Residential Building Design Project: Selected Column

The document is a column design for a residential building. It provides calculations for determining the axial load and bending moment on column E/4 based on slab and beam loading. The calculated axial load is 1965.41 kN and bending moment is 4.39 kN.m. Reinforcement details are designed to resist these loads with 5 number 20mm diameter bars and 6mm diameter links spaced at 240mm.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
54 views

Residential Building Design Project: Selected Column

The document is a column design for a residential building. It provides calculations for determining the axial load and bending moment on column E/4 based on slab and beam loading. The calculated axial load is 1965.41 kN and bending moment is 4.39 kN.m. Reinforcement details are designed to resist these loads with 5 number 20mm diameter bars and 6mm diameter links spaced at 240mm.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Designed By:

Eng Yahye A/kadir Sheet


Residential Building Design Waberi ()

Project
(Column Design) ID = 16-BSS-ENG-152 6 - 3 -2020

References Calculations Remarks

Selected column

Design data

Fcu = 30N/mm2
Fy = 460N/mm2
Fyv = 250N/mm2
Main Reinforcement = 20mm
Cover = 25mm
Beam size = 250mm x 400mm
Column size = 250mm x 400mm
ALL COLUMNS ARE UNBRACED
Designed By:
Eng Yahye A/kadir Sheet
Residential Building Design Waberi ()

Project
(Column Design) ID = 16-BSS-ENG-152 6 - 3 -2020

References Calculations Remarks

Column E/4

1. Design of roof slab load


[1.4(0.257x24)x7]x7.8 = 67.3kn/m
2. Design of 1st floor slab loading
[1.4(0.257x24)x7]x7.8 +(1.6x1.5x1.7)] = 84.1kn/m
Designed By:
Eng Yahye A/kadir Sheet
Residential Building Design Waberi ()

Project
(Column Design) ID = 16-BSS-ENG-152 6 - 3 -2020

References Calculations Remarks

3. Design of 1st floor loading Beam Loading.


Beam A/B ( dead load from slab and beam self-weight)
[1.4(0.257mx24kn/m3x4.8m) + (0.25x0.4x24)] = 56.32kn/m
Beam B/C ( dead load from slab and beam self-weight)
[1.4(0.257mx24kn/m3x3m) + (0.25x0.4x24)] = 36.46kn/m
Beam B/D ( dead load from slab and beam self-weight)
[1.4(0.257mx24kn/m3x4.6m) + (0.25x0.4x24)] = 54.12kn/m
Design of axial load at x-x
4.8+3
N= x [(67.3 + 84.1) + (2.4x56.32) + (1.5x36.46)] =1330.9
2
Design of axial load at y-y
4.6
N= x [(67.3 + 84.1) + (2.3x54.12)] = 634.51
2
N = 1330.9kn + 634.51kn
N = 1965.41kN
Stiffness, K (column size and beam size = 250mm x 400mm)
𝑏𝑑3 250𝑥4003
IB/E = IB/F = IB/A = IB/C = IB/D = = = 1333.34 x 106mm4
12 12

𝐼 1333.34 𝑥 106
KB/E = kB/F = = = 0.38 x 106 mm3
𝐿 3500
In the sub-frame, the beam stiffnesses are assumed to be equal to
(0.5 x actual value)
𝐼 1333.34 𝑥 106
KB/A = 0.5 x = 0.5 x = 0.14 x 106 mm3
𝐿 4800
𝐼 1333.34 𝑥 106
kB/D = 0.5 x = 0.5 x = 0.14 x 106 mm3
𝐿 4600
𝐼 1333.34 𝑥 106
kB/C = 0.5 x = 0.5 x = 0.22 x 106 mm3
𝐿 3000
Total K = (0.38+0.38+0.14+0.14+0.22) = 1.26 x 106 mm3
Designed By:
Eng Yahye A/kadir Sheet
Residential Building Design Waberi ()

Project
(Column Design) ID = 16-BSS-ENG-152 6 - 3 -2020

References Calculations Remarks

Distribution factor, DF
0.14
DFB/A = DFB/D = = 0.11
1.26
0.14
DFB/E = DFB/F = = 0.30
1.26
0.22
DFB/C = = 0.18
1.26

Fixed End Moment, FEM


𝑤𝑙 2 56.32𝑥4.82
MB/A = MA/B = ± = = ± 108.13kN.m
12 12
𝑤𝑙 2 36.46𝑥32
MB/C = MC/B = ± = = ± 27.34kN.m
12 12
𝑤𝑙 2 54.12𝑥4.62
MB/D = MD/B = ± = = ± 95.43kN.m
12 12

Completing the moment distribution at joint B gives:

Design Moment = 4.39 kn.m


Design Axial Load = 1965.41 kN
Designed By:
Eng Yahye A/kadir Sheet
Residential Building Design Waberi ()

Project
(Column Design) ID = 16-BSS-ENG-152 6 - 3 -2020

References Calculations Remarks

The effective height of column section BF is 3.5m about both


axes.
Table 3.19
x-x direction ; Lex/h = (3500/250) = 14 < 15 Column is
y-y direction ; Ley/h = (3500/400) = 8.75 < 15 short
Assume 8mm diameter links
Effective depth = (400 – 25 - 8 – 13) = 354mm
d/h = 354/400 = 0.89

use design chart No. 29


1965.41𝑥103 2 4.39𝑥106
N/bh = = 19.65 , M/bh = = 0.12
250𝑥400 250𝑥4002
From the chart 27
100Asc/bh = 0.2 k = 1.4
Asc = (1.4x250x400)/100 , Asc = 1400mm2
𝜋 𝜋
No. of bars = xD2 = x202 = 314.16
4 4
= 1400/314.16 =5 bars
5𝑇
𝑚𝑚2
1570.79
Minimum link diameter > (0.25xlargest compression)
= 0.25x20 = 5 ≈ 6mm link
Clause Spacing of link ≤ (12x smallest compression bar)
3.12.7.1 = 12x20 = 240mm
Select R6
at
240mmc/c