Transformer Test Report - Calculation Transformer Specification

The document is a test report summarizing the results of open circuit and short circuit tests on a 35 kVA transformer. Key details include: - The transformer has a primary voltage of 415V and secondary voltage of 220V. - Open circuit test results show a no-load power factor of 0.3559 and voltage, current, and power measurements. - Short circuit test results show a full-load power factor of 0.773 and primary current, power consumed, and impedance measurements. - Efficiency calculations show a value of 96.01% which meets the required minimum of 95%. Regulation is reported as 0.00% which meets the target of less than 2%.

Uploaded by

KALAI
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
229 views

Transformer Test Report - Calculation Transformer Specification

The document is a test report summarizing the results of open circuit and short circuit tests on a 35 kVA transformer. Key details include: - The transformer has a primary voltage of 415V and secondary voltage of 220V. - Open circuit test results show a no-load power factor of 0.3559 and voltage, current, and power measurements. - Short circuit test results show a full-load power factor of 0.773 and primary current, power consumed, and impedance measurements. - Efficiency calculations show a value of 96.01% which meets the required minimum of 95%. Regulation is reported as 0.00% which meets the target of less than 2%.

Uploaded by

KALAI
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

Transformer Test Report - Calculation

Transformer Specification Transformer Efficiency


Capacity 35 kVA Voltage Regulation
Primary DELTA
Secondary STAR
Primary Voltage 415 Voltage If Regulation denotes 0.00 % , Please keep the regula
Secondary Voltage 220 Voltage <2% . Due to the regulation value is almost nearest t
Primary Current 48.7 Amps
Secondary Current 91.15 Amps

Open Circuit Test : Short Circuit Test :

Voltage Applied (Vo) 415 Voltage Voltage Applied (Vs)


Current Consumed (Io) 0.95 Amps Current Consumed - Primary (Is)
Power Consumed (Woc) 243.00 Watts Power Consumed (Wsc)

Woct. 140.30 Watts Wsct.


Cos Փ 0.3559 Cos Փ
Sine Փ 0.9345 Sine Փ

Calculations : Calculations :

Core Loss Componen (Ic) 0.338 Amps Copper Loss Component (Ic)
Core Loss Resistance (Rc) 1227.6 Ω HV side Resistance (Rie)
Magnetising Current (Im) 0.888 Amps Magnetising Current (Im)
Magnetising Reactanc (Xm) 467.4 Ω HV side Leakage Reactance (Xie)
Magnetising Impedanc (Zie) 1313.6 Ω HV side Impedance (Zie)
Power Factor Cosθ (no-load) 0.3559 Power Factor cosθ (full-load)
n

96.01 % >95%
0.00 % <2%
To be fill Manually with Load test Readings

00 % , Please keep the regulation Value, Report results will be generated as per given values
tion value is almost nearest to the ZERO

13.5 Voltage
48.7 Amps
880.0 Watts

508.07 Watts
0.773
0.635

37.635 Amps
0.359 Ω
30.908 Amps
0.437 Ω
0.565 Ω
0.773