0% found this document useful (0 votes)
81 views

IntesisBox HI-AW-KNX-1 Manual Eng

Uploaded by

najib
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
81 views

IntesisBox HI-AW-KNX-1 Manual Eng

Uploaded by

najib
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 21

®

IntesisBox
HI-AW-KNX-1

User’s Manual
Issue date: 09/01/2013
r1 eng
IntesisBox® KNX – Hitachi A.W. User’s Manual r1 eng

© Intesis Software S.L. 2012 All Rights Reserved.

Information in this document is subject to change without prior notice. The software
described in this document is furnished under a license agreement or nondisclosure
agreement. The software may be used only in accordance with the terms of those
agreements. No part of this publication may be reproduced, stored in a retrieval system or
transmitted in any form or any means electronic or mechanical, including photocopying and
recording for any purpose other than the purchaser’s personal use without the written
permission of Intesis Software S.L.

Intesis Software S.L.


Milà i Fontanals, 1 bis
08700 Igualada
Spain

TRADEMARKS
All trademarks and trade names used in this document are acknowledged to be the
copyright of their respective holders.

Information in this document is subject to changes without prior notice.

© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 2 / 21


This information is subject to change without notice Email [email protected]
®
IntesisBox is a registered trademark of Intesis Software SL tel +34 938047134
IntesisBox® KNX – Hitachi A.W. User’s Manual r1 eng

Interface for the integration of Hitachi’s Air-to-


Water units into KNX TP-1 (EIB) control systems.
Compatible with Air-to-Water Yutaki S series.

Application’s Program Version: 0.2

Reference: HI-AW-KNX-1

© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 3 / 21


This information is subject to change without notice Email [email protected]
®
IntesisBox is a registered trademark of Intesis Software SL tel +34 938047134
IntesisBox® KNX – Hitachi A.W. User’s Manual r1 eng

INDEX

1. Presentation ......................................................................................................... 5
2. Connection ........................................................................................................... 6
3. Installation and setup ............................................................................................ 6
4. ETS parameters and communication objects ............................................................. 7
4.1 Default settings ................................................................................................. 7
Run or Stop the unit..................................................................................... 7
Change de Unit mode ................................................................................... 7
Run or Stop the C1 Circuit ............................................................................ 7
Anti-legionella System .................................................................................. 8
KNX menu blocking ...................................................................................... 8
Errors and Alarms ........................................................................................ 8
4.2 General dialog ................................................................................................... 9
4.2.1 System working mode .................................................................................. 9
OTC Mode ................................................................................................... 9
Water mode temperatures .......................................................................... 10
Air mode temperatures ............................................................................... 10
4.2.2 2nd circuit (C2) is available ......................................................................... 11
4.2.3 DHW is available (Domestic Hot Water) ........................................................ 12
Domestic Hot Water ................................................................................... 12
4.2.4 Swimming pool is available ......................................................................... 13
Swimming pool .......................................................................................... 13
4.2.5 Enable use of extra information objects (for Status) ....................................... 13
Yutaki S Extra Information .......................................................................... 14
Yutaki S80 Extra Information ...................................................................... 14
5. Technical Specifications ........................................................................................ 15
6. Compatible Air-to-Water (A.W.) units ..................................................................... 16
7. Error Codes ........................................................................................................ 16
Appendix A – Communication objects description table ................................................ 17

© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 4 / 21


This information is subject to change without notice Email [email protected]
®
IntesisBox is a registered trademark of Intesis Software SL tel +34 938047134
IntesisBox® KNX – Hitachi A.W. User’s Manual r1 eng

1. Presentation

The HI-AW-KNX-1 gateways allows fully bidirectional monitoring and


control of the Hitachi Air-to-Water systems from KNX installations.

The interface is compatible with all the models of the Yutaki S line
commercialized by Hitachi.

General features:

 Reduced dimensions, easy and fast installation.

 Multiple control and status objects (bit, byte, characters…) with standard KNX
datapoints.

 One status object available for each control object.

 Control on the A.W. unit based on the ambient temperature read from the unit itself or
from the temperature read by any KNX thermostat.

 The Hitachi A.W. can be controlled simultaneously through the remote controller of the
A.W. system or through the KNX bus.

 Total supervision and control of the Hitachi A.W. unit from KNX, including unit internal
variables supervision, special modes control (such as Anti-legionella) and error alarm
and codes too.

© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 5 / 21


This information is subject to change without notice Email [email protected]
®
IntesisBox is a registered trademark of Intesis Software SL tel +34 938047134
IntesisBox® KNX – Hitachi A.W. User’s Manual r1 eng

2. Connection
Connection of the interface to the AW indoor unit is by means of the cable supplied with the
indoor unit to connect the remote controller. It must be connected to the interface in one side
(connector H-Link) and to the internal electronic board of the Air-to-Water indoor unit in the
other side.

Connection of the interface to the KNX bus is by means of the standard KNX bus connector
also supplied with the interface.

In order to plug the interface to the external power supply, two different methods are available.
First one is using the external power supply provided with the interface using the DC JACK
connector

Connections diagram:

Power Supply

KNX TP-1
(Bus EIB)
A 2 wire terminal

B
B
DC Jack

IMPORTANT
Connect only one external power
H-Link
supply. Use either the two-wire HI-AW-KNX-1
terminal connector (A) or the DC Max 1000 m
adaptor Jack connector (B).

Hitachi - Yutaki

3. Installation and setup


This is a fully compatible KNX device that must be configured using the ETS software.
The ETS database can be downloaded from:

http://www.intesis.com/down/eib/HI-AW-KNX-1.zip

Please, check the README.txt file located inside the zip file to find instructions for proper
installation of the database.

IMPORTANT: Do not forget to select the corresponding features of the Air-to-Water


system connected to the HI-AW-KNX-1 interface. This should be selected in the
“Parameters” section on the ETS software.

© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 6 / 21


This information is subject to change without notice Email [email protected]
®
IntesisBox is a registered trademark of Intesis Software SL tel +34 938047134
IntesisBox® KNX – Hitachi A.W. User’s Manual r1 eng

4. ETS parameters and communication objects

4.1 Default settings


When importing the ETS database for the first time, the following menu appears, with these
parameter values selected as default:

Figure 4.1 Parameter values by default

With this configuration is possible to control the system (Control_ objects) and monitoring it
(Status_ objects) through the following communication objects:

 Run or Stop the unit

Figure 4.2 Run/Stop communication objects

This object allows to run or to stop the Hitachi unit features (C1,C2, DHW and/or
SwimPool) at once. Sending a “0” value will turn them off, while sending a “1” value
will turn them on.

 Change de Unit mode

Figure 4.3 Unit mode selection communication objects

This object allows changing the working mode of the Hitachi unit. Sending a “0”
value the unit will turn into “Cool” mode, while sending a “1” value will make the unit
turn into “Heat” mode.

 Run or Stop the C1 Circuit

Figure 4.4 C1 circuit Run/Stop communication objects

This object allows to run or to stop the Hitachi C1 Circuit (or C1 climate zone).
Sending a “0” value will close the C1 circuit, while sending a “1” value will open the
C1 Circuit.

More functions related with the C1 circuit and their communication objects can be
seen in section 4.2.1.

© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 7 / 21


This information is subject to change without notice Email [email protected]
®
IntesisBox is a registered trademark of Intesis Software SL tel +34 938047134
IntesisBox® KNX – Hitachi A.W. User’s Manual r1 eng

 Anti-legionella System

NOTE: The anti-legionella function is hidden to users by default. Installer can


make it available if desired.

Figure 4.5 Anti-legionella sysmte communication objects

The Hitachi Yutaki S units include an Anti-legionella system. From the gateway, this
function can be activated by sending a “1” value to the Control_ AntiLeg Run/Stop
object and can be stopped by sending a “0” value to the same object.

It is also possible to send a value to set the temperature of the Anti-legionella


system to this value. To do it so you have to use the Control_ AntiLeg Setpoint
object.

IMPORTANT: Anti-legionella will set the water temperature to the setting value
during the specified time. This temperature will be dangerous to the user and
could burn him or her. Installer is responsible for configuring it properly,
advising the user, and enabling the function.

 KNX menu blocking

Figure 4.6 KNX menu communication objects

This object allows blocking or enabling the KNX menu from Hitachi’s LCD panel.
Sending a “0” value will block the Menu, while sending a “1” value will enable the
Menu.

 Errors and Alarms

Figure 4.7 Errors and alarms communication objects

These objects allows reading the system status indicating if any alarm or error is
active (Status_ Error/Alarm) and, in case it exist, it indicates which error is (Status_
Error Code). See section 7 to get more information about the error codes.

© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 8 / 21


This information is subject to change without notice Email [email protected]
®
IntesisBox is a registered trademark of Intesis Software SL tel +34 938047134
IntesisBox® KNX – Hitachi A.W. User’s Manual r1 eng

4.2 General dialog


In the General Dialog (settings) tab, it is possible to enable, disable or modify the
parameters shown in Figure 4.1. For instance, the first field is showing where you can
download the database and the user manual from.

Figure 4.8 Database and User Manual location

4.2.1 System working mode


This parameter enables or disables communication objects depending on the working mode
selected: Water mode, Air, mode or Full (which includes both: Water and Air).

Figure 4.9 System working mode parameter details

o When selecting “Water” the interface will work for a water climate environment only.
Water climate control and status objects will be available. Air climate control and status
objects will be disabled.

 OTC Mode
The OTC mode (Output Temperature Compensation) allows keeping the desired
indoor temperature despite external temperature variations.

From the gateway you can:


 Turn this function off by sending a “1” value to the Control_ C1 OTC Mode
Heat/Cool Off communication object.

Figure 4.10 OTC Mode Off communication objects

 Activate the different modes available for the calculus of the water temperature
for the cooling or heating the facility where the unit is placed:
 Points: User fixes 4 points that will create a line function that will
depend on the current ambient temperature.
 Gradients: In this case, the function used is not a line but a gradient.
Only available for the Heat mode.
 Fix: The temperature adjustment is only performed by a fixed value.
This makes the unit to keep this fixed value all the time.

© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 9 / 21


This information is subject to change without notice Email [email protected]
®
IntesisBox is a registered trademark of Intesis Software SL tel +34 938047134
IntesisBox® KNX – Hitachi A.W. User’s Manual r1 eng

Figure 4.11 OTC Mode type selection communication objects

 Water mode temperatures


Using the following communication objects it is possible to control/monitorize water
setpoint temperatures for the Heat and Cool modes (C1 Water Heat Setpoint and
C1 Water Cool Setpoint).

Figure 4.12 Water Mode temperatures communication objects

o When selecting “Air”, the interface will work for an air climate environment only. Air
climate control and status objects will be available. Water climate control and status
objects will be disabled.

 Air mode temperatures


With the communication objects corresponding to this mode enabled,
control/monitoring of the setpoint temperature of the thermo (C1 Thermo Setpoint)
and the ambient temperature provided by a thermostat not included in the Hitachi
system (C1 Ambient Temp).

Figure 4.13 Air mode temperature communication objects

o When selecting “Full”, the interface will work for an air and water climate environment.
Air and Water climate control and status objects will be available.

© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 10 / 21


This information is subject to change without notice Email [email protected]
®
IntesisBox is a registered trademark of Intesis Software SL tel +34 938047134
IntesisBox® KNX – Hitachi A.W. User’s Manual r1 eng

4.2.2 2nd circuit (C2) is available


This parameter enables or disables the Control_ and Status_ communication objects of a
second circuit (or climate zone). In case the project is divided into 2 separated circuits this
parameter needs to be selected to get control on each circuit independently.

Figure 4.14 2nd circuit parameter detail

o When selecting “No”, the gateway will hide the 2nd circuit (C2) communication objects.

o When selecting “Yes”, the gateway will show the the 2nd circuit (C2) communication
objects. Depending on the other selected parameters, some objects will remain hidden
and some others will be shown.

 Run and Stop status:

Figure 4.15 2nd circuit Run/Stop communication objects

To activate or deactivat the 2nd circuit (C2) a “1” value or a “0” value needs
to be sent respectively to the Run/stop communication object.

 If “Water” mode is selected:

Figure 4.16 2nd circuit Water Mode communication objects

© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 11 / 21


This information is subject to change without notice Email [email protected]
®
IntesisBox is a registered trademark of Intesis Software SL tel +34 938047134
IntesisBox® KNX – Hitachi A.W. User’s Manual r1 eng

 If “Air” mode is selected:

Figure 4.17 2nd circuit Air Mode communication objects

 If “Full” mode is selected, all communication objects present when selecting


“Water” or “Air” will be enabled for this mode too.

4.2.3 DHW is available (Domestic Hot Water)


This parameter enables or disables the Control_ and Status_ objects corresponding to the
control and monitoring of a water tank or DHW system.

Figure 4.18 DHW Parameter detail

o When selecting “No”, the gateway will hide communication objects related with the
water tank or the Domestic Hot Water system.

o When selecting “Yes”, the gateway will show the communication objects related
with the water tank or the Domestic Hot Water system.

 Domestic Hot Water


By means of Control_ DHW Run/Stop and Control_ DHW Setpoint, it is possible to
turn on/off the DHW system and also to control its setpoint temperature.

Through the Status_ DHW Temperature communication object, it is possible to read


the instantaneous temperature of the DHW system.

Figure 4.19 DHW mode communication objects

© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 12 / 21


This information is subject to change without notice Email [email protected]
®
IntesisBox is a registered trademark of Intesis Software SL tel +34 938047134
IntesisBox® KNX – Hitachi A.W. User’s Manual r1 eng

4.2.4 Swimming pool is available


This parameter enables or disables the Control_ and Status_ objects corresponding to the
control and monitoring of a swimming pool system present in the project

Figure 4.20 Swimming pool parameter details

o When selecting “No”, the gateway will hide communication objects related with the
swimming pool.

o When selecting “Yes”, the gateway will show communication objects related with
the swimming pool.

 Swimming pool
By means of Control_ SwimPool Run/Stop and Control_ SwimPool Setpoint, it is
possible to turn on/off the Swimming pool system and also to control its setpoint
temperature.

Through the Status_ SwimPool Temperature communication object, it is possible to


read the instantaneous temperature of the Swimming pool system.

Figure 4.21 Swimming pool mode communication objects

4.2.5 Enable use of extra information objects (for Status)


These parameters enable or disable the Status_ communication objects related to the
monitoring of extra information depending on the installed Hitachi model (Yutaki S or Yutaki
S80).

o When selecting “No”, the gateway will hide communication objects related with the
extra information provided by the Hitachi units.

o When selecting “Yes”, the gateway will offer you to select extra information for a
Yutaki S80 model or the rest of Yutaki S models (then select “No”).

Figure 4.22 Extra Information parameters detail

 If “No” is selected (the installed unit is not a Yutaki S80 model)


communication objects providing extra information about the Yutaki S
models will appear.

© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 13 / 21


This information is subject to change without notice Email [email protected]
®
IntesisBox is a registered trademark of Intesis Software SL tel +34 938047134
IntesisBox® KNX – Hitachi A.W. User’s Manual r1 eng

 Yutaki S Extra Information

Figure 4.23 Extra Information status communication objects

 If “Yes” is selected (the installed unit is a Yutaki S80 model), the Control_
Unit Mode and the Status_ Unit Mode communication objetcs will be hidden
and new communication objects will appear providing extra and specific
information for the Yutaki S80.

 Yutaki S80 Extra Information

Figure 4.24 Extra Information for Yutaki S80 status communication objects

For more details about the information provided by those comunication objects, please
check the Hitachi user manual.

© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 14 / 21


This information is subject to change without notice Email [email protected]
®
IntesisBox is a registered trademark of Intesis Software SL tel +34 938047134
IntesisBox® KNX – Hitachi A.W. User’s Manual r1 eng

5. Technical Specifications
Enclosure ABS (UL 94 HB) de 2,5 mm thick
Dimensions 70 X 70 X 28 mm
Weight 70g
Color Ivory White
Power supply 29V DC, 6mA (KNX bus)
10-40V DC, 100mA
(Recommended: 12V DC, 100 mA)
External Power
Supply Must use a NEC Class 2 or Limited Power Source (LPS) and SELV rated power
supply.
Plug-in terminal block for power connection (2 poles).
Per terminal: solid wires or stranded wires (twisted or with ferrule)
Terminal wiring (for 1 core: 0.5mm2… 2.5mm2
power supply and
low-voltage signals) 2 cores: 0.5mm2… 1.5mm2
3 cores: not permitted
KNX port 1 x KNX TP1 (EIB) port opto-isolated. Plug-in terminal block (2 poles). TNV-1
H-Link port Plug-in terminal block for H-Link bus connection (2 poles) with no polarity
LED indicators 1 x KNX programming.
Push buttons 1 x KNX programming.
Configuration Configuration with ETS.
Operating
From 0ºC to 40ºC
Temperature
Storage Temperature From 0ºC to 40ºC
Operating Humidity 25-90% at 50ºC, non condensing
External Power Supply – KNX: 2500V
Isolation voltage
External Power Supply – H-Link: 1500V
RoHS conformity Compliant with RoHS directive (2002/95/CE).
CE conformity to EMC directive (2004/108/EC) and Low-voltage directive
(2006/95/EC)
Certifications
EN 61000-6-2; EN 61000-6-3; EN 60950-1; EN 50491-3; EN 50090-2-2;
EN 50428; EN 60669-1; EN 60669-2-1

External Power Supply connection

KNX port

KNX programming LED

KNX programming button


70 mm

H-Link port

28 mm
70 mm

© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 15 / 21


This information is subject to change without notice Email [email protected]
®
IntesisBox is a registered trademark of Intesis Software SL tel +34 938047134
IntesisBox® KNX – Hitachi A.W. User’s Manual r1 eng

6. Compatible Air-to-Water (A.W.) units


A list of Hitachi unit model references compatible with HI-AW-KNX-1 and their
available features can be found in:
http://www.intesis.com/pdf/IntesisBox_HI-AW-xxx-1_AC_Compatibility.pdf

7. Error Codes
Remote
KNX Error
Controller Error Error Description
Code
Code
00 N/A No errors
Activation of Outdoor Unit Protection Device
02 02
(Except for Alarm Code 41, 42)
03 03 Transmission Error
04 04 Inverter Transmission Abnormality
05 05 Power Phase Detection Abnormality
06 06 Undervoltage, Overvoltage
07 07 Abnormal decrease of discharge gas superheat degree
08 08 Compressor-Top Temp Over-increase
11 11 Water inlet thermistor abnormally (THMWI)
12 12 Water outlet thermistor abnormally (THMWO)
13 13 Indoor Liquid Pipe Temp Thermistor Abnormality (THML)
14 14 Indoor Gas Pipe Temp. Thermistor Abnormality (THMG)
15 15 Water outlet C2 thermistor abnormally (THMWO2)
16 16 Water DHWT thermistor abnormally (THMDHWT)
17 17 Swimming pool thermistor abnormally (THMSWP)
18 18 Water outlet boiler thermistor abnormally (THMWO3)
20 20 Compressor-Top Temp Thermistor Abnormality
21 21 2nd ambient thermistor abnormally (THMAMB2)
22 22 Outdoor Temp Thermistor Abnormality
24 24 Outdoor Heat Exchanger Liquid Pipe Thermistor Abnormality
31 31 Indoor/Outdoor Combination Setting Error
35 35 Indoor Unit Number Setting Error
38 38 Outdoor Protection Detection Circuit Abnormality
41 41 Cooling Overload
42 42 Heating Overload
47 47 Suction Pressure Decrease Prevention Activated
48 48 Inverter Current Sensor Abnormality
51 51 Overload Operation Protection Activation
53 53 Inverter Module Error
54 54 Inverter Fin Temp. Abnormality
55 55 Inverter Non-Operation
59 59 Inverter Fin Temp Thermistor Abnormality
b1 b1 Error in Address/Refrigerant System Setting
EE EE Compressor Factor Alarm
70 70 Hydraulic alarm
71 71 Water Pump Feedback
72 72 Thermostat Heater Alarm
73 73 Mixing over-temperature limit protection for Mixed circuit
74 74 Unit over-temperature limit protection
75 75 Freeze Protection by Cold water inlet, outlet temperature detection
76 76 Freeze Protection Stop by indoor liquid temperature thermistor
77 77 Opentherm Communication failure
78 78 RF Communication failure
79 79 Unit Capacity setting Error
80 80 LCD H-link transmission error
81 81 Incorrect PCB operation
65535 N/A Communication error between HI-AW-KNX-1 interface and the Hitachi Unit

In case you detect an error code not listed, please contact your nearest Hitachi support
center to get more information about the meaning of the error.

© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 16 / 21


This information is subject to change without notice Email [email protected]
®
IntesisBox is a registered trademark of Intesis Software SL tel +34 938047134
IntesisBox® KNX – Hitachi A.W. User’s Manual r1 eng

Appendix A – Communication objects description table


Control Objects

OBJECT DATAPOINT TYPE FLAGS


SECTION NAME LONG. FUNCTION
NUMBER
DPT_NAME DPT_ID R W T U

Run/Stop 0 Control_ Unit Run/Stop 1 bit DPT_Start 1.010 W T 0 - Stop; 1 - Run

Mode 1 Control_ Unit Mode 1 bit DPT_Heat/Cool 1.100 W T 0 - Cool; 1 – Heat

2/14 Control_ Cx1 Run/Stop 1 bit DPT_Start 1.010 W T 0 - Stop; 1 - Run

3/15 Control_ Cx1 Heat OTC Mode Off 1 bit DPT_Bool 1.002 W T 1 – Set OTC Mode OFF

4/16 Control_ Cx1 Heat OTC Mode Points 1 bit DPT_Bool 1.002 W T 1 – Set OTC Mode POINTS

5/17 Control_ Cx1 Heat OTC Mode Grad 1 bit DPT_Bool 1.002 W T 1 – Set OTC Mode GRAD

Water Circuit 6/18 Control_ Cx1 Heat OTC Mode Fix 1 bit DPT_Bool 1.002 W T 1 – Set OTC Mode FIX

(C1 and C2) 7/19 Control_ Cx1 Cool OTC Mode Off 1 bit DPT_Bool 1.002 W T 1 – Set OTC Mode OFF

8/20 Control_ Cx1 Cool OTC Mode Points 1 bit DPT_Bool 1.002 W T 1 – Set OTC Mode POINTS

9/21 Control_ Cx1 Cool OTC Mode Fix 1 bit DPT_Bool 1.002 W T 1 – Set OTC Mode FIX

10/22 Control_ Cx1 Thermo Setpoint 2 bytes DPT_Value_Temp 9.001 W T ºC (Between 0ºC and 35ºC)

11/23 Control_ Cx1 Ambient Temp 2 bytes DPT_Value_Temp 9.001 W T ºC (Between -20ºC and 40ºC)

1
X can be 1 or 2 depending on which circuit is being controlled.

© Intesis Software S.L. – Todos los derechos reservados URL http://www.intesis.com 17 / 21


Información sujeta a cambios sin previo aviso Email [email protected]
IntesisBox® es una marca registrada de Intesis Software SL tel +34 938047134
IntesisBox® KNX – Hitachi A.W. User’s Manual r1 eng

12/24 Control_ Cx1 Water Heat Setpoint 2 bytes DPT_Value_Temp 9.001 W T ºC (Between 20ºC and 80ºC)

13/25 Control_ Cx1 Water Cool Setpoint 2 bytes DPT_Value_Temp 9.001 W T ºC (Between 5ºC and 21ºC)

26 Control_ DHW Run/Stop 1 bit DPT_Start 1.010 W T 0 - Stop; 1 - Run


DHW
27 Control_ DHW Setpoint 2 bytes DPT_Value_Temp 9.001 W T ºC (Between 30ºC and 75ºC)

28 Control_ SwimPool Run/Stop 1 bit DPT_Start 1.010 W T 0 - Stop; 1 - Run


Swimming pool
29 Control_ SwimPool Setpoint 2 bytes DPT_Value_Temp 9.001 W T ºC (Between 24ºC and 33ºC)

30 Control_ AntiLeg Run/Stop 1 bit DPT_Start 1.010 W T 0 - Stop; 1 - Run


AntiLeg
31 Control_ AntiLeg Setpoint 2 bytes DPT_Value_Temp 9.001 W T ºC (Between 50ºC and 75ºC)

KNX Block 32 Control_ KNX Blocks/Enables Menu 1 bit DPT_Enable 1.003 W T 0 – Blocks; 1 – Enables

© Intesis Software S.L. – Todos los derechos reservados URL http://www.intesis.com 18 / 21


Información sujeta a cambios sin previo aviso Email [email protected]
IntesisBox® es una marca registrada de Intesis Software SL tel +34 938047134
IntesisBox® KNX – Hitachi A.W. User’s Manual r1 eng

Status Objects
OBJETO DATAPOINT TYPE FLAGS
SECTION NAME LONG. FUNCTION
NUMBER DPT_NAME DPT_ID R W T U
Mode 33 Status_ Unit Mode 1 bit DPT_Heat/Cool 1.100 R T 0 – Cool; 1 – Heat

34/46 Status_ Cx2 Run/Stop 1 bit DPT_Start 1.010 R T 0 – Stop; 1 – Run


2
35/47 Status_ Cx Heat OTC Mode Off 1 bit DPT_Bool 1.002 R T 1 – OTC Mode Off Set
2
36/48 Status_ Cx Heat OTC Mode Points 1 bit DPT_Bool 1.002 R T 1 – OTC Mode POINTS Set

37/49 Status_ Cx2 Heat OTC Mode Grad 1 bit DPT_Bool 1.002 R T 1 – OTC Mode FIX Set

38/50 Status_ Cx2 Heat OTC Mode Fix 1 bit DPT_Bool 1.002 R T 1 – OTC Mode Off Set
Water Circuit 39/51 2
Status_ Cx Cool OTC Mode Off 1 bit DPT_Bool 1.002 R T 1 – OTC Mode Off Set
2
(C1 y C2) 40/52 Status_ Cx Cool OTC Mode Points 1 bit DPT_Bool 1.002 R T 1 – OTC Mode POINTS Set

41/53 Status_ Cx2 Cool OTC Mode Fix 1 bit DPT_Bool 1.002 R T 1 – OTC Mode FIX Set

42/54 Status_ Cx2 Thermo Setpoint 2 bytes DPT_Value_Temp 9.001 R T ºC


2
43/55 Status_ Cx Ambient Temp 2 bytes DPT_Value_Temp 9.001 R T ºC
2
44/56 Status_ Cx Water Heat Setpoint 2 bytes DPT_Value_Temp 9.001 R T ºC

45/57 Status_ Cx2 Water Cool Setpoint 2 bytes DPT_Value_Temp 9.001 R T ºC

58 Status_ DHW Run/Stop 1 bit DPT_Start 1.010 R T 0 – Stop; 1 – Run

DHW 59 Status_ DHW Setpoint 2 bytes DPT_Value_Temp 9.001 R T ºC

60 Status_ DHW Temperature 2 bytes DPT_Value_Temp 9.001 R T ºC

61 Status_ SwimPool Run/Stop 1 bit DPT_Start 1.010 R T 0 – Stop; 1 – Run

Swimming pool 62 Status_ SwimPool Setpoint 2 bytes DPT_Value_Temp 9.001 R T ºC

63 Status_ SwimPool Temperature 2 bytes DPT_Value_Temp 9.001 R T ºC

2
X can be 1 or 2 depending on which circuit is being observed.

© Intesis Software S.L. – Todos los derechos reservados URL http://www.intesis.com 19 / 21


Información sujeta a cambios sin previo aviso Email [email protected]
IntesisBox® es una marca registrada de Intesis Software SL tel +34 938047134
IntesisBox® KNX – Hitachi A.W. User’s Manual r1 eng

64 Status_ AntiLeg Run/Stop 1 bit DPT_Start 1.010 R T 0 – Stop; 1 – Run


AntiLeg
65 Status_ AntiLeg Setpoint 2 bytes DPT_Value_Temp 9.001 R T ºC

KNX Block 66 Status_ KNX Block/Enable Menu 1 bit DPT_Enable 1.003 R T 0 – Block; 1 – Enable

67 Status_ Error/Alarm 1 bit DTP_Alarm 1.005 R T 0 - No Alarm; 1 - Alarm


Error and
Alarms
68 Status_ Error Code 2 bytes Enumerated R T 0 – No error; Other values see 7

69 Status_ Operation State Unit On/Off 1 bit DPT_Switch 1.001 R T 0 - Off; 1-On

70 Status_ Operation State Cool Demand 1 bit DPT_Switch 1.001 R T 0 - Off; 1-On

71 Status_ Operation State Cool Thermo 1 bit DPT_Switch 1.001 R T 0 - Off; 1-On

72 Status_ Operation State Heat Demand 1 bit DPT_Switch 1.001 R T 0 - Off; 1-On

73 Status_ Operation State Heat Thermo 1 bit DPT_Switch 1.001 R T 0 - Off; 1-On

74 Status_ Operation State DHW 1 bit DPT_Switch 1.001 R T 0 - Off; 1-On

75 Status_ Operation State Swim Pool 1 bit DPT_Switch 1.001 R T 0 - Off; 1-On

76 Status_ Operation State Alarm 1 bit DTP_Alarm 1.005 R T 0 - No Alarm; 1 - Alarm

77 Status_ Outdoor Ambient Temp 2 bytes DPT_Value_Temp 9.001 R T ºC


Extra
Information
78 Status_ Second Ambient Temp 2 bytes DPT_Value_Temp 9.001 R T ºC

79 Status_ Water Inlet Temp 2 bytes DPT_Value_Temp 9.001 R T ºC

80 Status_ Water Outlet Temp 2 bytes DPT_Value_Temp 9.001 R T ºC

81 Status_ Defrost Operation 1 bit DPT_Switch 1.001 R T 0 - Off; 1-On

82 Status_ Water Pump 1 Operation 1 bit DPT_Switch 1.001 R T 0 - Off; 1-On

83 Status_ Water Pump 2 Operation 1 bit DPT_Switch 1.001 R T 0 - Off; 1-On

84 Status_ Water Pump 3 Operation 1 bit DPT_Switch 1.001 R T 0 - Off; 1-On

85 Status_ Dish. Gas Temp 2 bytes DPT_Value_Temp 9.001 R T ºC

86 Status_ Suct. Gas Temp 2 bytes DPT_Value_Temp 9.001 R T ºC

© Intesis Software S.L. – Todos los derechos reservados URL http://www.intesis.com 20 / 21


Información sujeta a cambios sin previo aviso Email [email protected]
IntesisBox® es una marca registrada de Intesis Software SL tel +34 938047134
IntesisBox® KNX – Hitachi A.W. User’s Manual r1 eng

87 Status_ Gas Temp THMg 2 bytes DPT_Value_Temp 9.001 R T ºC

88 Status_ Liquid Temp THMI 2 bytes DPT_Value_Temp 9.001 R T ºC

89 Status_ Water Outlet Temp 3 2 bytes DPT_Value_Temp 9.001 R T ºC

90 Status_ Outdoor AmbAvg Temp 2 bytes DPT_Value_Temp 9.001 R T ºC

91 Status_ Inv Oper Freq 2 bytes DPT_Value_Frequency 14.033 R T Hz

92 Status_ Indoor Exp Valve Opening 1 byte DPT_Scaling 5.001 R T %

93 Status_ Outdoor Exp Valve Opening 1 byte DPT_Scaling 5.001 R T %

94 Status_ Mixing Valve Position 1 byte DPT_Scaling 5.001 R T %

95 Status_ Compressor Run Current 2 bytes DPT_Value_Cur 9.021 R T mA

96 Status_ Dish. Gas Temp R134A 2 bytes DPT_Value_Temp 9.001 R T ºC

97 Status_ Suct. Gas Temp R134A 2 bytes DPT_Value_Temp 9.001 R T ºC

98 Status_ Liquid Temp R134A 2 bytes DPT_Value_Temp 9.001 R T ºC

99 Status_ Evap. Gas Temp R134A 2 bytes DPT_Value_Temp 9.001 R T ºC

Extra 100 Status_ Disch. Pressure R134A 2 bytes DPT_Value_Pressure 14.058 R T Pa


Information
Yutaki S80 101 Status_ Suct. Pressure R134A 2 bytes DPT_Value_Pressure 14.058 R T Pa

102 Status_ Inv Oper Freq R134A 2 bytes DPT_Value_Frequency 14.033 R T HZ

103 Status_ Indoor Exp Valve Open R134A 1 byte DPT_Scaling 5.001 R T %

104 Status_ Compressor Run Current R134A 2 bytes DPT_Value_Cur 9.021 R T A

105 Status_ Error Code R134A 2 bytes Enumerated R T 0 – No error; Other values see 7

© Intesis Software S.L. – Todos los derechos reservados URL http://www.intesis.com 21 / 21


Información sujeta a cambios sin previo aviso Email [email protected]
IntesisBox® es una marca registrada de Intesis Software SL tel +34 938047134

You might also like