100% found this document useful (1 vote)
215 views

Construction Issue: Qty. (Nos) AI DI AO DO Hvac System I Water Chilling Units 3

This document provides a list of construction issues related to an HVAC system with details on field devices, BMS provider responsibilities, and service provider responsibilities. It includes 20 items total for the water chilling units and HVAC system, with 9 digital inputs, 3 analog outputs, and 11 digital outputs required. Item responsibilities include things like relay outputs, potential free contacts, temperature sensors, flow meters, and motorized butterfly valves for chilled/condenser water.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
215 views

Construction Issue: Qty. (Nos) AI DI AO DO Hvac System I Water Chilling Units 3

This document provides a list of construction issues related to an HVAC system with details on field devices, BMS provider responsibilities, and service provider responsibilities. It includes 20 items total for the water chilling units and HVAC system, with 9 digital inputs, 3 analog outputs, and 11 digital outputs required. Item responsibilities include things like relay outputs, potential free contacts, temperature sensors, flow meters, and motorized butterfly valves for chilled/condenser water.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 11

Construction Issue

S.No Description Qty.(Nos) Condition of service Field Device By BMS provider By respective service providers
AI DI AO DO
HVAC SYSTEM
I Water Chilling Units 3
Relay output @ 2 amp, 230 V & wiring
Potential free contact in auto mode in the
1 Chiller On/Off -- 3 Chiller Panel & termination from DDC Controler to
control circuit of Chiller MCC Panel
potential free contact of Chiller MCC
Auxillary Potential Free Contact provision in
2 Chiller Run Status -- 3 Chiller Panel Wiring & termination from chiller panel
chiller panel for acquiring the signal
Auxillary Potential Free Contact provision in
3 Chiller Trip Fault -- 3 Chiller Panel Wiring & termination from chiller panel chiller panel for acquiring the signal
Analog output to chiller panel and wiring Provision in chiller panel for accepting 0-10
4 Chiller Water Temp. Setpoint -- 3 Chiller Panel
from chiller panel V analog input for setpoint definition
Providing of suitably sized socket in the
5 Chiller Water Temperature In(1) + Out (1) -- 6 Immersion type temp. sensor Immersion temp sensor & field wiring
chilled / hot water supply line
Potential free contact in auto mode in the
6 Chiller Current Monitoring -- 3 Chiller panel Wiring & termination from chiller panel
control circuit of Chiller MCC Panel
7 Ambient Temperature -- 1 Temp. sensor Outside Air Temp Sensor & wiring -
8 Ambient RH -- 1 Humidity sensor Humidity Sensor & field wiring -
Providing of suitably sized socket in the
9 CHW flow rate -- 2 ultrasonic type flow meter Flow meter & field wiring
chilled / hot water supply line
Condenser water Temp. In / Out In (1) + Immersion temperature sensor with Providing of suitably sized socket in the
10 -- 6 Immersion type temp. sensor
Out (1) thermowell & wiring chilled / condenser water supply line
Immersion temperature sensor with Providing of suitably sized socket in the
11 1 Immersion type temp. sensor
Common CHW header Supply Temp thermowell & wiring chilled / condenser water supply line
Immersion temperature sensor with Providing of suitably sized socket in the
12 1 Immersion type temp. sensor
Condensor water header supply temp. thermowell & wiring chilled / condenser water supply line
Immersion temperature sensor with Providing of suitably sized socket in the
13 1 Immersion type temp. sensor
Common CHW header Return Temp thermowell & wiring chilled / condenser water supply line
Immersion temperature sensor with Providing of suitably sized socket in the
14 1 Immersion type temp. sensor
Condensor water header Return temp. thermowell & wiring chilled / condenser water supply line
Motorized Butterfly SITC of motorised Butterfly valves including
Output signal from the DDC Controller
8 CHW/CDW Valve by HVAC necessary nipples / mating flanges in the
& wiring to valve actuator
15 CHW/CDW Valve on/off Contractor pipeline
Sub Total : 20 9 3 11
II Bypass Line
Providing of suitably sized socket in the
1 CHW flow rate -- 1 ultrasonic type flow meter Flow meter & field wiring chilled / hot water supply line
SITC of motorised Butterfly valves including
Motorized Butterfly CHW Output signal from the DDC Controller
2 CHW/CDW Valve on/off 1 necessary nipples / mating flanges in the
Valve by HVAC Contractor & wiring to valve actuator
pipeline
Sub Total : 1 0 0 1

INTERCONTINENTAL DHAKA Page 1 of 11 1/15/2015


S.No Description Qty.(Nos) Condition of service Field Device By BMS provider By respective service providers
AI DI AO DO
III Heat Pumps Units 2
Relay output @ 2 amp, 230 V & wiring
Potential free contact in auto mode in the
1 Heat Pump On/Off -- 2 Chiller Panel & termination from DDC Controler to
control circuit of Chiller MCC Panel
potential free contact of Chiller MCC
Auxillary Potential Free Contact provision in
2 Heat Pump Run Status -- 2 Chiller Panel Wiring & termination from chiller panel
chiller panel for acquiring the signal
Auxillary Potential Free Contact provision in
3 Heat Pump Trip Fault -- 2 Chiller Panel Wiring & termination from chiller panel
chiller panel for acquiring the signal
Analog output to chiller panel and wiring Provision in chiller panel for accepting 0-10
4 Chiller Water Temp. Setpoint -- 2 Chiller Panel
from chiller panel V analog input for setpoint definition
Providing of suitably sized socket in the
5 Chiller Water Temperature In(1) + Out (1) -- 4 Immersion type temp. sensor Immersion temp sensor & field wiring
chilled / hot water supply line
Potential free contact in auto mode in the
6 Chiller Current Monitoring -- 2 Chiller panel Wiring & termination from chiller panel
control circuit of Chiller MCC Panel
Providing of suitably sized socket in the
7 CHW flow rate -- 2 ultrasonic type flow meter Flow meterr & field wiring
chilled / hot water supply line
Immersion temperature sensor with Providing of suitably sized socket in the
8 Hot water Temp. In / Out In (1) + Out (1) -- 2 Immersion type temp. sensor
thermowell & wiring chilled / condenser water supply line
Immersion temperature sensor with Providing of suitably sized socket in the
9 1 Immersion type temp. sensor
Common CHW header Supply Temp thermowell & wiring chilled / condenser water supply line
Immersion temperature sensor with Providing of suitably sized socket in the
10 1 Immersion type temp. sensor
Hot water header supply temp. thermowell & wiring chilled / condenser water supply line
Immersion temperature sensor with Providing of suitably sized socket in the
11 1 Immersion type temp. sensor
Common CHW header Return Temp thermowell & wiring chilled / condenser water supply line
Immersion temperature sensor with Providing of suitably sized socket in the
12 1 Immersion type temp. sensor
Hot water header Return temp. thermowell & wiring chilled / condenser water supply line
Sub Total : 12 6 2 2
IV Chilled Water Pumps
1 Chilled Water Pumps 3
Relay output @ 2 amp, 230 V & wiring
Potential free contact in auto mode in the
1.1 Chilled Water Pump ON/OFF -- 3 Pump panel & termination from DDC Controler to
control circuit of Pump MCC Panel
potential free contact of Pump MCC
Auxillary Potential Free Contact provision in
1.2 Chilled Water Pump Run Status -- 3 Pump panel Wiring & termination from Pump panel Pump panel for acquiring the signal
Auxillary Potential Free Contact provision in
1.3 Chilled Water Pump A/M Status -- 3 Pump panel Wiring & termination from Pump panel Pump panel for acquiring the signal
1.4 Variable speed monitoring 3 VFD Panel Wiring to VFD Provision of termination in VFD panel.
1.5 Fault Alarm 3 VFD Panel Wiring to VFD Provision of termination in VFD panel.
S.No Description Qty.(Nos) Condition of service Field Device By BMS provider By respective service providers
AI DI AO DO
2 Condenser Pumps 3
Relay output @ 2 amp, 230 V & wiring
Potential free contact in auto mode in the
2.1 Condenser Pump ON/OFF -- 3 Pump panel & termination from DDC Controler to
control circuit of Pump MCC Panel
potential free contact of Pump MCC

Auxillary Potential Free Contact provision in


2.2 Condenser Pump Run Status -- 3 Pump panel Wiring & termination from Pump panel
Pump panel for acquiring the signal

Auxillary Potential Free Contact provision in


2.3 Condenser Pump A/M Status -- 3 Pump panel Wiring & termination from Pump panel
Pump panel for acquiring the signal
2.4 Fault Alarm 3 VFD Panel Wiring to VFD Provision of termination in VFD panel.
Sub Total : 3 18 0 6
V Chilled Water Pumps (Heat Pumps)
1 Chilled Water Pumps (Heat Pumps) 2
Relay output @ 2 amp, 230 V & wiring
Potential free contact in auto mode in the
1.1 Chilled Water Pump ON/OFF -- 2 Pump panel & termination from DDC Controler to
control circuit of Pump MCC Panel
potential free contact of Pump MCC
Auxillary Potential Free Contact provision in
1.2 Chilled Water Pump Run Status -- 2 Pump panel Wiring & termination from Pump panel Pump panel for acquiring the signal
Auxillary Potential Free Contact provision in
1.3 Chilled Water Pump A/M Status -- 2 Pump panel Wiring & termination from Pump panel Pump panel for acquiring the signal
1.4 Fault Alarm 2 VFD Panel Wiring to VFD Provision of termination in VFD panel.
2 Hot water Pumps (Heat Pumps) 2
Relay output @ 2 amp, 230 V & wiring
Potential free contact in auto mode in the
2.1 Hot water Pump ON/OFF -- 2 Pump panel & termination from DDC Controler to
control circuit of Pump MCC Panel
potential free contact of Pump MCC

Auxillary Potential Free Contact provision in


2.2 Hot water Pump Run Status -- 2 Pump panel Wiring & termination from Pump panel
Pump panel for acquiring the signal

Auxillary Potential Free Contact provision in


2.3 Hot water Pump A/M Status -- 2 Pump panel Wiring & termination from Pump panel
Pump panel for acquiring the signal
2.4 Fault Alarm 2 VFD Panel Wiring to VFD Provision of termination in VFD panel.
Sub Total : 0 12 0 4
S.No Description Qty.(Nos) Condition of service Field Device By BMS provider By respective service providers
AI DI AO DO
VI Cooling Towers (Chilled water / D.G) 4
Relay output @ 2 amp, 230 V & wiring
& termination from DDC Controler to Potential free contact in auto mode in the
1 Cooling Tower Fan ON/OFF -- 6 Cooling tower panel
potential free contact of Coling Tower control circuit of Cooling Tower MCC Panel
MCC
Auxillary Potential Free Contact provision in
2 Cooling Tower Fan Run Status -- 6 Cooling tower panel Wiring & termination from CT panel Pump panel for acquiring the signal
Auxillary Potential Free Contact provision in
3 Cooling Tower Fan A/M Status -- 6 Cooling tower panel Wiring & termination from CT panel Pump panel for acquiring the signal
Supply & installation of level switch in the
4 Cooling Tower Sump Low Water -- 4 Level Switch Wiring from level switch CT tank.
Sub Total : 0 16 0 6
Air Handling Units
VII 48
(AHU/CSU/HSU/TFA)
Relay output @ 2 amp, 230 V & wiring
Potential free contact in auto mode in the
1.0 AHU Fan On/Off -- 48 AHU panel & termination from DDC Controler to
control circuit of AHU MCC Panel
potential free contact of AHU MCC
Auxillary Potential Free Contact provision in
2.0 AHU Run Status -- 48 AHU panel Wiring & termination from AHU panel AHU panel for acquiring the signal
Auxillary Potential Free Contact provision in
3.0 Trip Status -- 48 AHU panel Wiring & termination from AHU panel AHU panel for acquiring the signal
DP Switch(Filter) by BMS Provision for Installation of DP switch
4.0 AHU Filter Status -- 48 Wiring from DP Switch
Contractor across filter
Temperature Sensor by BMS Provision for Installation of Temperature
5.0 AHU Supply Air Temperature -- 48 Wiring from Temperature Sensor
Contractor sensor in duct
Temperature Sensor by BMS Provision for Installation of Temperature
6.0 AHU Return Air Temperature -- 48 Wiring from Temperature Sensor
Contractor sensor in duct
PICV CHW Valve by HVAC Output signal from the DDC Controller SITC of PICV valves including necessary
7.0 AHU Chilled Water Valve Modulation 48 Contractor & wiring to valve actuator nipples / mating flanges in the pipeline
0-10 volt signal & wiring from Potential free contact in auto mode in the
8.0 VFD for Speed Control 23 Wiring from VFD
VFD control circuit of VFD Panel
9.0 Fault Alarm 23 VFD Panel Wiring to VFD Provision of termination in VFD panel.
10.0 Fresh air dampers 23 VFD Panel Wiring to VFD Provision of termination in VFD panel.
Sub Total : 96 190 71 48
VIII Fan Coil Units (FCU)
Temperature Sensor by BMS Provision for Installation of Temperature
1.0 FCU Return Air Temperature 333 333 Wiring from Temperature Sensor
Contractor sensor in duct
PICV CHW Valve by HVAC Output signal from the DDC Controller SITC of PICV valves including necessary
2.0 FCU Chilled Water Valve status 333 Contractor & wiring to valve actuator nipples / mating flanges in the pipeline
Sub Total : 333 333 0 0
IX Heat Recovery Units 4
S.No Description Qty.(Nos) Condition of service Field Device By BMS provider By respective service providers
AI DI AO DO
Relay output @ 2 amp, 230 V & wiring
Potential free contact in auto mode in the
1.0 HRU Fans On/Off -- 8 HRU panel & termination from DDC Controler to
control circuit of HRU MCC Panel
potential free contact of HRU MCC
Auxillary Potential Free Contact provision in
2.0 HRU Run Status -- 8 HRU panel Wiring & termination from HRU panel HRU panel for acquiring the signal
Auxillary Potential Free Contact provision in
3.0 Trip Status -- 8 HRU panel Wiring & termination from HRU panel HRU panel for acquiring the signal
DP Switch(Filter) by BMS Provision for Installation of DP switch
4.0 HRU Filter Status -- 4 Wiring from DP Switch
Contractor across filter
Temperature Sensor by BMS Provision for Installation of Temperature
5.0 HRU Supply Air Temperature -- 4 Wiring from Temperature Sensor
Contractor sensor in duct
Temperature Sensor by BMS Provision for Installation of Temperature
6.0 HRU Return Air Temperature -- 4 Wiring from Temperature Sensor
Contractor sensor in duct
PICV CHW Valve by HVAC Output signal from the DDC Controller SITC of PICV valves including necessary
7.0 HRU Chilled Water Valve Modulation 4 Contractor & wiring to valve actuator nipples / mating flanges in the pipeline

Sub Total : 8 20 4 8
X Fans (Axial & Inline) 42
Auxillary Potential Free Contact provision in
1.0 Fan Run Status -- 42 Fan Panel Wiring & termination from Fan panel Fan panel for acquiring the signal
Auxillary Potential Free Contact provision in
2.0 Trip Status -- 42 Fan Panel Wiring & termination from Fan panel
Fan panel for acquiring the signal
0-10 volt signal & wiring from 6 nos.VFD for kitchen exhaust fans and Potential free contact in auto mode in the
3.0 VFD for Speed Control 17 VFD Wiring from VFD control circuit of VFD Panel
4.0 Fault Alarm 17 VFD Panel Wiring from VFD Provision of termination in VFD panel.
Sub Total : 0 101 17 0
XI Chilled Beams & radiant Cooling
Provision for Installation of RH sensor in in
RH Sensor by BMS
1.0 Relative Humidity -- 4 Wiring from RH Sensor room where chilled beams are installed &
Contractor
radiant cooling is provided
Providing of suitably sized socket in the
2 Chiller Water Temperature In(1) + Out (1) -- 2 Immersion type temp. sensor Immersion temp sensor & field wiring chilled / hot water supply line
Sub Total : 6 0 0 0
S.No Description Qty.(Nos) Condition of service Field Device By BMS provider By respective service providers
AI DI AO DO
XII Airwasher 7
Relay output @ 2 amp, 230 V & wiring
Potential free contact in auto mode in the
1.0 Airwasher ON/OFF -- 7 Air Washer panel & termination from DDC Controler to
control circuit of Airwasher MCC Panel
potential free contact of Airwasher MCC
Auxillary Potential Free Contact provision in
2.0 Airwasher Run Status -- 7 Air Washer panel Wiring & termination from AW panel AW panel for acquiring the signal
Auxillary Potential Free Contact provision in
3.0 Trip Status -- 7 Air Washer panel Wiring & termination from AW panel
AW panel for acquiring the signal
Provision of suitable sized socket for
4.0 Sump Level Monitoring High/Low Level 14 Level Switch Level Switch & field wiring installation of level switch
Relay output @ 2 amp, 230 V & wiring
Potential free contact in auto mode in the
5.0 Pump On/Off Command 7 Air Washer panel & termination from DDC Controler to
control circuit of Airwasher MCC Panel
potential free contact of Airwasher MCC
Auxillary Potential Free Contact provision in
6.0 Pump On/Off Status 7 Air Washer panel Wiring & termination from AW panel AW panel for acquiring the signal
Sub Total : 0 35 0 14
XIII Plate Type Heat Exchanger 3
PICV CHW Valve by HVAC Output signal from the DDC Controller SITC of PICV valves including necessary
1.0 PHE Chilled Water Valve Modulation 3 Contractor & wiring to valve actuator nipples / mating flanges in the pipeline
Relay output @ 2 amp, 230 V & wiring
Potential free contact in auto mode in the
2.0 Pump On/Off Command 3 Plate Type Heat Exchanger & termination from DDC Controler to
control circuit of PHE MCC Panel
potential free contact of PHE MCC
Auxillary Potential Free Contact provision in
3.0 Pump On/Off Status 3 Plate Type Heat Exchanger Wiring & termination from PHE panel PHE panel for acquiring the signal
Providing of suitably sized socket in the
4 Chiller Water Temperature In(1) + Out (1) -- 6 Immersion type temp. sensor Immersion temp sensor & field wiring chilled supply line
Sub Total : 6 3 3 3
XVI VAV 28
DP Switch VAV by BMS Provision for Installation of DP switch
1.0 VAV pressure Status 28 Wiring from DP Switch
Contractor across VAV
Sub Total : 28 0 0 0
XV Disabled room 2
Volt Free Contact by Wiring from DDC to Potential free Auxillary Potential Free Contact from
1.0 Disabled room alarm 2
Electrical Contractor contact Disabled room alarm
Sub Total : 2 0 0
S.No Description Qty.(Nos) Condition of service Field Device By BMS provider By respective service providers
AI DI AO DO
ELECTRICAL SYSTEM
XVI HT Panel 2
Volt Free Contact by Wiring from DDC to Potential free Auxillary Potential Free Contact from
1.0 HT Main panel breaker Status 2 Electrical Contractor contact Electrical Panel
Voltage Transducer to be Provision for installation of voltage
2.0 Incoming Voltage Monitoring -- 6 Voltage Transducer and field wiring
Provided by BMS Contractor transducer in HT panel
KWH Meter to be Provided by Wiring from DDC to Potential free KWH Meter providing Output on Open
3.0 Incoming Metering 2 Electrical Contractor contact Protocol BACnet / Modbus RTU
Volt Free Contact by Wiring from DDC to Potential free
4.0 Trip Alarm -- 2 Auxillary Potential Free Contact from HT
Electrical Contractor contact
Volt Free Contact by Wiring from DDC to Potential free
5.0 Over Current Alarm -- 2 Auxillary Potential Free Contact from HT
Electrical Contractor contact
Volt Free Contact by Wiring from DDC to Potential free
6.0 Earth Fault Alarm -- 2 Auxillary Potential Free Contact from HT
Electrical Contractor contact
Sub Total : 8 8 0 0
XVII LT Panel 1
Volt Free Contact by Wiring from DDC to Potential free Auxillary Potential Free Contact from
1.0 LT Incoming Breaker Status -- 4
Electrical Contractor contact Electrical Panel
Volt Free Contact by Wiring from DDC to Potential free Auxillary Potential Free Contact from
2.0 LT Outgoing Breaker Status -- 29
Electrical Contractor contact Electrical Panel
Integrated Through Rs 485
Communication Port to BMS
Wiring from DDC to Potential free KWH Meter providing Output on Open
3.0 LT Incoming KWH Consumption -- 4 (Typical). KWH Meter to be
contact Protocol BACnet / Modbus RTU
Provided by Electrical
Contractor
Integrated Through Rs 485
Communication Port to BMS
KWH Metering - All Outgoing From Wiring from DDC to Potential free KWH Meter providing Output on Open
4.0 -- 29 (Typical). KWH Meter to be
LT(Except Capacitor) contact Protocol BACnet / Modbus RTU
Provided by Electrical
Contractor
Power Factor Transducer by Power factor Transducer and field Provision for installation of power factor
5.0 Power Factor Monitoring -- 2 BMS Contractor wiring transducer in LT panel
Volt Free Contact by Wiring from DDC to Potential free
6.0 Bus Coupler Status -- 1 Potential Free Contact from LT Panel
Electrical Contractor contact
Sub Total : 35 34 0 0
XVIII UPS
DC Voltage Transducer by Provision for installation of voltage
1.0 Battery Status Monitoring -- 3 Voltage Transducer and field wiring
BMS Contractor transducer in UPS panel
Voltage Transducer by BMS Provision for installation of voltage
2.0 UPS Voltage Monitoring -- 9 Voltage Transducer and field wiring
Contractor transducer in UPS panel
Frequency Trancsducer by Provision for installation of Frequency
3.0 UPS Frequency -- 3 Frequency Transducer and field wiring
BMS Contractor transducer in UPS panel
Volt Free Contact in UPS Wiring from DDC to Potential free Auxillary Potential Free Contact from UPS
4.0 UPS Status -- 3 Panel contact Panel
Volt Free Contact by Wiring from DDC to Potential free Auxillary Potential Free Contact from UPS
5.0 Trip Alarm -- 8 Electrical Contractor contact Panel
S.No Description Qty.(Nos) Condition of service Field Device By BMS provider By respective service providers
AI DI AO DO
Sub Total : 15 11 0 0
XIX External Lighting
Volt Free Contact by Wiring from DDC to Potential free
1.0 External Lighting DB’s On/Off -- 1 Potential Free Contact from Electrical Panel
Electrical Contractor contact
Volt Free Contact by Wiring from DDC to Potential free
2.0 Aviation Light for Terrace On/Off -- 1 Potential Free Contact from Electrical Panel
Electrical Contractor contact
Sub Total : 0 0 0 2
XX DG SET 2
Wiring & termination of potential free
Volt Free Contact by DG Set Relay output @ 2 amp, 230 V & wiring
1.0 DG Run Status (On / Off) -- 2 2 contact in auto mode in the control circuit of
Supplier from FAN MCC
DG MCC Panel
DC Voltage Transducer by Provision for installation of voltage
2.0 DG Battery Monitoring -- 2 Voltage Transducer and field wiring
BMS Contractor transducer in Battery
Volt Free Contact in DG Wiring from DDC to Potential free Auxillary Potential Free Contact from DG
3.0 Earth Fault Alarm -- 2
Panel contact Panel
Volt Free Contact in DG Wiring from DDC to Potential free Auxillary Potential Free Contact from DG
4.0 Over Load Alarm -- 2
Panel contact Panel
Flame Proof Level Switch by Provision of suitably sized socket for
5.0 Oil Tank High/Low Level Monitoring -- 4 Level Switch & field wiring
BMS Contractor installation of level switch
Sub Total : 2 10 0 2
XXI Elevator 8
Wiring from DDC to Potential free Auxillary Potential Free Contact from Lift
1.0 Status Of Each Elevator -- 8 Volt Free Contact
contact control Panel
Wiring from DDC to Potential free Auxillary Potential Free Contact from Lift
2.0 Alarm Monitoring -- 8 Volt Free Contact
contact control Panel
Volt Free Contact by Wiring from DDC to Potential free
3.0 Trip Alarm -- 8 Auxillary Potential Free Contact from HT
Electrical Contractor contact
Sub Total : 0 24 0 0
XXII Fire Panel 1
Fire panel information on open protocol
BACNET Interface with Fire INTEGRATOR UNIT / Software
1.0 Fire Panel [BACnet/Modbus] with built-in interface &
panel Microprocessor connectivity communication cards.
Sub Total : 0 0 0 0
XXIII Public Address system 1
PA panel information on open protocol
BACNET Interface with PA INTEGRATOR UNIT / Software
1.0 PA Panel status [BACnet/Modbus] with built-in interface &
panel Microprocessor connectivity
communication cards.
Sub Total : 0 0 0 0
XXIV TRANSFORMER 2
Volt Free Contact in Wiring from DDC to Potential free Auxillary Potential Free Contact from
1.0 Transformer Trip Status 2 Transformer Panel contact Transformer Panel
Sub Total : 0 2 0 0
S.No Description Qty.(Nos) Condition of service Field Device By BMS provider By respective service providers
AI DI AO DO
PHE
XXV Water Supply & Distribution
Domestic Water Hydro Pneumatic Auxillary Potential Free Contact provision in
1.0 3 3 Pump Panel Wiring & termination from Pump panel
Pumps (Guest Rooms) Run Status Pump panel for acquiring the signal
Domestic Water Hydro Pneumatic
Auxillary Potential Free Contact provision in
2.0 Pumps (Guset Rooms) On VFDs run 3 3 Pump Panel Wiring & termination from Pump panel
Pump panel for acquiring the signal
status
Soft Water Hydro Pneumatic Pumps Auxillary Potential Free Contact provision in
3.0 3 3 Pump panel Wiring & termination from Pump panel
(Guest Rooms) Run Status Pump panel for acquiring the signal
Soft Water Hydro Pneumatic Pumps On Auxillary Potential Free Contact provision in
4.0 3 3 Pump Panel Wiring & termination from Pump panel
VFDs run status Pump panel for acquiring the signal
Level Monitoring (Low / High) Of Soft Level Switch By BMS Provision of suitably sized socket for
5.0 2 2 Level Switch & field wiring
Water Tank Contractor installation of level switch

Sub Total : 0 14 0 0
XXVI FIRE FIGHTING SYSTEM
Auxillary Potential Free Contact provision in
1.0 Hydrant Pump Run Status 1 1 Pump panel Wiring & termination from Pump panel Pump panel for acquiring the signal
Auxillary Potential Free Contact provision in
2.0 Sprikler Pump Run Status 1 1 Pump panel Wiring & termination from Pump panel Pump panel for acquiring the signal
Auxillary Potential Free Contact provision in
3.0 Jockey Pump Run Status 1 1 Pump panel Wiring & termination from Pump panel Pump panel for acquiring the signal
Auxillary Potential Free Contact provision in
4.0 Diesel Operated Pump Run Status 1 1 Pump panel Wiring & termination from Pump panel Pump panel for acquiring the signal
DC Voltage Transducer by Provision for installation of voltage
5.0 Engine Pump Battery Status Monitoring 1 1 Voltage Transducer and field wiring
BMS Contractor transducer in Battery
Pressure Transmitter By BMS Providing of suitably sized socket in the
6.0 Fire Hydrant Line Pressure Monitoring 1 1 Pressure transmitter & wiring
Contractor water line
Sub Total : 2 4 0 0
XXVII EFFULENT TREATMENT PLANT
Auxillary Potential Free Contact provision in
1.0 Equalisation Sump Pump Run Status 2 2 Pump panel Wiring & termination from Pump panel Pump panel for acquiring the signal
Auxillary Potential Free Contact provision in
2.0 Plant Room Sump Pump Run Status 2 2 Pump panel Wiring & termination from Pump panel Pump panel for acquiring the signal
Level Switch By BMS Provision of suitably sized socket for
3.0 Effulant Water Tank Level Monitoring 2 2 Level Switch & field wiring
Contractor installation of level switch
Auxillary Potential Free Contact provision in
4.0 Dosing Unit Pump Run Status 2 2 Pump panel Wiring & termination from Pump panel Pump panel for acquiring the signal
Auxillary Potential Free Contact provision in
5.0 Filter Feed Pump Run Status 2 2 Pump panel Wiring & termination from Pump panel Pump panel for acquiring the signal
Sub Total : 0 10 0 0
XXVIII Water treatment system 1
BACNET Interface with Water treatment system information on
INTEGRATOR UNIT / Software
1.0 Water treatment system status Water treatment system open protocol [BACnet/Modbus] with built-in
connectivity
Microprocessor Panel interface & communication cards.
Sub Total : 0 0 0 0
S.No Description Qty.(Nos) Condition of service Field Device By BMS provider By respective service providers
AI DI AO DO
XXIX SUBMERSIBLE PUMPS
Auxillary Potential Free Contact provision in
1.0 Submersible Pump Run Status 4 4 Pump panel Wiring & termination from Pump panel Pump panel for acquiring the signal
Level Switch by BMS Provision of suitably sized socket for
2.0 High Level Monitoring 2 2 Level Switch & field wiring
Contractor installation of level switch
Sub Total : 0 6 0 0
WATER CONSUMPTION FLOW
XXX METERING
Ultrasonic Flow Meter by Providing of suitably sized socket in the
1.0 Tubewell Water Supply 2 2 Flow meter & wiring
BMS Contractor water line
Ultrasonic Flow Meter by Providing of suitably sized socket in the
2.0 Domestic Hot Water Production Meter 2 2 Flow meter & wiring
BMS Contractor water line
Ultrasonic Flow Meter by Providing of suitably sized socket in the
3.0 Laundry Meter 1 1 Flow meter & wiring
BMS Contractor water line
Ultrasonic Flow Meter by Providing of suitably sized socket in the
4.0 Banquet Kitchen Meter 1 1 Flow meter & wiring
BMS Contractor water line
Ultrasonic Flow Meter by Providing of suitably sized socket in the
5.0 Health Club Meter 1 1 Flow meter & wiring
BMS Contractor water line
Ultrasonic Flow Meter by Providing of suitably sized socket in the
6.0 Hot water makup Meter 1 1 Flow meter & wiring
BMS Contractor water line
Sub Total : 8 0 0 0

XXXI HOT WATER SYSTEM 2


Hot Water Generator Supply Immersion Temperature Immersion temperature sensor with Providing of suitably sized socket in the hot
1.0 2 2
Temperature Sensor by BMS Contractor thermowell & wiring water line
Hot Water Generator Return Immersion Temperature Immersion temperature sensor with Providing of suitably sized socket in the hot
2.0 2 2
Temperature Sensor by BMS Contractor thermowell & wiring water line
Wiring from DDC to Potential free
3.0 Return Hot Water Pumps Run Status 2 2 Volt Free Contact Potential Free Contact from Pump Panel
contact
Wiring from DDC to Potential free
4.0 Water Bodies Pumps Run Status 2 2 Volt Free Contact Potential Free Contact from Pump Panel
contact
Volt Free Contact in Hot Wiring from DDC to Potential free Auxillary Potential Free Contact from Hot
5.0 Hot Water Generator Trip Status 2 2 Water Generator Panel contact Water GeneratorPanel
Sub Total : 4 6 0 0
XXXII WATER TANKS (HIGH/LOW LEVELS)
Fire Water Tank Level Monitoring (Under Provision of suitably sized socket for
1.0 2 2 Level Switch Level Switch & field wiring
Ground Tank) installation of level transmitter
Raw Water Tank Level Monitoring (Under Provision of suitably sized socket for
2.0 2 2 Level Switch Level Switch & field wiring
Ground Tank) installation of level transmitter
Treated Water Tank Level Monitoring Provision of suitably sized socket for
3.0 2 2 Level Switch Level Switch & field wiring
(Under Ground Tank) installation of level transmitter
Fire Water Tank Level Monitoring (Over Provision of suitably sized socket for
4.0 -- -- Level Switch Level Switch & field wiring
Head Tank) installation of level transmitter

S.No Description Qty.(Nos) Condition of service Field Device By BMS provider By respective service providers
AI DI AO DO
Domestic Water Tank Level Monitoring Provision of suitably sized socket for
5.0 -- -- Level Switch Level Switch & field wiring
(Over Head Tank) installation of level transmitter

INTERCONTINENTAL DHAKA Page 10 of 11 1/15/2015


Soft Water Tank Level Monitoring (Over Provision of suitably sized socket for
6.0 -- -- Level Switch Level Switch & field wiring
Head Tank) installation of level transmitter
Flushing Water Tank Level Monitoring Provision of suitably sized socket for
7.0 -- -- Level Switch Level Switch & field wiring
(Over Head Tank) installation of level transmitter
Sub Total : 6 0 0 0
XXXIII PNG GAS
Wiring & termination from gas supply Auxillary Potential Free Contact provision in
1.0 PNG Gas supply at site 1 1 Gas supply panel
panel gas supply panel for acquiring the signal

Wiring & termination from gas supply Auxillary Potential Free Contact provision in
2.0 PNG Gas supply at kitchen 1 1 Gas supply panel
panel gas supply panel for acquiring the signal

Wiring & termination from gas supply Auxillary Potential Free Contact provision in
3.0 PNG Gas supply at Boilers 1 1 Gas supply panel
panel gas supply panel for acquiring the signal

Gas detector location by Wiring & termination from gas detector Auxillary Potential Free Contact provision in
4.0 PNG Gas leakage 15 15
Kitchen consultant panel gas detector panel for acquiring the signal
Sub Total : 3 15 0 0
XXXIV CHILLER/COOLER/FREEZER 91
1.0 chiller/cooler/freeze Run Status 91 chiller/cooler/freezer panel Wiring & termination from chiller panel Provision in panel for acquiring the signal

2.0 High/Low Temperature Fault signal -- 91 chiller/cooler/freezer panel Wiring & termination from chiller panel Provision in panel for acquiring the signal
Sub Total : 0 182 0 0
596 1071 100 107
1874
Total With Spares 2155

INTERCONTINENTAL DHAKA Page 11 of 11 1/15/2015

You might also like