Smart BMS User Instructions About Cycle Times Calculation

1) The document provides instructions for calculating cycle times, protection times, and capacity for a smart battery management system (BMS). 2) Cycle times are increased when discharge capacity exceeds the set cycle capacity, and reset to 0 upon reconnection or parameter changes. Protection times increase by 1 when a protection event occurs and are reset to 0 by parameter changes. 3) Capacity calculation is based on charge/discharge cycles and calibrated over several cycles based on actual discharge amounts.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
168 views

Smart BMS User Instructions About Cycle Times Calculation

1) The document provides instructions for calculating cycle times, protection times, and capacity for a smart battery management system (BMS). 2) Cycle times are increased when discharge capacity exceeds the set cycle capacity, and reset to 0 upon reconnection or parameter changes. Protection times increase by 1 when a protection event occurs and are reset to 0 by parameter changes. 3) Capacity calculation is based on charge/discharge cycles and calibrated over several cycles based on actual discharge amounts.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

SHEN ZHEN LLT ELECTRNIC TECHONLOGY CO,.LTD WWW.lithiumbatterypcb.

com

Smart BMS user instructions

About cycle times calculation :

1) When the accumulated discharge capacity has exceeded the cycle capacity you

have set , the cycle times will be increased at one time . and it can not affect the cycle

time calculation when user charge the battery in the middle process .

2) When makes reconnection of the bms it can not affect the cycle times

om
metering ,and the accumulated discharge capacity will start to calculate from 0 with

.c
such action .

cb
3)When writes in new parameters or makes any calibration and any setting changes

a
yp
with the bms , it can affect the calculation of the cycle times . after above operation .
er
the accumulated discharge current will be metered from 0 again .
a tt

Protection times metering


u mb

1) When protection occurred with the bms , and protection times will be increased by 1 ,for
hi
it

example : over-voltage protection with single cell’s happened , the protection time with
l

single cell protection will be increased by 1 .


w.
ww

2) Make reconnection of the BMS which will not affect the protection times metering

3) When make the changes with new parameters and any other operation with bms

setting ,and the protection time will be cleared to 0 . therefore , please do not try to change

the parameters setting when the BMS works stably after installation .
SHEN ZHEN LLT ELECTRNIC TECHONLOGY CO,.LTD WWW.lithiumbatterypcb.com

About capacity calculation.

Typical capacity will be the battery’s real capacity value . and calibration will be done by

bms after aging cycles of the battery in according to the actual discharged capacity . and

in every time , the bms will make 10% calibration Minimally and 25% maximally ,. So

please setting the typical capacity of your battery the same with it’s real capacity .
For the big difference of the capacity comparing it’s real capacity , bms will needs several
more cycles to make calibration .

om
Aging cycle process will be : charge fully first , then discharge capacity completely and
makes charge again finally . and for the fully charge condition , it meets one condition as

.c
below will be took as fully charged .

cb
1. And average voltage has reached fully charge voltage you have set with single
cell .and the charge current dropped to 500mA below .

a
2. and over-charge protection with whole battery pack or with single cell occurred .
yp
er

3. Discharge completely : average voltage has reached the single cell over-discharge
tt

protection cut-off voltage .


a
mb

After above process , recharge the battery again . those process will be took as a
complete aging cycles .
u

Capacity calculation : after bms installation , bms will evaluate the remaining capacity in
hi

according to the parameter setting and battery average voltage . it depends on average
it

voltage of battery that which ranges it will be in .


l
w.
ww

In the late charge and discharge process , remaining capacity increase or decrease will be
metered in integral of Current*time , the capacity will jump to 100% or drop to 0 when the
battery meet the fully charge and discharge conditions .
Notes: when undervoltage protection occurred .the capacity will be cleared to 0 , any
parameter setting , or bms reconnection , calibration ,and parameter restore will change
the value of the remaining capacity .and BMS will meter the capacity based on voltage
again . also the cycle condition will be cleared also ,
SHEN ZHEN LLT ELECTRNIC TECHONLOGY CO,.LTD WWW.lithiumbatterypcb.com

About balance setting :

About the consistency of the battery system , if user does not have the professional test

instruments , we can make judgment based on below simply conditions .

1. when makes the battery package , each single cell voltage difference should be less

than 0.03V

2. After 10 times aging cycles . after fully charge of the battery , voltage difference are

om
less than 0.03v , it will indicate the battery capacity consistency is good .

.c
3. With one month rest , voltage difference is less than 0.03V , it indicates the battery

cb
inner resistance consistency is good .

a
yp
4. when there is no electricity with the battery , and big voltage difference will be normal ,
er
it has no relation with battery consistency .
tt

Application of Balance function:


a
mb

1、 Charge battery : balance will start works when the voltage reached the value of
u
hi

balance start voltage also the voltage difference is bigger than the voltage
it

difference you have set during charge process .


l
w.

2、 Static balance : when reaches balance condition during rest time . the balance will
ww

start work .

3、 When the battery has good consistency , we recommend to use charge balance

function . as for the static balance it works more effectively when the battery

voltage difference is big .

4、 Do not set the voltage difference with below of 0.02V , our default value 0.03V will

be good .
SHEN ZHEN LLT ELECTRNIC TECHONLOGY CO,.LTD WWW.lithiumbatterypcb.com

5、 When the battery consistency is good , you can set the balance start voltage with

higher value .

About Bluetooth connection .

1)Connection for Bluetooth will be failed when the signal with Bluetooth is weak

2) For the version of 1.3 or below , Bluetooth light will flash slowly ,and it will go to

hibernation status 8 seconds later together with PCB board . the light will turn on when

om
.c
connecting ,Bluetooth light will turn off when disconnect it 8S later .

cb
When for version of 1.5 or above . Bluetooth will not turn on when make disconnection .

a
and it’s light will light on while connecting .
yp
er
3) It will be better to connect an antenna on the Bluetooth if it was placed inside of the
tt

battery box , suggesting user to place the Bluetooth at outside of the battery to get a
a
mb

strong signal .
u

4) In the case of enabling to search the signal of bluetooth in the application process , user
hi
it

can click the repair button on App to see if the signal can be searched after re-start of
l

Bluetooth .
w.
ww

5) When meet the problems frequently when makes connection of “can not support the

device “,this problems usually resulted from weak signal or Mobile Bluetooth operation .

you can click this repair button to make the connection successfully

Please contact us when meets other problems you can not solved on your side

Common problems

A.. Can not search the signal of Bluetooth ?


SHEN ZHEN LLT ELECTRNIC TECHONLOGY CO,.LTD WWW.lithiumbatterypcb.com

Please check wires connection is correct or not with your battery

B. When meets the battery voltage is 0.1V and IC error message shows on the software

interface.

This problems usually comes from the incorrect wire connection order , please take off

these wires in a reverse order of wire connection order with our diagram , correct wires

connection order should start from making B- connection at first , then connect these

om
wires from B1 ,B2 …. B? ,B+ is the last to be connected .When there are some battery

.c
with 0.9V voltage around, and the neighboring cell with high voltage obviously

cb
please check the wires connection is correct or not

a
yp
er
a tt
u mb
hi
l it
w.
ww