SECTION-1
1.1 SCOPE
1.2 STANDARDS
1.2.1 Unless otherwise specified, the cable shall confirm in all respect
to IS:7098 (Part2)-1985,latest amendments till date.
1.3.1 The climatic conditions under which are cables shall operate
satisfactory are as follows:
pg. 3
1.4 PRINCIPAL PARAMETERS:
• Cores (Nos) : 3
• System Frequency HZ : 50
pg. 4
• 1.2/50 Microsecond lighting impulse withstand voltage wave value
kVp : 75
1.5.1 CONDUCTOR
pg. 5
1.5.3 INSULATION:
The sheath shall be suitable to withstand the site conditions and the
desired temperature. It shall be of adequate thickness, consistent
quality and free from defects. The PVC sheath shall be extruded. The
material of fillers and inner-sheath shall be compatible with the
temperature ratings of the cable and shall have no detritus effect on
any other component of the cable. Central PVC filler shall also, be
provided with other peripheral PVC fillers to have proper circular
shape. The cable shall have suitable round PVC filers laid up with
insulation cores to have subsequent circular cross section.
PVC Inner Sheath thickness should be less than 1.0 mm.
pg. 6
1.5.6 ARMOUR:
1.5.8 CONSTRUCTION:
pg. 7
1.5.9 CURRENT RATING:
1.5.10 OPERATION:
1.5.11 LENGTH:
pg. 8
• Name of manufacturer/year of manufacture/voltage grade/cable
code/size (300 sq. mm-3 core) /name of purchaser.
• Sequential cable length after each meter of cable just
diametrically opposite side of the above.
1.6 TEST:
All cables sizes i.e. items offered should have been fully type tested as
per the relevant standards at any Govt. recognized Laboratory .The
bidder shall furnish three sets of type test reports along with the offer.
The type test reports shall not be older than FIVE years and shall be
valid up to the expire of validity of offer. For any changes in
design/type offered against this specification, the purchaser reserves
the right to demand repetition of type test without any extra cost.
The purchaser also reserve the right to have tests carried out at his
own cost by an independent agency, whenever there is a dispute
regarding the quality of supply.
1.6.2 The following type test reports shall be furnished with the offer:
a. Test on conductor:
• Tensile test.
• Resistance test.
• Wrapping test (to be done before stranding )
b. Test for armouring wires:
• Dimensions test.
• Physical tests :
Tensile strength
Elongation at break
Torsion test(for round wires only)
Winding test for formed wires
Uniformity of zinc coating
Mass of zinc coating
Resistivity
pg. 9
c. Test for thickness of insulation and sheath:
g. Bending test
pg. 10
1.6.3 Acceptance Test:
The selection of samples pieces for acceptance test shall be from 10%
drums of each lot offered for inspection or part thereof. The minimum
shall be one drum. The purchaser reserves the right to conduct
acceptance test on more no of sample if he so desires.
pg. 11
1.6.4 All the acceptance test shall be carried out by the bidder, in the
presence of purchaser’s representative at their works. The bidder shall
give at least 15 days advance notice to the purchaser to enable him to
depute the engineer for witnessing the tests. The test certificate for
acceptance tests witnessed by inspecting officer / engineer shall be
submitted for approval before dispatch of material.
1.6.5 The bidder shall have to submit, well in advance the test certificates
for the following Routine Test for approval prior to inspection of the
materials for the complete lot offered for inspection at a time.
• Conductor resistance test as per IS : 7098 Part-2 (1985)
• Partial discharge test as per IS : 7098 Part-2 (1985)
• High voltage test for 5 min (as per IEC-60502 cl.16.4.4)
The supplier shall keep the purchaser informed in advance about the
program of manufacturing of cables so that arrangement can be made
for inspection.
The purchaser reserves the right to insist for witnessing the acceptance
/ routine tests of the bought out items.
pg. 12
1.8 SAMPLING OF CABLES:
Samples shall be taken and tested from each lot for ascertaining the
conformity of the lot to the requirements of the specification. The
sampling will be done complying to the conditions as stipulated in
Appendix A (Cl. 18.2.1) of IS:7098 (Part 2)- 1985.
1.9 DOCUMENTATION:
The bidder shall furnish following documents along with his offer.
pg. 13
1.10 PACKING AND FORWARDING:
pg. 14
• Over and above, name plate of aluminum of suitable size
and thickness, containing all the above information, shall be
fixed on the drum in addition to the painting.
• The bidder shall be responsible for any damage to the cables
during transit due to improper and inadequate packing.
Where ever necessary, proper arrangement of lifting hooks
shall be provided. Any cable found short inside the packing
cases shall be supplied by the supplier, without any extra
cost.
• Name of consignee.
• Details of consignment.
• Destination.
• Total weight of consignment.
• Handling and unpacking instruction.
• Bill of materials, including contents of each package.
pg. 15
Annexure-I
GUARANTEED TECHNICAL PARTICULARS
FOR 3 CORE 11 KV XLPE CABLE
1. Name of Manufacturer :
2. Country of Manufacture :
3. Type of Cable :
8. Conductor
(a) Material :
(b) Grade :
(c) Nominal Cross-Sectional Area : Sq. mm
(d) No. of Wires and Diameter of each : No / mm
Wire (before stranding)
(e) Shape :
(f) Diameter over Conductor : mm
9. Conductor Screen
(a) Material :
(b) Thickness : mm
(c) Diameter over Conductor Screen : mm
pg. 16
10. Insulation
(a) Material :
(b) Nominal Thickness : mm
(c) Minimum Thickness : mm
(d) Diameter over insulation : mm
(e) Designed Maximum Stress : kV/mm
(f) Method of curing : Dry
(a) Material :
(b) Thickness :
(c) Width :
(d) Area : 2.5mm²(minimum)
pg. 17
15. Armour Wire
(a) Material : GI Steel Round Wire
(b) No. of Wire and Diameter of each :
wire
(c) Diameter over armour : mm
(c) Embossing
(i) At every 3 Mts. length : CESC Ltd., Manufacturer’s Name, Type
of Cable, Year of Manufacture.
(ii) At every 1 Mt. length : Sequential marking of length
pg. 18
21. Minimum Bending Radius for Cable : m
during installation
(a) In Ground : A
(b) In Air : A
(c) In Pipe/ Ducts : A
pg. 19
27. Details of Drum
(a) Material and Weight of Drum : Kg.
(b) Weight of Drum with Cable : Kg.
(c) Flange Diameter of Drum : m
(d) Barrel Width of Drum : m
(e) Spindle Hole Diameter : Mm
NOTE :
1. The Short Circuit Rating of Metallic Tape & Armour Wires (combined) of 3-Core 11 kV
XLPE Cable should be 24 kA for 01 second.
pg. 20