Transfer Tank (Ground Tank) Size at Tower (A+B)
Transfer Tank (Ground Tank) Size at Tower (A+B)
Tank size = (Storage water volume / full fill capacity) * 1/2 = 64000 L
64 m3
If Tank high = 4m,
Area= volume/high = 16 m2
Domestic Tank (Roof Tank) size at Tower A ,
So,
Effective Volume of Pressure Vessel = ( Pump Running Time x Mean Flow Rate ) / (Pump start / stop time)
= 427.5 L
Total Volume of PressureVessel Size = Effective Volume / Accepatance Factor
= 1496.25 L
= 1.5 m3
L/s
L/s
L/s
L/s
L/min
Q = AV
A= 0.001216 m2
d= 0.0393 m
d= 39 mm
Choose(Pipe Size) d = 40 mm
For Booster Pump (Down Feed) ,
Q = AV
A= 0.00128 m2
d= 0.0404 m
d= 40.4 mm
Choose(Pipe Size) d = 40 mm
For Tower A (Booster Pipe ),
Distribution Pipe Size ( 8th floor) ,
TLU = 8th floor TLU + 7th floor TLU + 6th floor TLU + 5th floor TLU + 4th floor TLU
TLU = 655
From Loading Unit Chart ( flow Rate ) = 4.8 L/s
= 0.0048 m3/s
Q= 0.0048 m3/s
V= 1.25 m/s
A= 0.00384 m2
d= 0.0699 m
d= 70 mm
Chose pipe size, d = 80 mm
TLU = 7th floor TLU + 6th floor TLU + 5th floor TLU + 4th floor TLU
TLU = 524
From Loading Unit Chart ( flow Rate ) = 4.2 L/s
= 0.0042 m3/s
Q= 0.0042 m3/s
V= 1.25 m/s
A= 0.00336 m2
d= 0.0654 m
d= 65.4 mm
Chose pipe size, d = 65 mm
TLU = 6th floor TLU + 5th floor TLU + 4th floor TLU
TLU = 393
From Loading Unit Chart ( flow Rate ) = 3.2 L/s
= 0.0032 m3/s
Q= 0.0032 m3/s
V= 1.25 m/s
A= 0.00256 m2
d= 0.0571 m
d= 57.1 mm
Chose pipe size, d = 65 mm
TLU = 3rd floor TLU + 2nd floor TLU + 1st floor TLU
TLU = 393
From Loading Unit Chart ( flow Rate ) = 3.2 L/s
= 0.0032 m3/s
Q= 0.0032 m3/s
V= 1.25 m/s
A= 0.00256 m2
d= 0.0571 m
d= 57.1 mm
Chose pipe size, d = 65 mm
TLU + 4th floor TLU TLU = 8th floor TLU + 7th floor TLU + 6th floor TLU + 5th fl
TLU = 585
From Loading Unit Chart ( flow Rate ) = 4.5 L/s
= 0.0045 m3/s
Q= 0.0045 m3/s
V= 1.25 m/s
A= 0.0036 m2
d= 0.0677 m
d= 67.7 mm
Chose pipe size, d = 65 mm
TLU = 7th floor TLU + 6th floor TLU + 5th floor TLU + 4th fl
TLU = 468
From Loading Unit Chart ( flow Rate ) = 3.8 L/s
= 0.0038 m3/s
Q= 0.0038 m3/s
V= 1.25 m/s
A = 0.00304 m2
d= 0.0622 m
d= 62.2 mm
Chose pipe size, d = 65 mm
TLU = 6th floor TLU + 5th floor TLU + 4th floor TLU
TLU = 351
From Loading Unit Chart ( flow Rate ) = 2.8 L/s
= 0.0028 m3/s
Q= 0.0028 m3/s
V= 1.25 m/s
A = 0.00224 m2
d= 0.0552 m
d= 55.2 mm
Chose pipe size, d = 65 mm
TLU = 3rd floor TLU + 2nd floor TLU + 1st floor TLU
TLU = 351
From Loading Unit Chart ( flow Rate ) = 2.8 L/s
= 0.0028 m3/s
Q= 0.0028 m3/s
V= 1.25 m/s
A = 0.00224 m2
d= 0.0552 m
d= 55.2 mm
Chose pipe size, d = 65 mm
Pump Flow Rate = Storage Water Volume / Running hour = 4.31 L/s
= 0.00431 m3/s
m
m
m
m
oss ) + (Number of valve x loss)
m
m
m
m
m
m
m
m
m