 12.0 EER (as of 6/1/2011)
Resistance
single package 11.2 IEER (before 6/1/2011)
(or None)
135,000 Btu/h and 12.2 IERR (as of 6/1/2011)
<240,000 Btu/h 10.8 EER (before 6/1/2011)
Split system and 11.8 EER (as of 6/1/2011)
Air conditioners, All other
single package 11.0 IEER (before 6/1/2011)
evaporatively
12.0 IEER (as of 6/1/2011) AHRI 340/
cooled
11.0 EER (before 6/1/2011) 360
Electric
Split system and 11.9 EER (as of 6/1/2011)
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
Resistance
single package 11.1 IEER (before 6/1/2011)
(or None)
240,000 Btu/h and 12.1 IEER (as of 6/1/2011)
< 760,000 Btu/h 10.8 EER (before 6/1/2011)
Split system and 12.2 EER (as of 6/1/2011)
All other
single package 10.9 IEER (before 6/1/2011)
11.9 IEER (as of 6/1/2011)
11.0 EER (before 6/1/2011)
Electric
Split system and 11.7 EER (as of 6/1/2011)
Resistance
single package 11.1 IEER (before 6/1/2011)
(or None
11.9 IEER (as of 6/1/2011)
760,000 Btu/h
10.8 EER (before 6/1/2011)
Split system and 11.5 EER (as of 6/1/2011)
All other
single package 10.9 IEER (before 6/1/2011)
11.7 IEER (as of 6/1/2011)
10.1 EER (before 6/1/2011)
Condensing units, 10.5 EER (as of 6/1/2011
135,000 Btu/h – –
air cooled 11.4 IEER (before 6/1/2011)
11.8 IEER (as of 6/1/2011)
13.1 EER (before 6/1/2011)
Condensing units, 13.5 EER (as of 6/1/2011) AHRI
135,000 Btu/h – –
water cooled 13.6 IEER (before 6/1/2011) 365
14.0 IEER (as of 6/1/2011)
13.1 EER (before 6/1/2011)
Condensing units,
13.5 EER (as of 6/1/2011)
evaporatively 135,000 Btu/h – –
13.6 IEER (before 6/1/2011)
cooled
14.0 IEER (as of 6/1/2011
aIPLVs and part-load rating conditions are only applicable to equipment with capacity modulation.
bSection 12 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.
cSingle-phase, air-cooled air conditioners <65,000 Btu/h are regulated by NAECA. SEER values are those set by NAECA.
22
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
established a procedure (see Section 11.3.2) for sizing baseline equipment. When comparing dif-
ferent HVAC system options, all options must adequately meet the load in the building.
Relevant Sections of ASHRAE/IES Standard 90.1-2010: Section 6.8, Appendix G
DCO Item(s):
II.D. Lighting Systems
Lighting is the second-largest contributor to the heat load in a space. Therefore, it is critical to
accurately model the lighting power of a building and to look for opportunities to reduce lighting
wattage and increase effective daylighting without adding more cooling load from solar gain.
The energy model must account for the installed or designed wattage. Different areas in a
building require different levels of illumination; thus, the wattage of the lights will vary from
space to space. Standard 90.1 provides two acceptable methods, described in Sections 9.5.1
and 9.6.1, for determining the lighting power density LPD of a building: the Building Area
Method and the Space-by-Space Method.
The LPD must be established for each thermal zone in order to account for the load on the
HVAC system. For new construction projects seeking LEED certification, the LPD of the
design case, determined by either of the two procedures, must be compared to maximum
allowable LPD values found in Standard 90.1.
Note that the illumination levels of the spaces must be in accordance with Illuminating
Engineering Society of North America (IESNA) Lighting Handbook. The proper illumination
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
levels must be achieved within the LPD constraints specified in Standard 90.1. Illumination
levels can be achieved by a combination of overhead electrical lights and daylighting.
Relevant Sections of ASHRAE/IES Standard 90.1-2010: Sections 9.4–9.6
DCO Item(s):
II.F. District Energy Systems
The HVAC needs for buildings that are part of large campuses are generally provided by a dis-
trict-wide central plant. The building heating and cooling energy use is generally measured using
an energy meter, and tenants are billed based on usage. As a result, the direct energy use of such a
building accounts for only the lights and equipment installed in the space. In general, the sheer size
and capacity of a district-wide central plant provides inherent efficiencies; however, the pumping
energy associated with transporting the heat transfer fluid could be significant if the building is
located a significant distance from the district plant. Depending on the location and ownership of
the pumps, the pumping energy might need to be factored into the model.
For buildings served by district plants, the building operators have little to no control over
the plants and cannot implement energy conservation strategies such as chilled-water reset. As
a result, the energy modeler should be aware whether the building will be purchasing heating
hot water and chilled water from a district central plant so that no time is wasted in evaluating
strategies over which the design team or building owner has no control.
Relevant Sections of ASHRAE/IES Standard 90.1-2010: Sections 11.2.3, Appendix G
DCO Item(s):
II.H Controls
HVAC Controls and Basic Control Sequences. Controls form an integral component of any
HVAC system. A system without controls is virtually useless, because it will fail to meet occupant
23
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
comfort criteria while still using energy. There are a wide variety of controls for virtually all HVAC
systems. They range in complexity and functionality from simple controls, such as timers, to multi-
channel electronic time clocks. Each control has its optimal use in the field.
For HVAC systems, simple controls consists of timers to automatically turn on and off an air-
handling unit (AHU) fan. However, the addition of a variable-frequency drive (VFD) that responds
to duct static pressure changes and modulates the fan speed based on real-time inputs to maximize
occupant comfort is a much-desired control device for the AHU. The energy modeler must be able
to model and evaluate the effectiveness of various technologies. Although simulating the operation
of a timer is relatively simple, modeling the performance of a VFD is considerably more difficult.
The energy modeler will likely encounter hundreds of different devices in the field. Listing
all of the potential control devices and uses would be impossible; however, to evaluate the per-
formance of any control technology, the modeler must be able to separate the basic functional-
ity of the control from the capabilities of the device. For example, a simple 24-hour timer that
is used to switch on an AHU fan at 7:00 a.m. and off at 7:00 p.m. every day provides the same
functionality as an electronic, 7-day programmable time clock that is used to control the same
fan. The modeler must be careful to avoid being distracted by the capability of a particular
control and should focus on objectively evaluating the functionality of the device.
Standard 90.1 lists in Sections 6.4.3 and 6.5 the minimum acceptable level of functionality of
controls for a new building. The design team is free to choose controls that have far greater capabil-
ity than those specified in the standard. The energy modeler can demonstrate the value of the addi-
tional capability of the controls to help the design team and owner make cost-effective decisions.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
Lighting Controls. Because heat rejected by the lights contributes significantly to a
space’s overall heat load, turning off the lights when they are not needed will save wasted
lighting energy as well as reduce the cooling load. For perimeter spaces, light entering the
space through the windows can provide a significant portion of the illumination requirements.
Energy can be saved by turning off the overhead lights and reducing unnecessary illumination.
Lighting controls have come a long way since simple, timer-based controls that were used
to switch lights on and off. This, along with significant improvements in the types of lamps,
bulbs, and ballasts, provides the design team or owner with a myriad of options to control
lights. The energy modeler must be familiar with the various technologies available in the
market and their use. For example, in a large warehouse space, stepped dimming controls can
be implemented to turn off the overhead lights when there is adequate natural light entering
the space from the skylights. However, in a high-end retail space, dimming controls might be
more apt to ensure uniform illumination in the space. The modeler must understand the
nuances between the available technologies and where they are best used.
Although the energy savings from implementation of various controls vary from site to
site, Standard 90.1’s Table 9.6.2 provides the modeler with control factors that can be used to
estimate the energy savings.
Miscellaneous Load Controls and Equipment Sequencing. The entire electrical input
from all receptacle and equipment loads is assumed to add to the heat load of a space. This
includes all computers, servers, printers, coffee pots, refrigerators, microwave ovens, etc. It is
important to recognize that even when these devices are in idle or standby mode they consume
between 10% and 30% of their rated energy input. With the exception of refrigerators and serv-
ers, most electrical equipment can be switched off when not in use. The impacts of switching off
or disconnecting plug loads when equipment is not in use can result in significant energy and
utility cost savings. The energy modeler should be able to separate plug loads that can be turned
24
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
off from those that must be left in standby mode and simulate the potential savings from install-
ing controls that will automatically shut off equipment when it is not in use.
Relevant Sections of ASHRAE/IES Standard 90.1-2010: Sections 6.4, 6.5, 7.4, 8.4, 9.4,
11.3, Appendix G
DCO Item(s):
IV.A. Verification and Troubleshooting of Simulation Results
An unmet load hour is defined as an hour when the building load is in excess of the design
coil capacity by one percent or greater and one or more rooms are 1.5°F beyond the room set-
point. Excessive unmet load hours are indicative of a problem with the energy model or a
gross error of a certain input. The error could be something as simple as a typographical error
(e.g., a decimal point error) or, more significantly, improper zoning or material selection rela-
tive to the climate zone. The energy modeler must seek to resolve any unmet load hours. Cor-
recting the problem will significantly improve the quality of the results.
A model that is compliant with Standard 90.1 must ensure that any unmet loads for the proposed
design or baseline model not exceed 300 h (of an 8760 h simulation). Additionally, the unmet load
hours in the proposed design cannot exceed the unmet load hours of the baseline building model.
Relevant Sections of ASHRAE/IES Standard 90.1-2010: Section 11.3, Appendix G
DCO Item(s):
IV.E. Project Deliverable
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
The value of a model is its ability to assist the owner or architect in evaluating alternate designs,
systems or strategies. The differences are of particular importance in making incremental investment
decisions rather than the absolute values. As a result, the outcome of an energy model should be pre-
sented in a manner that will be most useful and easily understood by the owner or architect. Submit-
ting a stack of printouts from the modeling software has little or no use to a nontechnical person.
The documentation must include a description of the project, the key components used to
develop the baseline model, and all improvements made to the proposed design. The report
must be concise and easy to understand and should include energy use by month and by year.
The reports must include a breakdown of energy usage by the following components:
• Lighting
• Internal equipment
• Service-water-heating equipment
• Space-heating equipment
• Space-cooling equipment and heat rejection equipment
• Fans
• Auxiliary equipment, such as pumps
In addition to a nontechnical report, the energy modeler must provide all supporting docu-
mentation as part of the project deliverable. The submittals must include all input and output
reports from the simulation program or compliance software, including a breakdown of
energy usage by end use, as well as a summary of any unmet loads. Standard 90.1 also sug-
gests providing an explanation of error messages or warnings noted in the simulation program
output.
Relevant Sections of ASHRAE/IES Standard 90.1-2010: Section 11.1.5, Appendix G.1.4
25
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
ANSI/ASHRAE/IES
Standard 100-2006
Energy Conservation
in Existing Buildings
RESOURCE DESCRIPTION
ANSI/ASHRAE/IES Standard 100-2006 provides criteria that will result in the conserva-
tion of energy resources in existing buildings.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
RELEVANT CONTENT WITH DCO REFERENCES
DCO Item(s):
II.B Building Envelope and Partitions
Section 6.2 of Standard 100-2006 describes the required general condition of a building
envelope for an existing building for which compliance with the standard is claimed. Specifi-
cally, the standard requires that unnecessary gaps in the building envelope that would result in
excessive infiltration be closed. Such areas include broken or missing windows, door sweeps,
obsolete chimneys, door closers, etc. When modeling an existing building for which compli-
ance with Standard 100 is claimed, the energy modeler should ensure that air infiltration rates
reflect the true conditions of the building envelope.
Section 7.1 requires that where the building envelope has been improved or replaced it
must meet the requirements of section 5 of ASHRAE/IES Standard 90.1-2010. The modeler
should be familiar with that section when modeling a building for which compliance with
Standard 100-2006 is claimed.
Relevant Sections of ASHRAE/IES Standard 100-2006: Sections 6.2, 7.1
DCO Item(s):
II.C. Building HVAC Systems
Section 6.3 of Standard 100-2006 addresses a limited number of topics relevant to energy
modeling. The standard requires that electric heaters be eliminated, fossil-fueled heating
equipment be adequately maintained to operate at the highest possible efficiency, and air fil-
ters be replaced regularly to prevent excessive pressure drop, which would increase fan energy
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
consumption. The energy modeler should be familiar with these requirements when modeling
a building for which compliance with Standard 100-2006 is claimed.
Section 7.5 defines the requirements for replacement motors rated at 1 hp or greater
that operate more than 1000 h per year. The standard requires that motor efficiency meets
or exceeds that shown in Table 2 and that the motor horsepower does not exceed 125% of
the calculated maximum load being served. Finally, the standard also requires the use of
variable-speed operation whenever variable output is required unless an alternative, such
as throttling, results in a lower life-cycle cost. The energy modeler should be familiar
with the motor requirements defined in this section when modeling a building in compli-
ance with Standard 100-2006.
Relevant Sections of ASHRAE/IES Standard 100-2006: Sections 6.3, 7.5
DCO Item(s):
II.D. Lighting Systems
Section 6.6 of Standard 100-2006 defines lighting operations and maintenance require-
ments for existing buildings. Included in this section are the burnout replacement require-
ments for various types of lamps. A building energy modeler should be familiar with these
requirements when modeling a building for which compliance with this standard is claimed.
Relevant Sections of ASHRAE/IES Standard 100-2006: Section 6.6
DCO Item(s):
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
II.H. Controls
There are various relevant HVAC controls requirements for existing buildings seeking
compliance with Standard 100-2006. The first and probably the most important requirement is
that all HVAC systems be equipped with automatic shutdown and setback controls. HVAC
equipment should be scheduled to operate only when required by the building. Setback con-
trols should increase the deadband between heating and cooling setpoints from 45°F to 90°F.
If the building has an energy management system (EMS), Standard 100-2006 requires that
the EMS be used to adjust the start time of HVAC equipment to minimize runtime. In addi-
tion, the standard requires the use of chilled water and heating hot water reset controls on sys-
tems with capacities over 300,000 Btu/h.
Section 7 of Standard 100-2006 establishes the requirements for building modifications.
This section requires that all HVAC equipment be controlled by at least one thermostat for the
regulation of temperature. The standard also sets ranges for heating and cooling setpoints as
well as for deadbands.
Section 7.2.2 discusses the requirements for spaces with relative humidity controls for
comfort purposes. The standard requires that, when used for comfort purposes, the humidity
must not require the use of nonrenewable energy while the relative humidity in the space is
between 30% and 60%.
Finally, Section 7.3 defines the requirements for air distribution systems. The standard
requires that all units with outdoor air supply greater than 200 cfm have adjustable dampers
and controls that can close during unoccupied periods. In addition, all dual-duct and reheat
multizone systems must have supply air temperature reset controls for cold and hot decks.
Standard 100-2006 requires that manual switches be replaced with occupancy sensors,
interval timers, or timed switches, with the exception of emergency egress. In addition, the
28
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
standard requires that lights be turned off in areas adequately illuminated by daylight, using
photocell switches or dimming systems.
Relevant Sections of ASHRAE/IES Standard 100-2006: Sections 6.3.1, 6.3.2, 6.3.3.4, 6.6.3,
6.6.4, 7.2.1, 7.2.2, 7.2.3, 7.3
DCO Item(s):
III.A Simulation Comparisons
Section 5.4 discusses the use of building energy usage and electric demand data in the
analysis of existing buildings. The standard requires energy-use benchmarking the building
against similar buildings with similar usage and climates. In addition, the standard recom-
mends the collection of 12 months of utility bills for all energy and demand purchases.
Relevant Sections of ASHRAE/IES Standard 100-2006: Section 5.4
DCO Item(s):
III.B. Modeling Energy Performance
IV.B. Analyzing and Comparing Modeling Results
Section 5.5 defines one metric that can be used to compare existing buildings and energy
models. The Energy Utilization Index (EUI) is the total annual energy use in Btu/ft2 of condi-
tioned floor area. In order to use this metric, all energy purchases must be converted to British
thermal units. Table 1 provides fuel-to-Btu conversion factors. A second metric that could be
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
used is the Cost Index (CI), which is the total annual energy cost per square foot of condi-
tioned floor area.
Relevant Sections of ASHRAE/IES Standard 100-2006: Section 5.5
DCO Item(s):
IV.C. Economic Analysis
Section 6.8.4 defines the evaluation of energy conservation opportunities (ECOs) for exist-
ing buildings. For each ECO, the cost estimate and annual energy savings should be deter-
mined. Energy cost savings should be calculated using the current utility rate structure and not
a simple average blended rate. There are two recommended approaches to ranking ECOs. The
first and most simple is a simple payback period, which is the estimated capital cost divided
by the annual energy cost savings. The second and more complicated method is life-cycle
costing, which also takes into account the time value of money, annual maintenance costs, and
the life of the measure.
Relevant Sections of ASHRAE/IES Standard 100-2006: Sections 6.8.4, 6.8.5
29
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
RESOURCE DESCRIPTION
There are no formal criteria for confirming the accuracy of the results of a particular
model; that decision is generally left to the user. The simulation program must be robust
enough to provide simulation results that are comparable to results using other simulation
software packages and consistent against a previous version of itself.
ANSI/ASHRAE Standard 140-2007 specifies test procedures for evaluating the technical
capabilities and ranges of applicability of computer programs that calculate the thermal per-
formance of buildings and their HVAC systems.
Standard 140-2007 can be used for identifying and diagnosing predictive differences
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
from whole-building energy simulation software that may possibly be caused by algorith-
mic differences, modeling limitations, input differences, or coding errors. The current set
of tests consists of (1) comparative tests that focus on building thermal envelope and fabric
loads and mechanical equipment performance and (2) analytical verification tests that
focus on mechanical equipment performance. This procedure tests software over a broad
range of parametric interactions and for a number of different output types, thus minimiz-
ing the concealment of algorithmic differences by compensating errors. Different building
energy simulation programs, representing different degrees of modeling complexity, can be
tested. However, some of the tests may be incompatible with some building energy simula-
tion programs.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
• comparing the predictions from other simulation programs to the example results pro-
vided in the standard,
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
• checking the program against previous versions of itself after any changes to the algo-
rithms or code to ensure that only the intended changes resulted;, or
• diagnosing the algorithm sources of prediction differences.
Relevant Sections of ASHRAE Standard 140-2007: Section 4.1, Annexes B8, B9, B16
DCO Item(s):
III.B. Modeling Energy Performance
Section 5 of the standard provides input specifications for building thermal envelope and
fabric load tests, space-cooling equipment, and space-heating equipment to check the appro-
priateness of output and sensitivity of the building energy simulation software. The inputs will
guide the modeler in assembling an accurate base-building model that is thermally decoupled
from ambient conditions. This is done to allow the modeler to test the performance of the
heating and cooling equipment.
Relevant Sections of ASHRAE Standard 140-2007: Section 5
DCO Item(s):
III.C. Evolution of Simulation Techniques to Meet Project Methods
and Objectives
It is likely that the modeler will have to make changes to the source code of a particular
energy modeling software for the purpose of testing. These changes must have a mathematical,
physical, or logical basis and be applied consistently across the test. The standard does not allow
arbitrary modifications to the simulation program. The changes must be made available in pub-
licly released versions of the software. If the changes are not publicly available, the modeler
must document the changes in sufficient detail using the template provided in Annex A2.
32
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Modifications for infiltration and fan adjustments for altitude, exterior radiative and con-
vective surface coefficients, infrared portion of film coefficients, window optical properties,
and solar fractions can be found in Annexes B3 through B7 of the standard.
Relevant Sections of ASHRAE Standard 140-2007: Section 4.4.3, Annexes A2, B3 to B7
DCO Item(s):
IV.A. Verification and Troubleshooting of Simulation Results
IV.B. Analyzing and Comparing Modeling Results
The energy modeler can compare the output results of the simulation per Section 4.4 of
the standard. Annex B8 gives the example simulation results for the building thermal enve-
lope and fabric load tests. Annex B16 gives example simulation results for HVAC equip-
ment performance tests. These comparisons allow the modeler to then verify the accuracy of
the model and highlight any major flaws or limitations in the capability of the building
energy program.
Relevant Sections of ASHRAE Standard 140-2007: Sections 4.1, 4.4, Annexes B8, B16
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
33
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
demand savings of commercial equipment. Additionally, guidelines for calibrating sim-
ulation models to measured data and sensitivity analyses are covered in detail. Energy
modelers should refer to this guideline to determine an approach to estimate baseline
and proposed energy usage as well as calibrate baseline and proposed energy simulation
models.
DCO Item(s):
III.B Modeling Energy Performance
Guideline 14-2002 describes that a simulation must be calibrated or checked against actual
measured energy use, energy bills, demand data, or other operating data. The calibrated model
must be used as a baseline condition. Savings can be determined by comparing the calibrated
model under two different sets of conditions or by comparing the baseline model to actual
metered data.
Appendix B7 of this guideline further summarizes calibrating simulation models:
“As described in clause 6.3 of this guideline, calibrated simulation is an appropriate
method to consider when one or more of the following conditions are present:
1. No pre-retrofit whole building hourly monitored data other than utility bills available,
while monitored post-retrofit data are available,
2. Retrofit measures interact with other building systems, and it is desired to account for
those interactions when savings are reported.
3. Only whole-building energy use data are available, and the [measurement and verifica-
tion] M&V calls for verifying savings due to individual retrofits.
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
ASHRAE Guideline 14 allows all three cases to be treated. It suggests that when
only whole building energy use is being monitored, that uncertainty be reported
solely for this energy use, and that no attempt be made to estimate uncertainty at a
more disaggregated level or for individual retrofits. A building energy simulation
model once calibrated with hourly data would still differ from the measured values.
This difference between modeled and measured hourly data allows the analyst to
compute a CV (coefficient of variation) just as when a regression model approach
was adopted. It is this CV that will be used along with equations (B13) or (B15)
(found in Appendix B) to estimate the fractional uncertainty.”
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
Guideline 14-2002 defines three standard approaches to determining energy savings:
• Whole-Building Approach. The most appropriate method when the total building
performance is to determined, rather than the performance of specific retrofits. Figure
6.1-1 (reproduced on p. 37) shows a flowchart of the whole-building approach.
• Retrofit Isolation Approach. This approach should be used when a whole-building
approach is not appropriate and the energy use can be determined by measurements
taken at a specific equipment or subsystem. Figure 6.2-1 (reproduced on p. 38) shows
a flowchart of the retrofit isolation approach.
• Whole-Building Calibrated-Simulation Approach. This approach is appropriate
when one or more of the following conditions are present:
• Either pre-retrofit or post-retrofit whole-building metered electrical
data are not available.
• Savings cannot be easily determined using before/after measurements.
• Measures interact with other building systems, and it is desired to account
for those interactions, and retrofit isolation methods are not readily feasible.
• Only whole-building energy use data are available, but savings from
individual retrofits are desired.
• Baseline adjustments are needed.
• Figure 6.3-1 (reproduced on p. 39) shows a flowchart of the calibrated-simulation
approach.
36
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
37
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
38
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
39
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
results. The information in Chapter 19 is especially relevant to energy modeling and
should be familiar to any energy modeler.
DCO Item(s):
I.A. Modeling Objectives
I.B. Analysis Methodologies
I.C. Software and Tool Selection
Chapter 19, Energy Estimating and Modeling Methods, in 2009 ASHRAE Handbook—
Fundamentals contains much information relevant to energy modeling. The chapter starts
with a description of its intention:
The definition of a model and two broad modeling approaches are described starting on
the first page of Chapter 19. Table 1 (reproduced on p. 42) classifies methods for analyzing
building energy use as either forward or data-driven and either steady-state or dynamic.
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Data-Driven
Empirical Physical
or Calibrated or
Method Forward Black-Box Simulation Gray-Box Comments
Steady-State Methods
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
Multistep parameter identification — — — X Uses daily data to determine overall heat
(Reddy et al. 1999) loss and ventilation of large buildings.
Dynamic Methods
The chapter’s Table 10 (reproduced above) presents a decision diagram for selecting a for-
ward or data-driven model where use of the model, degree of difficulty in understanding and
42
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
applying the model, the time scale for data used by the model, calculation time, and input vari-
ables used by the models are the criteria used to choose a particular model.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
There are a variety of modeling methods and it is important to use the right analytical
approach. Decision criteria for selecting the most appropriate calculation methodology
include accuracy, sensitivity, versatility, and ease of use, among others. Choosing an analysis
method is described on p. 19.3 of Chapter 19.
There are several analytical methods that can be developed using spreadsheet calculations.
These include degree-day method, temperature-bin method, and correlation. The two methods
are described in detail in Chapter 19.
Relevant Sections of 2009 ASHRAE Handbook—Fundamentals: Chapter 19 (pp. 19.1–
19.3, 19.17–19.22, 19.24–19.31)
DCO Item(s):
II.C. Building HVAC Systems
II.E. Other Internal and Process Loads
II.H. Controls
There are many elements that contribute to the cooling and heating loads on an HVAC sys-
tem, including external loads, internal loads, infiltration, and system loads. The energy mod-
eler should account for these elements. Chapters 17 and 18 of 2009 ASHRAE Handbook—
Fundamentals cover these topics and provide examples of calculating the heat gains of the
respective loads. Chapter 17 focuses on residential applications, whereas Chapter 18 focuses
on nonresidential applications. Chapter 19 gives further detail on building loads and also dis-
cusses the equipment end-use energy and controls.
The energy modeler should also be aware of the differentiation of the following heat flow
rates:
43
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
• Space Heat Gain. An instantaneous rate of heat gain at which heat enters into and/or is
generated within a space. Sensible heat is added directly to the conditioned space by
conduction, convection, and/or radiation. Latent heat gain occurs when moisture is
added to the space. Radiant heat is first absorbed by surfaces that enclose the space then
is released to the air by convection when the surfaces become warmer than the sur-
rounding air.
• Space Cooling Load. The rates at which sensible and latent heat must be removed
from the space to maintain a constant air temperature and humidity.
• Space Heat Extraction Rate. The rates at which sensible and latent heat are removed
equal to the space cooling load (if room air temperature and humidity are held con-
stant).
• Cooling Coil Load. The rate at which energy is removed at a cooling coil equals the
sum of instantaneous space cooling loads plus any system loads.
Energy absorbed by walls, floor furniture, etc., contributes to space cooling load only after
a time lag. Chapter 18 shows two calculation methods to take this time delay effect into con-
sideration: the heat balance (HB) method and the radiant time series (RTS) method.
Tables 1 through 10 of Chapter 18 (see samples, p. 48) list recommended heat gains for peo-
ple and equipment. Chapter 18 also includes detailed examples of cooling and heating load cal-
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
culations.
Modeling primary and secondary HVAC equipment and their controls is described in
Chapter 19.
Relevant Sections of 2009 ASHRAE Handbook—Fundamentals: Chapters 17, 18, 19
(pp. 19.3–19.17, 19.22–19.24)
DCO Item(s):
III.A. Simulation Comparisons
III.B. Modeling Energy Performance
IV.A. Verification and Troubleshooting of Simulation Results
IV.B. Analyzing and Comparing Modeling Results
IV.D. Sensitivity Analyses
44
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
METHODOLOGICAL BASIS
There are three ways to evaluate a whole-building energy simulation program’s accuracy (Judkoff et al. 1983; Neymark
and Judkoff 2002):
• Empirical validation, which compares calculated results from a program, subroutine, algorithm, or software object to
monitored data from a real building, test cell, or laboratory experiment
• Analytical verification, which compares outputs from a program, subroutine, algorithm, or software object to results
from a known analytical solution or a generally accepted numerical method calculation for isolated heat transfer under
very simple, highly constrained boundary conditions
• Comparative testing, which compares a program to itself or to other programs
Table 11 compares these techniques (Judkoff 1988). In this table, the term “model” is the representation of reality
for a given physical behavior. For example, heat transfer may be simulated with one-, two-, or three-dimensional
thermal conduction models. The term “solution process” encompasses the mathematics and computer coding to
solve a given model. The solution process for a model can be perfect, while the model remains inappropriate for a
given physical situation, such as using a one-dimensional conduction model where two-dimensional conduction
dominates. The term “truth standard” represents the standard of accuracy for predicting real behavior. An analytical
solution is a “mathematical truth standard,” but only tests the solution process for a model, not the appropriateness
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
of the model. An approximate truth standard from an experiment tests both the solution process and appropriateness
of the model within experimental uncertainty. The ultimate (or “absolute”) validation truth standard would be com-
parison of simulation results with a perfectly performed empirical experiment, with all simulation inputs perfectly
defined.
Internal Error Types
• Differences between actual thermal transfer mechanisms in the real building and its HVAC systems versus the simpli-
fied model of those processes in the simulation (all models, no matter how detailed, are simplifications of reality)
• Errors or inaccuracies in the mathematical solution of the models
• Coding errors
45
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
The simplest level of empirical validation compares a building’s actual long-term energy use to that calculated by a
computer program, with no attempt to eliminate sources of discrepancy. Because this is similar to how a simulation tool
is used in practice, it is favored by many in the building industry. However, it is difficult to interpret the results because
all possible error sources are acting simultaneously. Even if there is good agreement between measured and calculated
performance, possible offsetting errors prevent a definitive conclusion about the model’s accuracy. More informative lev-
els of validation involve controlling or eliminating various combinations of error types and increasing the density of out-
put-to-data comparisons (e.g., comparing temperature and energy results at time scales ranging from subhourly to annual).
At the most detailed level, all known sources of error are controlled to identify and quantify unknown error sources and
to reveal causal relationships associated with error sources.
This principle also applies to intermodel comparative testing and analytical verification. The more realistic the test case,
the more difficult it is to establish causality and diagnose problems; the simpler and more controlled the test case, the easier
it is to pinpoint sources of error or inaccuracy. Methodically building up to realistic cases is useful for testing interactions
between algorithms modeling linked mechanisms.
A comparison between measured and calculated performance represents a small region in an immense N-dimen-
sional parameter space. Investigators are constrained to exploring relatively few regions in this space, yet would like
to be assured that the results are not coincidental (e.g., not a result of offsetting errors) and do represent the validity
of the simulation elsewhere in the parameter space. Analytical and comparative techniques minimize the uncer-
tainty of extrapolations around the limited number of sampled empirical domains. Table 12 classifies these extrap-
olations. Use of the term “vice versa” in Table 12 is intended to mean that the extrapolation can go both ways (e.g.,
from short-term to long-term data and from long-term to short-term data). This does not mean that such extrapola-
tions are correct, but only that researchers and practitioners have either explicitly or implicitly made such inferences
in the past.
Figure 21 shows one process to combine analytical, empirical, and comparative techniques. These three techniques may
also be used together in other ways; for example, intermodel comparisons may be done before an empirical validation exer-
cise, to better define the experiment and to help estimate experimental uncertainty by propagating all known error sources
through one or more whole-building energy simulation programs (Hunn et al. 1982; Lomas et al. 1994).
For the path shown in Figure 21, the first step is running the code against analytical verification test cases to check its
mathematical solution. Discrepancies must be corrected before proceeding further.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
Second, the code is run against high-quality empirical validation data, and errors are corrected. Diagnosing error
sources can be quite difficult and is an area of research in itself. Comparative techniques can be used to create diagnostics
procedures (Judkoff 1988; Judkoff and Neymark 1995a, 1995b; Judkoff et al. 1980, 1983; Morck 1986; Neymark and Jud-
koff 2002; Spitler et al. 2001) and better define the experiments.
The third step is to check agreement of several different thermal solution and modeling approaches (that have passed
through steps 1 and 2) in a variety of representative cases. This uses the comparative technique as an extrapolation tool.
Deviations in the program predictions indicate areas for further investigation.
When programs successfully complete these three stages, they are considered validated for cases where acceptable
agreement was achieved (i.e., for the range of building, climate, and mechanical system types represented by the test
cases). Once several detailed simulation programs have satisfactorily completed the procedure, other programs and sim-
plified design tools can be tested against them. A validation code does not necessarily represent truth. It does represent a
set of algorithms that have been shown, through a repeatable procedure, to perform according to the current state of the art.
NREL methodology for validating building energy simulation programs has been generally accepted by the Interna-
tional Energy Agency (Irving 1988), ASHRAE Standard 140 and Addendum p to ASHRAE Standard 90.1, and else-
where, with refinements suggested by other researchers (Bland 1992; Bloomfield 1988, 1999; Guyon and Palomo
1999b; Irving 1988; Lomas 1991; Lomas and Bowman 1987; Lomas and Eppel 1992). Additionally, the Commission
of European Communities has conducted considerable work under the PASSYS program (Jensen 1989; Jensen and
van de Perre 1991).
46
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
II.A. Location and Climate Definition
Building energy use is typically dependent, in part, on local climatic conditions. Accord-
ingly, building energy modelers should account for climatic conditions in their models. Chap-
ter 14 (and the accompanying CD) of 2009 ASHRAE Handbook—Fundamentals provides “the
climatic design information for 5564 locations in the United States, Canada, and around the
world” (14.1). Chapter 14 provides procedures for generating and using temperature data in
formats suitable for energy modeling.
Relevant Sections of 2009 ASHRAE Handbook—Fundamentals: Chapter 14
DCO Item(s):
II.B. Building Envelope and Partitions
Heat transfer through a building’s envelope contributes to its heating and cooling loads
and, eventually, to its energy use. A building energy modeler must take care to properly define
envelope components and to account for the associated heat transfer through those surfaces.
2009 ASHRAE Handbook—Fundamentals provides information relevant to modeling the
building envelope and internal partitions.
47
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Table 1 Representative Rates at Which Heat and Moisture Are Given Off by Human Beings
in Different States of Activity (2009 ASHRAE Handbook—Fundamentals, Chapter 18)
Total Heat, W % Sensible Heat that
Sensible Latent is Radiantb
Adult Adjusted, Heat, Heat,
Degree of Activity Male M/F a W W Low V High V
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
a Adjusted heat gain is based on normal percentage of men, women, and chil- d Figure one person per alley actually bowling, and all others as sitting (117 W)
dren for the application listed, and assumes that gain from an adult female is or standing or walking slowly (231 W).
48
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
integrating fenestration into natural ventilation strategies that can reduce energy
use for cooling and fresh air requirements” (15.1).
Chapter 25 provides guidance in the analysis and design of building envelope assemblies
for good heat, air, and moisture control performance. This chapter discusses the fundamentals
of combined heat, air, and moisture movement as it relates to envelope assemblies.
Chapter 26 presents thermal and water vapor transmission data based on steady-state or
equilibrium conditions. This information can be used in the simplified calculation methods
described in Chapter 27 or in software-based methods that develop step-wise steady-state
conditions into a time-dependent solution. Table 4 shows typical thermal properties of vari-
ous building materials. Chapter 27 draws on Chapter 25’s fundamental information on heat,
air, and moisture transport in building assemblies, as well as Chapter 26’s material property
data. Examples demonstrate calculation of heat, moisture, and air transport in typical
assemblies.
Relevant Sections of 2009 ASHRAE Handbook—Fundamentals: Chapters 15, 25, 26, 27
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
49
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
According to Building Energy and Environmental Modelling (the BEEM Manual),
“This manual will be of interest to anyone who plays a role in creating energy-efficient
buildings that produce a healthy, comfortable and productive indoor environment.”
Energy modelers may use the BEEM Manual as a general guideline that covers the
entire process, from creating a computer-aided energy model to delivering the results to
the client.
DCO Item(s):
I.A. Modeling Objectives
Chapter 2 of the BEEM Manual discusses several modeling objectives, including the fol-
lowing:
The energy modeler should understand these concepts when beginning any building simu-
lation project in order to achieve the main goals of the interested parties.
Relevant Sections of Building Energy and Environmental Modelling: Chapter 2
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
DCO Item(s):
I.B. Analysis Methodologies
I.C. Software and Tool Selection
Subsection 4.1 of the BEEM Manual discusses considerations for approaches to choosing
analysis methodologies and software selection. An underlying knowledge of the algorithms
used in the methodologies and software will influence the energy modeler’s decision to
choose the appropriate program.
Subsection 3.2.3 discusses several simulation methods including annual, seasonal/bin, and
hourly simulations. The energy modeler should understand the basic concepts and the advan-
tages and disadvantages when choosing an appropriate method.
Relevant Sections of Building Energy and Environmental Modelling: Subsections 3.2.3, 4.1
DCO Item(s):
II.B. Building Envelope and Partitions
Subsection 3.2.1 of the BEEM Manual discusses building envelope considerations. The
energy modeler should understand the concepts of the load calculations presented in this sec-
tion. It is especially critical to accurately define a building envelope, especially when compar-
ing changes to exterior and interior building components.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
Relevant Sections of Building Energy and Environmental Modelling: Subsection 3.2.1
DCO Item(s):
II.C. Building HVAC Systems
Subsection 3.4 of the BEEM Manual discusses tools used to evaluate ventilation and air
movement. The subsection covers five methods for predicting airflow in buildings (empirical
airtightness, simplified theoretical, network, computational fluid dynamics, and physical mod-
eling). A computer program used for energy modeling may include one or some of these
methodologies, so it is important for the energy modeler to understand them when evaluating
airflow in a computer model.
Relevant Sections of Building Energy and Environmental Modelling: Subsection 3.4
DCO Item(s):
II.D. Lighting Systems
Subsection 3.3 of the BEEM Manual covers the analysis of lighting and daylighting. The
topics presented here are more relevant to lighting design than energy performance. However,
the topics are useful to the energy modeler for understanding the basic elements of lighting
and daylighting in computer-aided software.
Relevant Sections of Building Energy and Environmental Modelling: Subsection 3.3
DCO Item(s):
III.A. Simulation Comparisons
III.B. Modeling Energy Performance
52
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
53
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
IESNA Lighting
Handbook, 9th Edition
(IES)
RESOURCE DESCRIPTION
Patterns of light and dark affect both our perceptions of the world and our emotional and
physiological responses, and thus they are essential in gathering information about the physi-
cal world. Good-quality lighting can support visual performance and interpersonal communi-
cation and improve our feelings of well-being. Poor-quality lighting can be uncomfortable and
confusing and can inhibit visual performance. Illuminating Society of North America (IES) is
the recognized technical authority on illumination. For over ninety years, its objective has
been to communicate information on all aspects of good lighting practice to its members, to
the lighting community, and to consumers through a variety of programs, publications, and
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
services.
IESNA Lighting Handbook, 9th Edition, encourages good lighting principles and does not
prescribe the use of specific technologies. It guides the lighting designer to match and rank the
needs of the people using the space with the economic and environmental considerations and
the architectural objectives and then to translate the results into a workable design and func-
tional installation. Although this standard specifies the illumination levels for various spaces,
codes and standards have mandated the lighting power density (LPD) limits (such as
ASHRAE/IES Standard 90.1). Proper illumination levels must be achieved within the LPD
constraints specified by applicable codes and standards.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
DCO Item(s):
II.D. Lighting Systems
The lighting needs of a space must be defined to optimize proper allocation and manage-
ment of energy. Lighting needs may range from simple orientation to complex visual tasks.
Important considerations for prolonged visual tasks associated with work environments
include adequate illumination on the task surface, a proper balance of luminance between the
task surface and surrounding surfaces, control of direct and reflected glare, and acceptable
color rendering of task elements and surroundings. Other considerations also apply, depending
on the details of the specific visual task being performed.
When the nature and location of visual tasks can be identified, it is usually possible to
reduce surrounding ambient illumination and corresponding energy consumption by provid-
ing light more selectively where and when it is needed. When specific tasks and their locations
cannot be identified, a more uniform pattern of ambient illumination is generally provided,
along with provisions for task lighting and local control. In applications where there are no
prolonged visual tasks, lighting for emphasis, aesthetics, and safety are prime considerations.
Lighting needs for specific applications can be found in Chapter 10, Quality of the Visual
Environment, of the handbook. Chapter 26, Energy Management, covers some basics on light
sources, daylighting, and luminaires.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
Relevant Sections of IESNA Lighting Handbook: Chapters 10, 26, 27
DCO Item(s):
II.H. Controls
Generally, light sources are equipped with controls to either enhance or match the light
levels of a space for aesthetic appeal or for energy management. Aesthetic controls provide
the ability to change space functions and can create emotional appeal, offering control of
lighting quality, mood, color, and attitude. Energy management controls for lighting systems
provide energy and cost savings through reduced power or reduced time of use.
Lighting controls for energy management should be implemented centrally, over an entire
building, or locally, in individual areas. Various combinations of these two levels of control
are also common. Central lighting control systems allow for lighting load scheduling to
reduce peak demand as well as provide the ability to monitor and control total energy use.
Central lighting control systems can be interfaced with overall building management systems
(BMSs). A building also can be divided into areas that have different lighting needs and
require different control strategies. For example, perimeter zones consisting mainly of private
offices should be differentiated from core zones using an open-plan landscape. Private offices
are good candidates for manual and automatic lighting control because they have unpredict-
able occupancy schedules, are typically low-traffic areas requiring task-level illumination only
when occupied, and often use a significant daylight contribution. Areas where there is signifi-
cant daylight contribution are perfect candidates for daylighting controls: the power for elec-
tric lighting varies in response to the amount of daylighting available. Both dimming and
switching strategies can be used. For successful application of daylight-based switching, high
levels of daylight must be present so that sufficient illumination for the task remains after the
electric lighting has been lowered. Proper use of controls can assist with compliance with
56
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
ASHRAE/IES 90.1 Standard, reduce building operating costs, and significantly benefit the
environment.
It is incumbent on the engineer and lighting designer to be aware of the wide variety of
electronic lighting controls available and to correctly apply them to the project at hand. As
with all technology-driven areas, the energy modeler and the design team must stay current in
the field to be able to develop accurate models that can be used to make strategic economic
decisions during the building or renovation phase of a project.
Relevant Sections of IESNA Lighting Handbook: Chapter 27
DCO Item(s):
IV.C. Economic Analysis
Economic considerations invariably drive the decision-making process of any project, and
lighting design is no exception. The lighting professional must factor the economic consider-
ations as part of the overall design criteria. The economic analysis should be viewed as a
framework within which all of the needs of the client must be taken properly into account.
A comprehensive lighting economic analysis for new or existing systems should do the
following:
• Compare alternative systems
• Evaluate maintenance techniques and procedures
• Evaluate energy management technologies and strategies
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
• Determine the effect of lighting on other building systems
• Plan budget and cash flow
• Simplify lighting system characteristics to a cost measure
• Determine the benefit of lighting relative to its life-cycle cost
Chapter 25 of the handbook covers simple payback calculation as well as the life-cycle
cost benefit analysis (LCCBA) of a lighting project.
Relevant Sections of IESNA Lighting Handbook: Chapter 25
57
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Solar Radiation
and Daylight Models
(T. Muneer)
RESOURCE DESCRIPTION
Solar Radiation and Daylight Models provides guidelines for computing solar radiation
and daylight for different building types.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
world. Energy modelers can use this information to accurately predict the effect of solar
radiation and daylight on baseline and proposed energy models.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
tributes to its heating and cooling loads and eventually to its energy use. A building energy
modeler must take care to properly identify the significant modes of heat transfer for a given
project. The effect of these heat transfers must be accounted for in the building energy model.
Mechanical HVAC systems most commonly use fluids to transfer heat from or to the
conditioned space. Fluid heat exchangers (e.g., air-to-air, air-to-water, etc.) are the back-
bone of HVAC systems. A well-defined energy model should accurately account for the
characteristics of fluid flow in a building and for the effect of system heat exchangers.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
ing. Much of what is presented within the book is an overview, with limited details about
many of the most important building systems that an energy modeler must understand,
particularly the HVAC system. The book does provide a good reference for envelope heat
gain calculations, particularly those involving solar heat gain.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
modeling buildings. The position of the sun at any instant with respect to an observer is
defined by the altitude angle and azimuth angle. The altitude angle is the angle between the
horizon and the sun’s position above the horizon. The azimuth is the angle between the
sun’s projection and true south.
Sunpath projection charts define the sun’s position throughout the year. They can be used
to assess site condition, orient a building, or provide information critical for passive solar
design. Section 6.4 provides descriptions of various types of sunpath projection charts and
how they are derived.
Relevant Sections of Mechanical and Electrical Equipment for Buildings: Chapter 6
DCO Item(s):
II.B. Building Envelope and Partitions
Shading windows from solar heat gains reduces heat loads in any building. Chapter sec-
tion 6.5 discusses different shading approaches. Section 6.6 discusses the use of shadow
angles and shading masks to design shading devices.
Chapter 7 describes the various heat flow paths within a building, including sensible and
latent heat flow through the opaque envelope, heat flow through fenestration, and heat flow
via air movement. The book discusses the fundamental difference between static and dynamic
approaches to modeling heat flow. Under a static simulation, the key building component is
the thermal resistance, whereas in a more complicated dynamic simulation, the thermal capac-
itance must also be considered. The book describes the key static thermal properties of enve-
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
lope materials, including conductivity, conductance, resistance, and emittance. The thermal
performance of air films is also discussed. Finally, the composite thermal performance of an
architectural assembly is defined as the overall heat transfer rate or U-factor. The building
energy modeler must understand these concepts to appropriately model the thermal perfor-
mance of the envelope of any building. The book provides representative values for resistance
of the various building construction materials used for walls, roofs, floors, and doors. The
book also discusses special considerations of external heat transfer on below-grade floors.
For dynamic simulations, it is necessary to consider additional building material proper-
ties, such as density, specific heat, and thermal capacity. The book defines these properties
and discusses their relevance to time lag, which is a measure of the delay in the flow of heat.
Time lag has a significant effect when modeling building environments because the greatest
heat load on the HVAC system does not always coincide with the greatest internal and exter-
nal loads.
Chapter section 7.4 describes the latent heat loads through the opaque envelope. The flow
of moisture is driven by vapor pressure differential. The permeance of the building material is
the rate at which moisture is transferred through the material.
As with the opaque envelope, the thermal performance of windows is also defined by the
U-factor or overall heat transfer rate. Unlike opaque surfaces, windows have different conduc-
tivities in different areas, depending on whether they are at the center of the glass, along the
edge, or on the frame. The U-factor is the combined heat transfer rate given these different
characteristics. In addition to the U-factor, the thermal performance of a window is also char-
acterized by the solar heat gain coefficient (SHGC). The SHGC is the percentage of solar radi-
ation incident upon a window that enters a building as heat. SHGCs typically range from 20%
to 90% and depend upon type of class, number of panes, tinting, and reflective coating. The
book also defines the shading coefficient (SC), which is a different method of describing the
64
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
same characteristic of the glass. The SC is the ratio of the radiant heat gain through a given
glass type relative to a 1/8 in. single-pane clear glass.
The visible transmittance (VT) is yet another glass property that pertains mainly to day-
lighting and daylighting controls. The VT of a window is the percentage of optical light that
passes through a particular glazing. The VT and SHGC are not always interdependent, and the
ratio between the two (light-to-solar ratio [LSG]) indicates whether a glazing is appropriate
for daylighting in a particular climate.
Infiltration is discussed in Section 7.7a. The book describes the two main approaches to
modeling infiltration: the air-change method and the crack method. (For more detail, also refer
to Chapter 16 of 2009 ASHRAE Handbook—Fundamentals.)
Section 7.8 discusses heat loss and gain calculations. The book describes in detail the pro-
cedures and equations used to calculate the design heat loss for a building. The calculation of
design heat gain is a much more complicated calculation, primarily because it requires a
dynamic heat flow analysis. An approximate method for calculating heat gain is presented in
Chapter section 8.11. Table 8.13 gives a comparison of the different detailed methods of cal-
culating heat gain.
Relevant Sections of Mechanical and Electrical Equipment for Buildings: Chapters 7, 8;
Chapter sections 6.5, 6.6
DCO Item(s):
II.C. Building HVAC Systems
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
Chapter section 5.6 presents an overview of various building components used to control
indoor air quality. The equipment discussed includes exhaust fans, makeup air units, air-to-air
heat exchangers, energy recovery ventilators, heat pipes, enthalpy wheels, and desiccant cool-
ing components. None of these components are described in any great detail.
Chapter 9 presents HVAC systems for smaller buildings, including (1) cooling-only sys-
tems such as air conditioners, evaporative coolers, and indirect evaporative coolers; (2)
heating-only systems such as wood-burning furnaces, electric resistance heaters, gas-fired
heaters, hot-water boilers, and radiant systems; and (3) heating and cooling systems such as
ground-source and water-source heat pumps.
Chapter section 9.9 discusses psychrometrics and refrigeration. The concept of the sensible
heat factor is discussed as it pertains to building cooling systems. This is an important concept
that must be understood in order to size cooling equipment appropriately. An example is pro-
vided to illustrate the importance of considering latent loads when sizing cooling equipment.
Chapter 10 presents HVAC systems for larger buildings and discusses some general concepts
that must be understood by any building energy modeler, including zoning strategies, HVAC
system anatomy, and distribution systems. The chapter provides a brief overview of various
zone-level system types, including single-duct variable-air-volume (VAV) systems, fan-powered
VAV systems, VAV reheat systems, dual-duct systems, induction systems, fan-coil systems, radi-
ant panels, and water-loop heat pumps. The descriptions are limited, but diagrams are provided
that may be helpful for the novice energy modeler looking for an introduction to these types of
systems. The chapter provides additional detail about the various types of boilers, including how
to calculate boiler horse power. The section on chillers describes the basics of absorption and
vapor-compression chillers. Cooling towers are only discussed briefly, with little detail. A few
energy-efficiency devices or systems are also briefly discussed, including boiler flue economiz-
ers, runaround coils, economizers, geoexchange systems, and thermal energy storage. Much of
65
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
the content comes from examples or case studies of the systems in question. Air-handling equip-
ment is also present with limited detail, including a brief description of the different fan types.
Relevant Sections of Mechanical and Electrical Equipment for Buildings: Chapter sec-
tions 5.6, 9.6, 9.7, 9.8, 9.9, 10.1, 10.2, 10.3, 10.4, 10.5, 10.6
DCO Item(s):
II.D. Lighting Systems
Chapter 11 provides an in-depth description of lighting fundamentals. Although not
directly relevant to energy modeling, the concepts discussed provide a background for the
lighting design process discussed in Chapter 13.
Chapter 12 is focused on light sources, which is more directly relevant to energy model-
ing. The book describes the standard lamp types, including incandescent lamps, halogen
incandescents, fluorescent lamps, compact fluorescents, and high-intensity discharge lamps.
The primary characteristic of concern to the energy modeler is the efficacy of the lamp, which
is the light output divided by the power input. Table 12.1 provides typical efficacies for vari-
ous light sources. The efficacy is required in order to calculate the LPD in a building energy
model. Other concepts discussed for each lamp type include lamp life and lumen mainte-
nance, which is the depreciation of efficacy with time.
Chapter section 12.11 describes ballasts, which are required for all gaseous discharge
lamps to trigger the lamp with high ignition voltage and to control the amount of electric cur-
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
rent for proper operation. The ballast has a significant impact on the overall power consump-
tion of a lighting fixture.
Chapter section 13.7 discusses the energy considerations of lighting systems. The book
covers various approaches to energy-efficient design, including energy-efficient luminaires,
thermally controlled luminaires, daylighting, and control strategies, among others. Figure 13.2
provides a reference for determining where heat produced by a lighting fixture is transferred,
depending on type and location. The building energy modeler must be familiar with this con-
cept to accurately estimate the impact of the lighting system on the HVAC load.
Chapter sections 15.18 to 15.33 provide additional detail about lighting design calcula-
tions, including the calculation of average illuminance, horizontal illuminance, the light loss
factor, and the zonal cavity method. The topics covered are beyond the scope of most building
energy modelers, except those who are directed to provide a detailed lighting design or feed-
back on one.
Relevant Sections of Mechanical and Electrical Equipment for Buildings: Chapters 11,
12; Chapter sections 13.7, 15.18–15.33
DCO Item(s):
II.E. Other Internal and Process Loads
II.F. District Energy Systems
Chapter sections 10.8 and 10.9 conceptually discuss district heating/cooling systems and
cogeneration systems. Section 10.8 focuses on high-temperature-water and chilled-water sys-
tems. Section 10.9 discusses several different types of cogeneration systems, including tur-
bines, reciprocating engines, and fuel cells. None are discussed in great detail.
Relevant Sections of Mechanical and Electrical Equipment for Buildings: Chapter sec-
tions 10.8, 10.9
66
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
DCO Item(s):
II.G. Renewable Energy Systems
Chapter 29 describes photovoltaic (PV) systems. The book provides detail about PV cells
and arrays as well as the configuration of various PV systems, including stand-alone systems
with energy storage and grid-tied systems. Battery technologies are also discussed with some
detail on different types of batteries, voltage requirements, life, and ratings. Simple, single-
line wiring diagrams are provided, which greatly assist in the understanding of these complex
systems. The book also addresses some economic considerations at a high level.
Finally, the book provides a step-by-step approach for the design of stand-alone and grid-
tied PV systems, including a discussion of the current codes and standards that apply to both
types of systems.
DCO Item(s):
II.H. Controls
Chapter sections 15.13 to 15.17 address lighting control systems. The book discusses the
two basic types of control functions: switching and dimming. Switching lamps and fixtures off
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
will provide discrete steps in light levels and power consumption with efficacy maintained at
full lamp output levels. Dimming provides a continuously variable light level at a variable
power input. Depending on the type of lamp, the efficacy will change as light levels are
reduced. Figure 15.22 shows a graph of typical part-load lumen output and power input for
various lamp types. The book describes the two types of control initiation—manual and auto-
matic. Automatic controls may consist of time scheduling or occupancy sensing. Finally, day-
light compensation is also discussed in this chapter.
Chapter section 21.5 discusses well water supply, including the types of pumps required
for water extraction. Section 21.6 discusses domestic hot-water (DHW) systems and equip-
ment. Temperature setpoint requirements for various uses are provided in Table 21.6. Water-
heating systems and equipment discussed include storage tank water heaters, circulating-
storage water heaters, tankless heaters, solar water-heating systems, and heat pump water
heaters. The chapter provides details about the selection and sizing of DHW systems. Table
21.10 provides an estimate of the water usage for various building types on a per person
basis. Chapter sections 21.9 and 21.10 discuss domestic water distribution systems, including
piping, valves, and controls. It is necessary to understand the domestic water system in order
to estimate the energy use associated with the pumping and DHW heating required.
Chapter sections 31.42 to 31.45 discuss the power and energy requirements for vertical
transportation systems. In detailed energy models, it is necessary to account for this power
demand and energy usage.
Relevant Sections of Mechanical and Electrical Equipment for Buildings: Chapter sec-
tions 15.13–15.17, 21.5, 21.6, 21.9, 21.10, 31.42–31.45
67
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Appendix A—
BEMP Certification DCO
Application
Analysis
Building Energy Modeling Professional Examination
Recall
Totals
Detailed Content Outline'&2*
Open cells show an examination could include items from indicated cognitive levels.
Shaded cells prevent appearance of items on examinations.
A. Modeling Objectives 0 1 2 3
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
1. Define the purpose of the modeling study
2. Interpret the design intent of the building project
3. Evaluate the completeness of the design and operation
information
4. Link required project deliverables to goals of the modeling study
B. Analysis Methodologies 2 3 3 8
1. Differentiate among calculation methods within available software
and tools e.g.,
a. time-neutral e.g.,
x bin method x degree day
b. time-sequencing e.g.,
x heat balance x thermal network
x weighting factor x parametric
2. Evaluate mathematical modeling methods for building
components e.g.,
x empirical x first-principle of thermodynamics
x regression
3. Translate a building project into an energy model
a. simplify building physics to a mathematical model
b. anticipate the impact of simplification and model deficiencies
C. Software and Tool Selection 1 2 1 4
1. Evaluate the appropriateness of the methodology by
characteristics of the project e.g.,
x project phase x climate
x building type
2. Select the optimal software and tools to meet output data needs
of the project e.g.,
x life-cycle cost analysis x individual component
x energy use and demand performance
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Application
Analysis
Building Energy Modeling Professional Examination
Recall
Totals
Detailed Content Outline'&2*
Open cells show an examination could include items from indicated cognitive levels.
Shaded cells prevent appearance of items on examinations.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
x temperature x solar
x humidity x elevation
x precipitation x wind
2. Choose the best source of weather data for a project e.g.,
x long-term representative x geographically equivalent
x constructed x historical for a time period
3. Identify site characteristics e.g.,
x microclimates x reflectance
x orientation x vegetation effects
x adjacent buildings x local wind
x shading x solar effects
B. Building Envelope and Partitions 1 3 2 6
1. Model exterior and interior opaque surface performance e.g.,
x geometry x thermal transmission and
x boundary conditions capacitance
2. Model ground-coupled surface performance
3. Model fenestrations e.g.,
x solar heat gain x glazing
x shading x framing
x reflectance x spectral
4. Model building airflow e.g.,
x psychrometrics x driving forces of infiltration
x air-tightness
70
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Appendix A
Application
Analysis
Building Energy Modeling Professional Examination
Recall
Totals
Detailed Content Outline'&2*
Open cells show an examination could include items from indicated cognitive levels.
Shaded cells prevent appearance of items on examinations.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
4. Model packaged systems e.g.,
x split x packaged terminal air-conditioner
x roof-top
5. Model ventilation e.g.,
x mechanical x natural
D. Lighting Systems 1 1 1 3
1. Model artificial lighting power
2. Model daylighting e.g.,
x glare x illuminance
3. Distribute lighting heat gain among room, return, and plenum
E. Other Internal and Process Loads 2 2 3 7
1. Differentiate between space loads and building loads
2. Model loads as sensible, latent, or radiant fractions and thermal
distribution e.g.,
x occupants x vertical transportation
x water heating x commercial refrigeration
x plug loads x external lighting
x appliances x special processes
F. District Energy Systems 0 1 1 2
1. Model purchased energy
2. Model shared energy systems
71
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Application
Analysis
Building Energy Modeling Professional Examination
Recall
Totals
Detailed Content Outline'&2*
Open cells show an examination could include items from indicated cognitive levels.
Shaded cells prevent appearance of items on examinations.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
d. outside air ventilation e.g.,
x quantity x temperature
x quality x demand-control
x humidity
e. supply and return flow e.g.,
x economizers x maximum and minimum
x exhaust x capacity control
2. Model lighting controls e.g.,
x illuminance x energy-rate based
x occupancy x glare considerations
x time-based x dimming
3. Model controls for miscellaneous equipment e.g.,
x service hot water x vertical transportation
x process equipment
4. Describe basic control sequences e.g.,
x 2-position x proportional integral derivative
x scheduled
5. Sequence equipment to manage loads e.g.,
x pumps x large plant equipment
x fans
72
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Appendix A
Application
Analysis
Building Energy Modeling Professional Examination
Recall
Totals
Detailed Content Outline'&2*
Open cells show an examination could include items from indicated cognitive levels.
Shaded cells prevent appearance of items on examinations.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
x forensics x measurement and verification
x utility bills
B. Modeling Energy Performance 2 3 1 6
1. Choose whole-building metrics e.g.,
x cost x source energy consumption
x emissions x site energy consumption
x demand
2. Choose component metrics e.g.,
x equipment usage x component performance
x equipment sizes
3. Choose metrics for indoor environmental performance e.g.,
x temperature x ventilation rate
x humidity x daylighting
C. Evolution of Simulation Techniques to Meet Project Methods and
Objectives 0 1 1 2
1. Adapt simulations to the project phase
2. Customize simulations for changes in building use
73
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Application
Analysis
Building Energy Modeling Professional Examination
Recall
Totals
Detailed Content Outline'&2*
Open cells show an examination could include items from indicated cognitive levels.
Shaded cells prevent appearance of items on examinations.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
4. Review data for anomalies
5. Reconcile anomalies using single time-step reports
6. Resolve loads not met and hours outside of control range
B. Analyzing and Comparing Modeling Results 2 4 2 8
1. Analyze simulation outputs e.g.,
x component metrics x whole building metric
x energy use intensity
2. Compare outputs to targets e.g.,
x rating programs x building labelling programs
x codes
C. Economic Analyses 1 1 1 3
1. Determine effects of utility rate structures and regulations on
costs
2. Calculate financial metrics e.g.,
x life-cycle costing x investment performance
x cash flow x client financing needs
3. Estimate the effects of incentives
D. Sensitivity Analyses 0 1 1 2
1. Perform a sensitivity analysis on modeling assumptions
2. Identify critical synergistic interactions of building components
74
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Appendix A
Application
Analysis
Building Energy Modeling Professional Examination
Recall
Totals
Detailed Content Outline'&2*
Open cells show an examination could include items from indicated cognitive levels.
Shaded cells prevent appearance of items on examinations.
E. Project Deliverable 1 1 1 3
1. Communicate results
2. Communicate methodology and assumptions on which results are
based
3. Submit documentation that affirms the accuracy and
completeness of results
4. Recommend actions
Totals 25 41 34 100
*
Each new test form will include two 15-item pretests (e.g., 1A, 1B).
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
75
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson
© ASHRAE (www.ashrae.org). For personal use only.
Copyrighted material licensed to Faheem Mushtaq on 2016-05-12 for licensee's use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
All rights reserved. No further reproduction or distribution is permitted. Distributed for ASHRAE by Thomson Reu
Excerpts of the relevant publications are included in the study guide, along with
the program’s full detailed content outline (DCO), which is a blueprint for the
certification examination, and a DCO matrix that serves as a road map for identifying
the essential resources for ASHRAE’s BEMP certification program. It lays out in a
single table which sections of the resources are applicable to the different sections
of the examination. As much as possible, this study guide identifies the specific
areas on the program’s DCO that each reference helps support.
This publication is also a valuable resource for any individual in the building
energy modeling field, whether aiming to be ASHRAE certified or not. Full of a
• Road map to prepare for ASHRAE’s BEMP certification
multitude of references, this guide serves as an indispensable source of information • Excerpts from ASHRAE resources for energy modeling
related to building energy modeling.
• Where to find other essential energy modeling guidance
• How each resource impacts energy modeling
ISBN 978-1-936504-19-0 • Review of resources needed for energy modeling practitioners
ASHRAE
1791 Tullie Circle
Atlanta, GA 30329-2305
Phone: (404) 636-8400 (worldwide)
www.ashrae.org 9 7 8 1 9 3 65 0 4 1 90 ASHRAE
Product code: 90287 1/12