Acid Dew Point Calculation For CFB Boilers Parameters Value Units

This document outlines the parameters and equations used to calculate the acid dew point temperature for flue gases in circulating fluidized bed boilers. It lists common values for variables like SO2 and moisture content in the flue gas. The main equation shown calculates the dew point temperature as a function of the partial pressures of water vapor and sulfur trioxide in the flue gas. The calculated dew point is compared to actual flue gas temperature measurements to check for condensation of acidic vapors.

Uploaded by

Usman Naseem
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
70 views2 pages

Acid Dew Point Calculation For CFB Boilers Parameters Value Units

This document outlines the parameters and equations used to calculate the acid dew point temperature for flue gases in circulating fluidized bed boilers. It lists common values for variables like SO2 and moisture content in the flue gas. The main equation shown calculates the dew point temperature as a function of the partial pressures of water vapor and sulfur trioxide in the flue gas. The calculated dew point is compared to actual flue gas temperature measurements to check for condensation of acidic vapors.

Uploaded by

Usman Naseem
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

Acid Dew point calculation for CFB Boilers

Parameters Value Units


SO2 in flue gas #REF! ppm
Air preheater flue gas pressure -200 mmWC (g)
745.3 mmHg (a)
Moisture in flue gas #REF! % vol
#REF!
Partial pressure of H2O #REF! mmHg(a)
Natural log of f #REF!
SO2 to SO3 conversion #REF! %
#REF!
SO2 in volume percent #REF! %
Partial pressure of SO3 #REF! mmHg(a)
Natural log of j #REF!

Dew Point of Acid Vapors - Sulfurous acid Equation: 1000/T dp=2.276-0.0294 ln(PH2O)-.0858 ln(PSO3)+0.0062
ln(PH2O)ln(PSO3)
Formula as metioned above #REF!
#REF! oK

#REF! oC

150~160 oC
Remarks
Use value in ppm not of mg/NM3

Convert to mmHG (abs) from mmWC


Reference value 10%, based on Lab results
convert to fraction

Assued value Constant 2%


convert to fraction
ppm to % conversion
Mol wt of SO2 & SO3

6-0.0294 ln(PH2O)-.0858 ln(PSO3)+0.0062

Display value on DCS near TT-1020-05. Compare


value with TT-1020-05A/B

If calculated value is higher than operating


value of TT-1020-05A/B, then generate alarm
with description "Operating temperature lower
than Acid dew point temperature"