Data Sheet C250D6 PDF
Data Sheet C250D6 PDF
Model: C250 D6
Frequency: 60
Fuel Type: Diesel
Standby Prime
Fuel consumption Kw (kVA) Kw (kVA)
Ratings 250 (313) 225 (281)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
gph 5.1 8.6 12.2 16.3 3.7 6.8 10.1 13.7
L/hr 23.4 39.0 55.7 74.3 16.7 31.0 45.9 62.5
Fuel flow
Maximum fuel flow, L/hr 165
Maximum fuel inlet restriction, mm Hg 203
Maximum fuel inlet temperature (°C) 70
©2012 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
Document no. DS69-CPGK-RevD - 24/2/2012
Air Standby Rating Prime Rating
Combustion air, m 3/min 24.70 23.30
Maximum air cleaner restriction, kPa 6.2
Exhaust
Exhaust gas flow at set rated load, m3/min 65.2 56.1
Exhaust gas temperature, °C 580 500
Maximum exhaust back pressure, kPa 10.2
Genset outline
Open set
Enclosed set
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.
©2012 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
Document no. DS69-CPGK-RevD - 24/2/2012
Alternator data
Connection 1 Temp rise °C Duty2 Alternator Voltage
Wye, 3 Phase 125/105 S/P HC4D 416-480V
Wye, 3 Phase 150/125C S/P UCD274K 440-480
Ratings definitions
Emergency Standby Limited-Time running Prime Power (PRP) Base Load (Continuous)
Power (ESP) Power (LTP): Power (COP)
Applicable for supplying power to Applicable for supplying power to a Applicable for supplying power to Applicable for supplying power
varying electrical load for the constant electrical load for limited varying electrical load for unlimited continuously to a constant electrical
duration of power interruption of a hours. Limited Time Running Power hours. Prime Power (PRP) is in load for unlimited hours. Continuous
reliable utility source. Emergency (LTP) is in accordance with ISO accordance with ISO 8528. Ten Power (COP) in accordance with ISO
Standby Power (ESP) is in 8528. percent overload capability is 8528, ISO 3046, AS 2789, DIN 6271
accordance with ISO 8528. Fuel available in accordance with ISO and BS 5514.
Stop power in accordance with ISO 3046, AS 2789, DIN 6271 and BS
3046, AS 2789, DIN 6271 and BS 5514.
5514.
©2012 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
Document no. DS69-CPGK-RevD - 24/2/2012