iPRF and iPRD Surge Arresters

The document summarizes surge arrester products for electrical installations, including their specifications and applications. It recommends Type 1 surge arresters for installations protected by a lightning protection system. These protect against direct lightning strikes and conduct current from the earth conductor to network conductors. Surge arresters must be installed with an upstream disconnection device rated for the maximum short-circuit current.

Uploaded by

Robert Camargo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
997 views36 pages

iPRF and iPRD Surge Arresters

The document summarizes surge arrester products for electrical installations, including their specifications and applications. It recommends Type 1 surge arresters for installations protected by a lightning protection system. These protect against direct lightning strikes and conduct current from the earth conductor to network conductors. Surge arresters must be installed with an upstream disconnection device rated for the maximum short-circuit current.

Uploaded by

Robert Camargo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 36

iPRF1 12.

5r/PRD1 35r/PRD1 25r/PRD1 Master


The Type 1 surge arrester is recommended for electrical installations in the service
sector and industrial buildings protected by a lightning conductor or by a meshed
cage.
It protects electrical installations against direct lightning strikes.
It is used to conduct the direct lightning current, propagating from the earth
conductor to the network conductors.
It must be installed with an upstream disconnection device, such as a fuse or
circuit-breaker, whose breaking capacity must be at least equal to the maximum
prospective short-circuit current at the installation point.
iPRF1 12.5r and PRD1 25r surge arresters also provide Type 2 protection and

DB119038
DB408470
PB104275-35-b

iPRF1 12.5r (1P+N, 3P+N)


Type Product solution

Fixed surge 1P+N 3P+N


arrester
iPRF1 12.5r (3P+N) PRD1 35r (1P) iPRF1 12.5r A9L16632 A9L16634
T1, T2
PB104260-35

DB119036

DB119037

PRD1 25r (1P+N, 3P+N) PRD1 Master (1P+N, 3P+N)


Cartridge 1P+N 3P+N
surge arrester
PRD1 25r 16330 16332
T1 + T2
PRD1 25r (3P+N)

PRD1 Master 16361 16363


T1
PB104264-35

PRD1 35r
T1

PRD1 Master (3P+N)

284 Version : 2.5 11/01/2017 CA903005E


DB123384

DB118911

DB119039

PRD1 35r (1P) iPRF1 12.5r (3P) PRD1 35r (2P, 3P, 4P)
Earthing Recommended
system accessory
1P 2P 3P 4P

TT, TN-S
A9L16633 TN-C
DB122528
DB122527

DB122527

PRD1 25r (1P) PRD1 25r (2P, 3P, 4P) PRD1 Master (2P, 3P, 4P)
1P 2P 3P 4P

TT, TN-S
16329 2 x 16329 4 x 16329 TT, TN-C
16331 TN-C
TT, TN-S
16360 2 x 16360 4 x 16360 TT, TN-C
16362 TN-C
2 x 16649 IT distributed neutral, 16643
TT, TN-S
16649 3 x 16649 IT non-distributed 16644
neutral, TN-C
4 x 16649 IT distributed neutral 16645

CA903005E Version : 2.5 11/01/2017 285


Type Nb. of Width I imp (kA) I max (kA) In - kA Up - kV Un - (V) Uc - V Cat. no.
poles (10/350) (8/20) Nominal Voltage Rated Maximum
Impulse Maximum discharge protection voltage continious
current discharge current level network operating
current voltage
Fixed surge 9 mm (L-N)/(N-PE)
arrester modules
iPRF1 12.5r Type 1 + 2
1P+N 4 12.5 (L-N)/50 (N-PE) 50 25 1.5 230 350/255 A9L16632
3P 8 12.5 50 25 1.5 230/400 350 A9L16633
3P+N 8 12.5 (L-N)/50 (N-PE) 50 25 1.5 230/400 350/255 A9L16634
Withdrawable surge arrester
PRD1 25r Type 1 + 2
1P 4 25 40 25 1.5 230 350 16329
1P+N 8 25 (L-N)/100 (N-PE) 40 25 1.5 230 350/350 16330
3P 12 25 40 25 1.5 230/400 350 16331
3P+N 16 25 (L-N)/100 (N-PE) 40 25 1.5 230/400 350/350 16332
PRD1 Master Type 1
1P 4 25 50 25 1.5 230 350 16360
1P+N 8 25 (L-N)/100 (N-PE) 50 25 1.5/2.5 230 350/350 16361
3P 12 25 50 25 1.5 230/400 350 16362
3P+N 16 25 (L-N)/100 (N-PE) 50 25 1.5/2.5 230/400 350/350 16363
PRD1 35r Type 1
1P 4 35 50 35 2.5 230/400 440 16649
Spare cartridge
C1 Master-350 - 4 - - 25 1.5 - 350 16314
C1 25-350 - 23 mm - - 25 1.5 - 350 16315
C2 40-350 - 12 mm - - 20 1.5 - 350 16316
C1 Neutral-350 - 4 - - - - - 350 16317
C1 35-440 - 4 - 35 2.5 - 440 16318

Surge arresters Spare cartridge


Phase Neutral
Type 1 Type 2
PB104268-30

PRD1 25r
PRD1 25r 1P 16315 16316 -
PRD1 25r 1P+N 16315 16316 16317
PRD1 25r 3P 3 x 16315 3 x 16316 -
PRD1 25r 3P+N 3 x 16315 3 x 16316 16317
PRD1 Master
PRD1 Master 1P 16314 - -
C1 Neutral-350
PRD1 Master 1P+N 16314 - 16317
PRD1 Master 3P 3 x 16314 - -
PRD1 Master 3P+N 3 x 16314 - 16317
PRD1 35r
PRD1 35r 1P 1 x 16318 - -
PRD1 35r 2P 2 x 16318 - -
PRD1 35r 3P 3 x 16318 - -
PRD1 35r 4P 4 x 16318 - -

Accessories
DB123370

Type Number of poles (18 mm)


Wiring comb busbars for 2 x 1P 4 16643
Wiring comb busbars for 3 x 1P 6 16644
Wiring comb busbars for 4 x 1P 8 16645
- 16646

286 Version : 2.5 11/01/2017 CA903005E


Technical data
iPRF1 12.5r PRD1 35r PRD1 25r PRD1 Master
Operating frequency 50 Hz 50/60 Hz 50 Hz 50 Hz
Degree of protection Front panel IP40 IP40 IP40 IP40
Terminals IP20 IP20 IP20 IP20
Impacts IK05 IK05 IK05 IK05
Response time 25 ns 100 ns 25 ns 100 ns
Short circuit withstand (Isccr) 50 kA 50 kA 25 kA 50 kA
Temporary overvoltage UT (L-N) 335 V AC/5 s 580 V AC/5 s 415 V AC/5 s 415 V AC/5 s
withstand (UT) UT (N-PE) 1200 V AC/200 ms 800 V AC/120 min 1200 V AC/200 ms 1200 V AC/200 ms
Temporary overvoltage Safe UT (L-N) 440 V AC/120 min 1640 V AC/200 ms 440 V AC/120 min 440 V AC/120 min
failure mode (UT)
Ground residual current (IPE) IPE (N-PE) 0.004 mA 0.005 mA 0.01 mA for 1P+N, 3P+N 0.01 mA for 1P+N, 3P+N
Follow current interrupting rating I (L-N) - 50 kA 25 kA/264 V AC 50 kA
(I ) 3 kA/350 V AC
I (N-PE) 100 A - 100 A 100 A
End-of-life indication Green: correct operation White: correct operation White: correct operation White: correct operation
Red: at end of life Red: at end of life Red: at end of life Red: at end of life
Remote 1.5 A/250 V AC 1 A/250 V AC 1 A/250 V AC 1 A/250 V AC
1 A/30 V DC 1 A/30 V DC 1 A/30 V DC
By tunnel terminal Rigid cable 10...35 mm² 16...35 mm² 10...35 mm² 10...35 mm²
Flexible 10...25 mm² 10...25 mm² 10...25 mm² 10...25 mm²
cable
Operating temperature -25°C to +60°C -40°C to +80°C -40°C to +80°C -40°C to +80°C
Humidity range 5 % to 95 % 5 % to 95 % 5 % to 95 % 5 % to 95 %
Standards IEC 61643-11: 2011 T1, T2 IEC 61643-11 T1 IEC 61643-11: 2011 T1, T2 IEC 61643-11: 2011 T1
EN 61643-11: 2012 Type 1 EN 61643-11 Type 1 EN 61643-11: 2012 Type 1 EN 61643-11: 2012 Type 1
+ Type 2 + Type 2
Approvals CE, EAC CE CE, KEMA-KEUR CE, KEMA-KEUR

Choice of disconnector / surge arrester


Type I imp: Isc: prospective short-circuit current at the installation point
impulse 10 kA 15 kA 25 kA 36 kA 50 kA
current
iPRF1 12.5r 12.5 kA C120N 80 A curve C C120H 80 A curve C NG125N 80 A curve C NG125H 80 A curve C NG125L 80 A curve C
or Compact NSX100B or Compact NSX100B or Compact NSX100B or Compact NSX100F or Compact NSX100N
100 A * 100 A * 100 A * 100 A * 100 A *
PRD1 35r 35 kA Compact NSX160B 160 A Compact NSX160F Compact NSX160N
160 A 160 A
PRD1 25r 25 kA Compact NSX100B 100 A -
PRD1 Master 25 kA Compact NSX100B 100 A Compact NSX100F Compact NSX100N
100 A 100 A
(*) For lightning impulse current withstand
PB113739-90

PRD1 25r / PRD1 Master /


PRD1 35r Reversible
The surge arrester base can be turned
over to allow the phase/neutral/earth
cables to enter through either the top or
the bottom

CA903005E Version : 2.5 11/01/2017 287


Dimensions (mm)

DB123928
DB408471

PRD1 35r iPRF1 12.5r


DB123929

PRD1 Master
DB123930

PRD1 25r

Weight (g)
Surge arresters
Type iPRF1 12,5r PRD1 35r PRD1 25r PRD1 Master
1P - 401 334 394
1P+N 290 - 725 774
3P 590 - 1010 1175
3P+N 590 - 1338 1535
Cartridge Neutral - - 229 229
Phase - 245 - 242

288 Version : 2.5 11/01/2017 CA903005E


CA903001E Version : 3.4 11/01/2017 289
incoming protection (type 2):
the iPF65(r) is recommended for a very high risk level (strongly exposed site)
the iPF40(r) is recommended for a high risk level
the iPF20 is recommended for a medium risk level
secondary protection (type 2 or 3):
the iPF8 ensures secondary protection of loads to be protected and is placed in
cascade with the incoming surge arresters. This surge arrester is required when the
loads to be protected are at a distance of more than 10 m from the incoming surge
arrester.

The iPF surge arresters with “r” indication have remote transfer of the information:
“surge arrester to be replaced”.

Rated discharge Type of protection Network


current (Imax) /

DB122942

DB122943
Nominal discharge
current (In)

Incoming Secondary 1P+N 3P+N 1P 2P 3P 4P


(type 2 or 3)
65 kA / 20 kA
PB105278-35

Very high risk level iPF65 A9L15683


A9L15684
A9L15584
A9L15581
A9L15685
A9L15586
A9L15585
40 kA / 15 kA
High risk level iPF40 A9L15686
A9L15687
1P+N. A9L15587
A9L15582
A9L15690
A9L15688
A9L15590
PB105280-35

A9L15588
20 kA / 5 kA
Medium risk level iPF20 A9L15691
A9L15692
A9L15592
A9L15597
A9L15693
A9L15593
8 kA / 2.5 kA
Secondary protection: iPF8 A9L15694
3P+N. placed near the loads to be A9L15695
protected when they are at a A9L15595
distance of more than 10 m
from the incoming surge A9L15598
arrester A9L15696
A9L15596

Surge arrester/circuit breaker association


Type of surge arrester Associated circuit breaker
iPF65 Curve C 50 A
iPF40 Curve C 40 A
iPF20 Curve C 25 A
iPF8 Curve C 20 A

290 Version : 3.4 11/01/2017 CA903001E


Earthing Transfer Surge Width Up - (kV) Un - (V) Uc - (V)
system arrester in mod. Voltage protection level Rated Maximum continuous
name of 9 mm voltage operating voltage
network
CM* DM* CM* DM*

L/ N/ L/N L/ N/ L/N

iPF65
TT & TN iPF65 1P 2 1.5 - - 230 340 - -
TT & TN-S iPF65 1P+N 4 - 1.5 1.5 - 260 340
TN-C iPF65 2P 1.5 1.5 - 340 340 -
TN-C iPF65 3P 8 1.5 - - 230/400 340 - -
TT & TN-S iPF65r 3P+N - 1.5 1.5 - 260 340
TT & TN-S iPF65 3P+N - 1.5 1.5 - 260 340
TN-C iPF65r 4P 1.5 1.5 - 340 340 -
iPF40
TT & TN iPF40 1P 2 1.5 - - 230 340 - -
TT & TN-S iPF40 1P+N 4 - 1.5 1.5 - 260 340
TN-C iPF40 2P 1.5 1.5 - 340 340 -
TN-C iPF40 3P 8 1.5 - - 230/400 340 - -
TT & TN-S iPF40r 3P+N - 1.5 1.5 - 260 340
TT & TN-S iPF40 3P+N - 1.5 1.5 - 260 340
TN-C iPF40r 4P 1.5 1.5 - 340 340 -
TN-C iPF40 4P 1.5 1.5 - 340 340 -
iPF20
TT & TN iPF20 1P 2 1.1 - - 230 340 - -
TT & TN-S iPF20 1P+N 4 - 1.5 1.1 - 260 340
TN-C iPF20 2P 1.1 1.1 - 340 340 -
TN-C iPF20 3P 8 1.1 - - 230/400 340 - -
TT & TN-S iPF20 3P+N - 1.5 1.1 - 260 340
TN-C iPF20 4P 1.1 1.1 - 340 340 -
iPF8 (1) Type 2 / Type 3
TT & TN iPF8 1P 2 1 / 1.1 - - 230 340 - -
TT & TN-S iPF8 1P+N 4 - 1.5 / 1.2 1 / 1.1 - 260 340
TN-C iPF8 2P 1 / 1.1 1 / 1.1 - 340 340 -
TN-C iPF8 3P 8 1 / 1.1 - - 230/400 340 - -
TT & TN-S iPF8 3P+N - 1.5 / 1.2 1 / 1.1 - 260 340
TN-C iPF8 4P 1 / 1.1 1 / 1.1 - 340 340 -
* CM: common mode (phase to earth and neutral to earth). * DM: differential mode (phase to neutral). (1) Uoc: combinated waveform voltage: 10 kV.

CA903001E Version : 3.4 11/01/2017 291


Connection
Type Tightening Copper cables
DB123129

torque Rigid Flexible or with ferrule


11 mm

DB122945

DB122946
6.5 mm
PZ2

iPF 3.5 N.m 25 mm2 max. 16 mm2 max.

Technical data
Main characteristics
Operating frequency 50/60 Hz
Operating voltage (Ue) 230/400 V AC
Permanent operating current (Ic) < 1 mA
Response time < 25 ns
End of life indication: Green In operation
by green/red indicator light Red At end of life
End of life remote indication By contact NO, NC 250 V / 0.25 A
Additional characteristics
Operating temperature -25°C to +60°C
Type of connection terminals Tunnel terminals, 2.5 to 35 mm²
Standards IEC 61643-1 T2 and EN 61643-11 Type 2

Weight (g)
Surge arrester
Type iPF
1P 125
2P 210
3P 335
4P 420

Dimensions (mm)
DB123595

1P 1P+N 3P
2P 3P+N
4P

292 Version : 3.4 11/01/2017 CA903001E


CA903011E Version : 1.0 11/01/2017 293
incoming protection (type 2):
DB406142

the iPF K 65 is recommended for a very high risk level (strongly exposed site),
the iPF K 40 is recommended for a high risk level,
the iPF K 20 is recommended for a medium risk level.
PB114703-40

Rated discharge Type of Network


current (Imax) / protection

DB122942

DB407087
Nominal discharge
current (In)

Incoming 1P+N 3P+N 1P 3P


65 kA / 20 kA
Very high risk level iPF K 65 A9L15586
1P
40 kA / 15 kA
High risk level iPF K 40 A9L15686
A9L15687
PB114702-40

A9L15582
A9L15688
20 kA / 5 kA
Medium risk level iPF K 20 A9L15691
A9L15692
A9L15597
A9L15693
PB114701-40

Surge arrester/circuit breaker association


Type of surge arrester Associated circuit breaker
(1 to 4 poles protected)
(Isc 6 kA)
3P iPF K 65 iK60N Curve C 50 A
iPF K 40 iK60N Curve C 40 A
iPF K 20 iK60N Curve C 20 A
PB114700-40

294 Version : 1.0 11/01/2017 CA903011E


Earthing Surge Width Up - (kV) Un - (V) Uc - (V)
system arrester in mod. Voltage protection level Rated Maximum continious operating
name of 9 mm voltage voltage
network
CM* DM* CM* DM*

L/ N/ L/N L/ N/ L/N
iPF K 65
TT & TN-S iPF K 65 3P+N - 1.5 1.5 - 260 340
iPF K 40
TN iPF K 40 1P 2 1.5 - - 230 340 - -
TT & TN-S iPF K 40 1P+N 4 - 1.5 1.5 - 260 340
TN-C iPF K 40 3P 8 1.5 - - 230/400 340 - -
TT & TN-S iPF K 40 3P+N - 1.5 1.5 - 260 340
iPF K 20
TN iPF K 20 1P 2 1.1 - - 230 340 - -
TT & TN-S iPF K 20 1P+N 4 - 1.5 1.1 - 260 340
TN-C iPF K 20 3P 8 1.1 - - 230/400 340 - -
TT & TN-S iPF K 20 3P+N - 1.5 1.1 - 260 340
* CM DM (1) Uoc

Connection
Type Tightening Copper cables
DB123129

torque Rigid Flexible or with ferrule


11 mm
6.5 mm
DB122945

DB122946

PZ2

iPF K 3.5 N.m 25 mm2 max. 16 mm2 max.

CA903011E Version : 1.0 11/01/2017 295


Technical data
Main characteristics
DB123310

Operating frequency 50/60 Hz


Rated voltage network (Un) 230/400 V AC ±10 %
Permanent operating current (Ic) < 5 mA
Response time < 25 ns
Short circuit withstand (ISCCR) 25 kA (50 Hz)
Temporary overvoltage withstand (UT) UT (L-N) 337 V AC / 5 s
LV network UT (L-PE) 442 V AC / 120 min
Temporary overvoltage withstand (UT) UT (N-PE) 1200 V AC / 200 ms
HV network UT (L-PE) 1453 V AC / 200 ms
Ground residual current (IPE) IPE (L-PE) 1P: 5 mA
3P: 25 mA
IPE (N-PE)
Operation indication by mechanical Green In operation
indicator Red At end of life
Additional characteristics
Degree of protection (IEC 60529) Device only IP20 (built-in)
DB123312

Device in IP40
modular
enclosure
Operating temperature -25°C to +60°C
Humidity range 5 % to 95 %
Standards IEC 61643-11: 2011 T2

Weight (g)
IP20 IP40
DB123314

Surge arrester
Type iPF K
1P 125
1P+N 210
3P 335
3P+N 420

Dimensions (mm)
DB123595

1P 3P

296 Version : 1.0 11/01/2017 CA903011E


CA903008E Version : 2.8 11/01/2017 297
DB123854

DB106604

DB406142
incoming protection (type 2):
the iPRD65r is recommended for a very high risk level (strongly exposed site)
the iPRD40(r) is recommended for a high risk level
Country approval pictograms the iPRD20(r) is recommended for a medium risk level
secondary protection (type 2 or 3):
the iPRD8(r) ensures secondary protection of loads to be protected and is placed
in cascade with the incoming surge arresters. This surge arrester is required when
the loads to be protected are at a distance of more than 10 m from the incoming
surge arrester.

The iPRD surge arresters with “r” indication have remote transfer of the information:
“cartridge to be replaced”.

Catalogue number iPRD surge arresters


Rated Nominal Type of Network
discharge discharge protection

DB122942

DB122943
current current
(Imax) (In)
PB110274-35

Incoming Secondary 1P+N 3P+N 1P 2P 3P 4P


iPRD65
65 kA 20 kA iPRD65 A9L65101
Very high risk A9L65121
level (strongly A9L65501
exposed site) A9L65201
A9L65301
A9L65321
2P
A9L65601
A9L65401
iPRD40
40 kA 15 kA iPRD40 A9L40101
High risk level A9L40100
A9L40501
A9L40500
PB110280-35

A9L40201
A9L40200
A9L40301
A9L40321
A9L40300
A9L40601
A9L40600
A9L40401
A9L40421
A9L40400
iPRD20
4P 20 kA 5 kA iPRD20 A9L20100
Medium risk level A9L20501
A9L20500
A9L20200
A9L20300
A9L20321
A9L20601
A9L20600
A9L20400
A9L20421
iPRD8
8 kA 2.5 kA iPRD8 A9L08100
Secondary A9L08501
protection: A9L08500
placed near the A9L08200
loads to be
A9L08300
protected when
they are at a A9L08321
distance of more A9L08601
than 10 m from A9L08600
the incoming A9L08400
surge arrester A9L08421

298 Version : 2.8 11/01/2017 CA903008E


PB110284-35

Spare cartridges iPRD


Type Spare cartridges for Cat. no
iPRD 65-350 iPRD65r A9L65102
iPRD 40-350 iPRD40, iPRD40r A9L40102
iPRD 20-350 iPRD20, iPRD20r A9L20102
iPRD 8-350 iPRD8, iPRD8r A9L08102
iPRD Neutral All products (1P+N, 3P+N) A9L00002

Spare cartridges iPRD IT


Cartridge Type Spare cartridges for Cat. no
C 65-460 iPRD65r IT A9L65122
C 40-460 iPRD40r IT A9L40122
C 20-460 iPRD20r IT A9L20122
C 8-460 iPRD8r IT A9L08122

Earthing Transfer Surge Width Up - (kV) Un - (V) Uc - (V)


system arrester in mod. Voltage protection level Rated Maximum continuous
name of 9 mm voltage operating voltage
network
CM* DM* CM* DM*

L/ N/ L/N L/ N/ L/N
iPRD65
A9L65101 TT & TN iPRD65r 1P 2 1.5 - - 230 350 - -
A9L65121 IT iPRD65r 1P IT 2.3 - - 460 - -
A9L65501 TT & TN-S iPRD65r 1P+N 4 - 1.4 1.5 - 260 350
A9L65201 TN-C-S iPRD65r 2P 1.5 1.5 - 350 350 -
A9L65301 TN-C iPRD65r 3P 6 1.5 - - 230/400 350 - -
A9L65321 IT iPRD65r 3P IT 2.3 - - 460 - -
A9L65601 TT & TN-S iPRD65r 3P+N 8 - 1.4 1.5 - 260 350
A9L65401 TN-C-S iPRD65r 4P 1.5 1.5 - 350 350 -
iPRD40
A9L40101 TT & TN iPRD40r 1P 2 1.6 - - 230 350 - -
A9L40100 TT & TN iPRD40 1P 1.6 - - 350 - -
A9L40501 TT & TN-S iPRD40r 1P+N 4 - 1.4 1.6 - 260 350
A9L40500 TT & TN-S iPRD40 1P+N - 1.4 1.6 - 260 350
A9L40201 TN-C-S iPRD40r 2P 1.6 1.6 - 350 350 -
A9L40200 TN-C-S iPRD40 2P 1.6 1.6 - 350 350 -
A9L40301 TN-C iPRD40r 3P 6 1.6 - - 230/400 350 - -
A9L40321 IT iPRD40r 3P IT 2.2 - - 460 - -
A9L40300 TN-C iPRD40 3P 1.6 - - 350 - -
A9L40601 TT & TN-S iPRD40r 3P+N 8 - 1.4 1.6 - 260 350
A9L40600 TT & TN-S iPRD40 3P+N - 1.4 1.6 - 260 350
A9L40401 TN-C-S iPRD40r 4P 1.6 1.6 - 350 350 -
A9L40421 IT iPRD40r 4P IT 2.2 2.2 - 460 - -
A9L40400 TN-C-S iPRD40 4P 1.6 1.6 - 350 350 -
iPRD20
A9L20100 TT & TN iPRD20 1P 2 1.2 - - 230 350 - -
A9L20501 TT & TN-S iPRD20r 1P+N 4 - 1.4 1.2 - 260 350
A9L20500 TT & TN-S iPRD20 1P+N - 1.4 1.2 - 260 350
A9L20200 TN-C-S iPRD20 2P 1.2 1.2 - 350 350 -
A9L20300 TN-C iPRD20 3P 6 1.2 - - 230/400 350 - -
A9L20321 IT iPRD20r 3P IT 1.8 - - 460 - -
A9L20601 TT & TN-S iPRD20r 3P+N 8 - 1.4 1.2 - 260 350
A9L20600 TT & TN-S iPRD20 3P+N - 1.4 1.2 - 260 350
A9L20400 TN-C-S iPRD20 4P 1.2 1.2 - 350 350 -
A9L20421 IT iPRD20r 4P IT 1.8 1.8 - 460 - -
iPRD8 (1) Type 2 / Type 3 (1)
A9L08100 TT & TN iPRD8 1P 2 1.2 - - 230 350 - -
A9L08501 TT & TN-S iPRD8r 1P+N 4 - 1.4 1.2 - 260 350
A9L08500 TT & TN-S iPRD8 1P+N - 1.4 1.2 - 260 350
A9L08200 TN-C-S iPRD8 2P 1.2 1.2 - 350 350 -
A9L08300 TN-C iPRD8 3P 6 1.2 - - 230/400 350 - -
A9L08321 IT iPRD8r 3P IT 1.6 / 1.8 - - 460 - -
A9L08601 TT & TN-S iPRD8r 3P+N 8 - 1.4 1.2 - 260 350
A9L08600 TT & TN-S iPRD8 3P+N - 1.4 1.2 - 260 350
A9L08400 TN-C-S iPRD8 4P 1.2 1.2 - 350 350 -
A9L08421 IT iPRD8r 4P IT 1.6 / 1.8 1.6 / 1.8 - 460 - -
* CM: common mode (phase to earth and neutral to earth). * DM: differential mode (phase to neutral). (1) Uoc: combinated waveform voltage: 10 kV.

CA903008E Version : 2.8 11/01/2017 299


Connection iPRD surge arresters
Type Tightening torque Copper cables
DB123130

Rigid Flexible or with ferrule


14 mm

DB122945

DB122946
6.5 mm

iPRD 3.5 N.m 2.5 to 25 mm2 4 to 16 mm2

PZ2

Technical data iPRD surge arresters


Main characteristics iPRD iPRD IT
Operating frequency 50/60 Hz
Operating voltage (Ue) 230/400 V AC ±10 %
Permanent operating current (Ic) < 1 mA
Response time < 25 ns
Short circuit current rating (Isccr) 50 kA (50 Hz) -
Short circuit current rating (Isccr), case of double fault - 5 kA (50 Hz)
Temporary overvoltage UT (L-N) 337 V AC / 5 s 337 V AC / 5 s
withstand (UT) UT (L-PE) 442 V AC / 120 min -
Temporary overvoltage UT (N-PE) 1200 V AC / 200 ms 1455 V AC / 200 ms
Safe failure mode (UT) UT (L-PE) 1455 V AC / 200 ms 1455 V AC / 200 ms
Ground residual current (IPE) IPE (L-PE)
IPE (N-PE) -
Satisfactory operation indication: White In operation
by mechanical indicator Red Cartridge must be replaced
Remote indication of satisfactory operation By contact NO, NC 250 V / 0.25 A
Additional characteristics
Degree of protection Device only IP20 (built-in)
(IEC 60529) Device in modular IP40
IP20 IP40
DB123314

enclosure
Operating temperature -25°C to +60°C
Storage temperature -40°C to +85°C
Humidity range 5 % to 95 %
Type of connection terminals Tunnel terminals, 2.5 to 35 mm²
Standards IEC 61643-11: 2011 T2, T3 and
EN 61643-11: 2012 Type 2, Type 3

Surge arrester/circuit breaker association


Surge arrester Associated circuit breaker
iPRD iPRD IT
Isc 25 kA Isc 50 kA Isc (IT 400 V AC) 5 kA

iPRD65 Curve C 50 A Curve C 63 A Curve C 25 A


iPRD40 Curve C 40 A Curve C 63 A Curve C 20 A
iPRD20 Curve C 20 A Curve C 63 A Curve C 10 A
iPRD8 Curve C 10 A Curve C 63 A Curve C 10 A

iPRD dimensions (mm)


DB404819

1P 1P+N, 2P 3P 3P+N, 4P
Weight (g)
Surge arrester
Type iPRD
1P 119
1P+N, 2P 220
3P 340
3P+N, 4P 450

300 Version : 2.8 11/01/2017 CA903008E


iPRD surge arresters
PB110281-60

Terminals
IP20

Satisfactory operation
indication
By mechanical indicator
white: operating
red: cartridge must be replaced

Transfer to
Acti 9 Smartlink

Connection iPRD surge arrester with its short circuit disconnector


TT / TN-S TT / TN-S
Power supply through the top Reversible Power supply through the bottom
Connection with cables The surge arrester base can be turned Connection with comb busbar
over to allow the phase/neutral/earth
PB110289-50

PB110793-50
cables to enter through either the top or
the bottom

Surge arrester iPRD 3P+N + iC60N 3P+N Surge arrester iPRD 3P+N + iC60N 3P+N
PB110287-80

IT/TNC-S with neutral IT/TNC-S with neutral


Power supply through the top Power supply through the bottom
Connection with comb busbar Connection with comb busbar
PB1107290-50

PB110794-50

Surge arrester iPRD 4P + iC60N 4P Surge arrester iPRD 4P + iC60N 4P

CA903008E Version : 2.8 11/01/2017 301


Rated discharge Type of Network
current (Imax) / protection

DB122942

DB122943
Nominal discharge
current (In)

Incoming Secondary 1P+N 3P+N 1P 2P 3P 4P


65 kA / 20 kA
PB105274-35

Very high risk level iPRD65 A9L16555


(strongly exposed site) A9L16556
A9L16557
A9L16442
A9L16558
A9L16443
A9L16559
A9L16659
40 kA / 15 kA
1P+N High risk level iPRD40 A9L16561
A9L16566
A9L16562
A9L16567
A9L16444
A9L16667
PB105275-35

A9L16445
A9L16568
A9L16563
A9L16564
A9L16569
A9L16597
A9L16664
A9L16669
20 kA / 5 kA
Medium risk level iPRD20 A9L16571
3P A9L16672
A9L16572
A9L16446
A9L16447
A9L16573
A9L16674
PB105276-35

A9L16574
A9L16599
A9L16673
8 kA / 2.5 kA
Secondary protection: iPRD8 A9L16576
placed near the loads to be A9L16677
protected when they are at a A9L16577
distance of more than 10 m
from the incoming surge A9L16448
arrester A9L16449
A9L16578
3P+N A9L16679
A9L16579
A9L16678
A9L16680
PB105272-35

Spare cartridges Surge arrester/circuit breaker association


Type Spare cartridges for Cat. no Surge Associated circuit breaker
C 65-460 iPRD65r IT A9L16682 arrester
iPRD iPRD IT
C 65-340 iPRD65r A9L16681
C 40-460 iPRD40r IT A9L16684 Isc 25 kA Isc 50 kA Isc (IT 400 V AC)
C 40-340 iPRD40, iPRD40r A9L16685 5 kA
C 20-460 iPRD20r IT A9L16686 iPRD65 Curve C 50 A Curve C 63 A Curve C 25 A
C 20-340 iPRD20, iPRD20r A9L16687 iPRD40 Curve C 40 A Curve C 63 A Curve C 20 A
C 8-460 iPRD8r IT A9L16688 iPRD20 Curve C 20 A Curve C 63 A Curve C 10 A
C 8-340 iPRD8, iPRD8r A9L16689 iPRD8 Curve C 10 A Curve C 63 A Curve C 10 A
Cartridge
C neutral All products A9L16691

302 Version : 3.3 11/01/2017 CA903002E


Earthing Transfer Surge Width Up - (kV) Un - (V) Uc - (V)
system arrester in mod. Voltage protection level Rated Maximum continuous
name of 9 mm voltage operating voltage
network
CM* DM* CM* DM*

L/ N/ L/N L/ N/ L/N
iPRD65
IT iPRD65r 1P IT 2 2 - - 230 460 - -
TT & TN iPRD65r 1P 1.5 - - 340 - -
TT & TN-S iPRD65r 1P+N 4 - 1.5 1.5 - 260 340
TN-C iPRD65r 2P 1.5 1.5 - 340 340 -
IT iPRD65r 3P IT 6 2 - - 230/400 460 - -
TN-C iPRD65r 3P 1.5 - - 340 - -
TT & TN-S iPRD65r 3P+N 8 - 1.5 1.5 - 260 340
TN-C iPRD65r 4P 1.5 1.5 - 340 340 -
iPRD40
TT & TN iPRD40r 1P 2 1.4 - - 230 340 - -
TT & TN iPRD40 1P 1.4 - - 340 - -
TT & TN-S iPRD40r 1P+N 4 - 1.4 1.4 - 260 340
TT & TN-S iPRD40 1P+N - 1.4 1.4 - 260 340
TN-C iPRD40r 2P 1.4 1.4 - 340 340 -
TN-C iPRD40 2P 1.4 1.4 - 340 340 -
TN-C iPRD40r 3P 6 1.4 - - 230/400 340 - -
TN-C iPRD40 3P 1.4 - - 340 - -
IT iPRD40r 3P IT 2 - - 460 - -
TT & TN-S iPRD40r 3P+N 8 - 1.4 1.4 - 260 340
TT & TN-S iPRD40 3P+N - 1.4 1.4 - 260 340
IT iPRD40r 4P IT 2 2 - 460 460 -
TN-C iPRD40r 4P 1.4 1.4 - 340 340 -
TN-C iPRD40 4P 1.4 1.4 - 340 340 -
iPRD20
TT & TN iPRD20 1P 2 1.1 - - 230 340 - -
TT & TN-S iPRD20r 1P+N 4 - 1.4 1.1 - 260 340
TT & TN-S iPRD20 1P+N - 1.4 1.1 - 260 340
TN-C iPRD20 2P 1.1 1.1 - 340 340 -
TN-C iPRD20 3P 6 1.1 - - 230/400 340 - -
IT iPRD20r 3P IT 1.6 - - 460 - -
TT & TN-S iPRD20r 3P+N 8 - 1.4 1.1 - 260 340
TT & TN-S iPRD20 3P+N - 1.4 1.1 - 260 340
IT iPRD20r 4P IT 1.6 1.6 - 460 460 -
TN-C iPRD20 4P 1.1 1.1 - 340 340 -
iPRD8 (1) Type 2 / Type 3
TT & TN iPRD8 1P 2 1/ 1 - - 230 340 - -
TT & TN-S iPRD8r 1P+N 4 - 1.4 / 1 1 / 1.1 - 260 340
TT & TN-S iPRD8 1P+N - 1.4 / 1 1 / 1.1 - 260 340
TN-C iPRD8 2P 1/ 1 1/ 1 - 340 340 -
TN-C iPRD8 3P 6 1/ 1 - - 230/400 340 - -
IT iPRD8r 3P IT 1.4 / 1.6 - - 460 - -
TT & TN-S iPRD8r 3P+N 8 - 1.4 / 1 1 / 1.1 - 260 340
TT & TN-S iPRD8 3P+N - 1.4 / 1 1 / 1.1 - 260 340
IT iPRD8r 4P IT 1.4 / 1.6 1.4 / 1.6 - 460 460 -
TN-C iPRD8 4P 1/ 1 1/ 1 - 340 340 -
* CM: common mode (phase to earth and neutral to earth). * DM: differential mode (phase to neutral). (1) Uoc: combinated waveform voltage: 10 kV.

CA903002E Version : 3.3 11/01/2017 303


Connection
Type Tightening torque Copper cables
DB123130

Rigid Flexible or with ferrule


14 mm

DB122945

DB122946
6.5 mm
PZ2

iPRD 2 N.m 2.5 to 25 mm2 2.5 to 16 mm2

Technical data
Main characteristics
Operating frequency 50/60 Hz
Operating voltage (Ue) 230/400 V AC
Permanent operating current (Ic) < 1 mA
Response time < 25 ns
End of life indication: by mechanical White In operation
indicator Red At end of life
End of life remote indication By contact NO, NC 250 V / 0.25 A
Additional characteristics
Operating temperature -25°C to +60°C
Type of connection terminals Tunnel terminals, 2.5 to 35 mm²
Standards IEC 61643-1 T2 and EN 61643-11 Type 2

Weight (g)
Surge arrester
Type iPRD
1P 115
2P 220
3P 340
4P 450

Dimensions (mm)
DB123596

1P 1P+N
2P

3P 3P+N
4P

304 Version : 3.3 11/01/2017 CA903002E


EN 61643-11: 2012 Type 2, IEC 61643-11: 2011 T2
They protect electrical and electronic equipment against lightning-induced surges.
Withdrawable surge arrester iQuick PRD surge arresters are prewired, incorporating
their end-of-life disconnector.

incoming protection (type 2):


iQuick PRD40r is recommended for a high risk level
PB106430-29

iQuick PRD20r is recommended for a moderate risk level


secondary protection (type 2 or 3):
iQuick PRD8r provides secondary protection for the loads to be protected and is
cascade-mounted with the incoming surge arresters. This surge arrester is required
as close as possible to the loads to be protected when they are located more than
10 metres away from the incoming surge arrester.

Maximum discharge Type of Network


current (Imax) / protection

DB114409

DB114410
Nominal discharge
current (In)
PB106429-29

Incoming Secondary 1P+N 3P+N 3P


protection protection
40 kA / 20 kA
High risk level iQuick PRD40r A9L16292
A9L16293
A9L16294
20 kA / 5 kA
Moderate risk level iQuick PRD20r A9L16295
A9L16296
A9L16297
8 kA / 2 kA
PB106428-29

Secondary protection: iQuick PRD8r A9L16298


placed near the loads to be A9L16299
protected when they are at a A9L16300
distance of more than 10 m from
the incoming surge arrester
DB123837

Replacement cartridges
Type Replacement cartridges for Cat. no.
C 40-350 iQuick PRD40r A9L16310
C 20-350 iQuick PRD20r A9L16311
C 8-350 iQuick PRD8r A9L16312
C neutral-350 All products A9L16313

Replacement cartridges.

306 Version : 2.5 11/01/2017 CA903003E


Connection
Type Tightening Copper cables
DB123888

torque Rigid Flexible or with ferrule


11 mm
6.5 mm

DB122945

DB122946
PZ2
iQuick PRD Ph / N 8r/20r 2.5 N.m 2.5 to 25 mm2 2.5 to 25 mm2
Ph / N 40r 2.5 to 35 mm2 2.5 to 35 mm2
25 mm2 max. 25 mm2 max.

Earthing Transfert Name of Width in 9 Up – (kV) Un - (V) Uc – (V)


system surge mm Voltage protection level Rated Maximum continious
arrester modules voltage operating voltage
CM* DM* network CM* DM*

N/ L/N N/ L/N

iQuick PRD40r
TT & TN-S 1P+N 8 1.7 2.5 230 264 350
TN-C 3P 13 - 2.5 230/400 - -
TT & TN-S 3P+N 15 1.7 2.5 264 350
iQuick PRD20r
TT & TN-S 1P+N 8 1.7 1.7 230 264 350
TN-C 3P 13 - 1.5 230/400 - -
TT & TN-S 3P+N 15 1.5 1.5 264 350
iQuick PRD8r (2) Type 2 / Type 3
TT & TN-S 1P+N 8 1.7/1,5 1.2/1.4 230 264 350
TN-C 3P 13 - 1.2/1.4 230/400 - -
TT & TN-S 3P+N 15 1.7/1,5 1.2/1.4 264 350

* CM common mode (between neutral and earth). * DM: differential mode (between phase and neutral).
(1) Up (MCB + SPD): total value measured between Modular Circuit Breaker (MCB) terminal block and PE surge arrester device terminal block (SPD).
(2) Uoc: open-circuit voltage in combined wave: 10 kV.

Accessories
DB123842

Earth terminal block support


Type Cat. no.
Support kit L = 4 blocks Batch of 1 PRA90053
DB107889

25 mm2 terminal block kit L = 1 block Batch of 5 PRA90046


DB107884

Pragma: the earth terminal block needs 1 support kit and


1 terminal block kit.

CA903003E Version : 2.5 11/01/2017 307


Technical data
DB123310

Main characteristics
Operating frequency 50/60 Hz
Operating voltage (Ue) 230/400 V AC
Disconnector short-circuit iQuick PRD 8r/20r 25 kA (50 Hz)
withstand (Isc) iQuick PRD 40r 20 kA (50 Hz)
Temporary overvoltage UT (L-N) 415 V AC / 5 s
withstand (UT) UT (N-PE) 1200 V AC / 200 ms
Clip on DIN rail 35 mm. Temporary overvoltage UT (L-N) 440 V AC / 120 min
withstand Safe failure
mode (UT)
Permanent operating current (Ic) < 1 mA
Response time < 25 ns
Status indication By the White Operational
cartridges Red At end of life
By white mechanical indicator/ Operational
DB123312

handle ON
By red mechanical indicator/ At end of life
handle OFF
Remote indication end of life By the NO/NC remote indication contact
250 V AC / 2 A
Additional characteristics
Degree of protection Device only IP20, IK05
Indifferent position of installation. Device in modular IP40
enclosure
Operating temperature -25°C to +60°C
Storage temperature -40°C to +80°C
Humidity range 5 % to 95 %
NF, KEMA KEUR

IP20 IP40
DB123314

Weight (g)
Surge arresters
Type iQuick PRD8r/20r iQuick PRD40r
1P+N 435 445
3P 665 700
3P+N 810 850

Dimensions (mm)
DB123595

1P+N 3P 3P+N

308 Version : 2.5 11/01/2017 CA903003E


EN 61643-11: 2012 Type 2, IEC 61643-11: 2011 T2
DB106604

Protects electrical and electronic equipment against indirect overvoltage due to the
lighting effect.
Coordination with selective version "SI " and types.

The iQuick PF is precabled. It incorporates its end of life safety disconnector and an
earthing terminal block.

Accessories supplied
Terminal and 16 mm² cable for connection to the earth bar of the enclosure
PB107103-35

PB107104-35

(supplied mounted).
1 lug to crimp for 16 mm² earthing cable.
iQuick PF 1P+N: 2 connection accessories for the electrical link between the
surge arrester and the incoming residual current circuit breaker:
1 mounted, centre distance between axes: 9 mm,
1 supplied, centre distance between axes: 18 mm.

Maximum discharge Network Earthing Width in 9 Up – (kV) Un - (V) Uc – (V)


current (Imax) / system mm modules Voltage Rated Maximum
Nominal discharge protection voltage continius
current (In) level (*) network operating
DB123843

voltage

1P+N 3P+N
10 kA / 5 kA
iQuick PF A9L16617 TT & TN-S 4 1.5 230 275
A9L16618 TT & TN-S 10 1.5 230/400 275

Remote auxiliary
PB107105-40

IEC 60947-5-1
The remote auxiliary iSR allows to remote the iQuick PF operating status.

Auxiliary
Type Width in mod.
of 9 mm
iSR Contact Voltage (Ue)
3A 415 V CA A9L16619 1
DB122821

Connection
Type Tightening Copper cables
DB123387

torque Rigid Flexible or with ferrule


13 mm
DB122945

DB122946

6.5 mm

iQuick PF Ph / N 2 N.m 1 to 16 mm2 1 to 16 mm2


10 to 25 mm2 10 to 25 mm2
iSR 1.2 N.m 16 mm2 max. 16 mm2 max.
PZ2

CA903004E Version : 2.3 11/01/2017 309


Technical data
DB123310

Main characteristics
Operating frequency 50 Hz
Operating voltage (Ue) 230/400 V AC
Integrated breaking capacity (Isc at 50 Hz) 6 kA
Temporary overvoltage withstand (UT) UT (L-N) 337 V AC / 5 s
UT (L-PE) 442 V AC / 5 s
Temporary overvoltage withstand Safe UT (N-PE) 1200 V AC / 200 ms
failure mode (UT)
Ground residual current (IPE) IPE (N-PE)
Status indication: Mechanical indicator white/ Operational
handle ON
Mechanical indicator red/ At end of life
handle OFF
Remote indication end of life By iSR auxiliary
Additional characteristics
DB123312

Degree of protection Device only IP20


Device in modular enclosure IP40
Operating temperature -25°C to +70°C
Storage temperature -40°C to +80°C
Humidity range 5 % to 95 %

IP20 IP40
DB123314

Weight (g)
Surge arresters
Type iQuick PF
1P+N 370
3P+N 640

Dimensions (mm)
DB123848

DB123849

DB123850

310 Version : 2.3 11/01/2017 CA903004E


Analogue telephone line protection: the iPRC surge arrester wired in series to the
private installation input protects the telephones, the PABX, the modems
(including ADSL), etc.

Protection for 2 low-current lines without common potential or 4 lines with


common reference potential: the iPRI protects the measuring instrument and PLC
"sensor" inputs and the DC power supply inputs up to 53 V and AC power supply
Protection against overvoltages related to inputs up to 37 V.
lightning strikes. The input current must not exceed 300 mA.
PB104269-35

PB104270-35

DB122585

DB126523
A9L16337 A9L16339
DB122624

Line L1 Cables 7-8 Line L1 Cables 5-6


Line L2 Cables 11-12 Line L2 Cables 11-12
– – Line L’1 Cables 1-2
– – Line L’2 Cables 7-8
Cable 3 Cables 3-4-9-10
IN Ligne side IN Ligne side

Catalogue numbers OUT Protected side OUT Protected side

Surge arresters iPRC iPRI


Mains voltage (Un) <130 V AC 48 V DC
Analogue telephone system –
Telephone transmitter –
Digital telephone system –
Automation network –
VLV load power supply (12…48 V) –
xDSL compatibility –
Cat. no.. A9L16337 A9L16339
Width in 9 mm modules 2 2

Diagrams
DB122600

Position
switches

Analog
sensors

CA903006E Version : 2.1 11/01/2017 311


Connection
Tightening Copper cables

DB122584
torque Rigid Flexible or with
8 mm ferrule
3 mm

DB122945

DB122946
PZ1 0.8 N.m 0.2 to 4 mm2 0.2 to 2,5 mm2
DB123309

Technical data
Main characteristics
iPRC iPRI
Number of protected lines 2 2
Test category IEC/EN C1, C2, C3, D1, B2 C1, C2, C3, D1, B2
Maximum continuous voltage (Uc) 180 V DC, 130 V AC 53 V DC, 37 V AC
Limitation voltage (Up) 300 V 70 V
Rated discharge current (8/20) (In) 10 kA 10 kA
DB123300

Maximum discharge current (8/20) (Imax) 18 kA 10 kA


Response time < 500 ns 1 ns
Nominal impulse current 100 A 70 A
Rated current (IN) 450 mA (up to 45°C) 300 mA (up to 45°C)
Series resistor
End-of-life information by Loss of dialling tone Loss of transmission
Additional characteristics
Degree of protection Device only IP20 IP20
Device in modular IP40 IP40
IP20 IP40
DB123311

enclosure
IK 05 05
IK05 IK05
Operating temperature -25°C to +60°C -25°C to +60°C
Storage temperature -40°C to +85°C -40°C to +85°C

Weight (g)
Surge arresters
Type iPRC iPRI
25 65

Dimensions (mm)
DB122585

312 Version : 2.1 11/01/2017 CA903006E


IEC 61643-1 T2
EN 61643-11 Type 2
UTE C 61740-51 T2
prEN 50539-11 T2
PB107585-40

iPRD-DC direct current surge arresters are designed to protect against overvoltages
due to a lightning strike: of the "DC" input to the inverter and of photovoltaic panels.

It should be installed in a switchboard inside the building. If the switchboard is


located outside, it must be weatherproof.

Withdrawable iPRD-DC surge arresters allow damaged cartridges to be replaced


quickly.
They offer remote reporting of the "cartridge must be changed" message.

Catalogue numbers
Internal diagram Imax (kA) In (kA) Up (kV) UCPV (V) (1) Width in Cat. no.
Maximum Nominal Protection level Maximum steady state module of
discharge discharge voltage 9 mm
current current
L+/ L-/ L+/L- L+/ L-/ L+/L-
iPRD-DC40r 600PV
40 15 1.6 1.6 2.8 600 600 840 6 A9L16434
DB124051

iPRD-DC40r 1000PV
40 15 3.9 3.9 3.9 1000 1000 1000 6 A9L16436
DB124052

Replacement cartridges
PB107586-30

PB107587-30

Type Replacement cartridges for Cat. no.


C 40-600PV iPRD-DC40r 600PV A9L16683
C 40-1000PV iPRD-DC40r 1000PV A9L16692
C neutral PV iPRD-DC40r 600PV A9L16690

CA903007E Version : 2.2 11/01/2017 313


Connection
Type Tightening torque Copper cables
DB124057

Rigid Flexible or with ferrule


14 mm

DB122945

DB122946
6.5 mm
PZ2

iPRD-DC 2 N.m 2.5 to 25 mm2 2.5 to 16 mm2

Depending on the distance between the "generator" part and the "conversion" part, it
may be necessary to install two surge arresters or more, to ensure protection of each
of the two parts.
Generator
DB124049

Generator
Conversion

Conversion

314 Version : 2.2 11/01/2017 CA903007E


Technical data
DB123310

Main characteristics
Type of network Isolated direct current
Temps de réponse < 25 ns
Short circuit current (ISCPV) 30 A
Type of surge arresters Type 2
End-of-life indication mode Circuit opened by integrated thermal
disconnector
Additional characteristics
DB123312

Degree of protection Device only IP20


(IEC 60529) Device in modular IP40
enclosure
Chocs IK03
End-of-life indication By the cartridges White Operational
Red At end of life
By the NO/NC remote indication contact 250 V AC / 0.25 A
Operating temperature -25°C to +60°C
Storage temperature -40°C to +85°C
Tropicalization (IEC 60068-1) Treatment 2 (relative humidity
of 95 % at 55°C)
IP20 IP40
DB123314

Weight (g)
Surge arresters
Type
iPRD-DC40r 600PV 400
iPRD-DC40r 1000PV 400

Dimensions (mm)
DB124050

CA903007E Version : 2.2 11/01/2017 315


UTE C 61740-51 T2
DB123854

EN 50539-11: 2013 T2
PB110283-40

iPRD PV-DC direct current surge arresters are designed to protect against
overvoltages due to a lightning strike: of the "DC" input to the inverter and of
photovoltaic panels.

It should be installed in a switchboard inside the building. If the switchboard is


located outside, it must be weatherproof.

Withdrawable iPRD PV-DC surge arresters allow damaged cartridges to be replaced


quickly.
The surge arrester base can be turned over to allow the phase/neutral/earth cables
to enter through either the top or the bottom
They offer remote reporting of the "cartridge must be changed" message.

Catalogue numbers
Internal diagram I Total (kA) In (kA) Up (kV) UCPV (V) (1) Width in Cat. no.
Total Nominal Protection level Maximum continuous module of
discharge discharge operating voltage 9 mm
current current L+/ , L-/ , L+/L- L+/ , L-/ , L+/L-
iPRD 40r 800PV
40 15 3 800 6 A9L40271
DB124052

iPRD 40r 1000PV


40 15 3.9 1000 6 A9L40281
DB124052

Replacement cartridges
PB110285-30

Type Replacement cartridges for Cat. no.


C 40-800PV iPRD 40r 800PV A9L40172
C 40-1000PV iPRD 40r 1000PV A9L40182

316 Version : 2.1 11/01/2017 CA903009E


Connection
Type Tightening torque Copper cables
DB124057

Rigid Flexible or with ferrule


14 mm

DB122945

DB122946
6.5 mm
PZ2

iPRD PV-DC 3.5 N.m 2.5 to 25 mm2 2.5 to 16 mm2

Depending on the distance between the "generator" part and the "conversion" part, it
may be necessary to install two surge arresters or more, to ensure protection of each
of the two parts.
Generator
DB124049

Generator
Conversion

Conversion

CA903009E Version : 2.1 11/01/2017 317


Application diagram

String PV protection enclosure


DB406863

Photovoltaic string modules

Diagram with C120NA-DC for


current 100 A

PV Inverter protection
enclosure PV Inverter

*C120NA-DC:
100 A/1000 V DC
MN, MX, MNx, MN , MX+OF,
OF, SD, OF+SD/OF, OF+SD24

318 Version : 2.1 11/01/2017 CA903009E


DB123310

Technical data
Main characteristics
Type of network Isolated direct current
Maximum continuous iPRD 40r 800PV 800 V
operating voltage (UCPV) iPRD 40r 1000PV 1000 V
Response time < 25 ns
Permanent operating current (Ic) < 1 mA
Short circuit current (ISCPV) 200 A
Type of surge arresters Type 2
DB123312

Ground residual current IPE (AC)


IPE (DC)
End-of-life indication mode Circuit opened by integrated thermal
disconnector
Additional characteristics
Degree of protection Device only IP20
(IEC 60529) Device in modular IP40
enclosure
Chocs IK03
Satisfactory operation By the cartridges White Operational
IP20 IP40
DB123314

indication Red Cartridge must be replaced


By the NO/NC remote indication contact 250 V AC / 0.25 A
Operating temperature -25°C to +60°C
Storage temperature -40°C to +85°C
Humidity range 5 % to 95 %
Standards UTE C 61740-51 T2
EN 50539-11: 2013 T2

Weight (g)
Surge arresters
Type
iPRD 40r 800PV 400
iPRD 40r 1000PV 400

Dimensions (mm)
DB124050

CA903009E Version : 2.1 11/01/2017 319