This document provides operating instructions and troubleshooting information for an OILMATIC temperature control system. It describes how to start and stop the system using control panel buttons or external signals. Settings like key lock and temperature control mode can be adjusted. Alarm codes and their causes are listed to help with issues, such as sensing a temperature outside the set range or filter clogging. Troubleshooting steps are suggested, such as checking sensor connections.

Uploaded by

sunhuynh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
67% found this document useful (3 votes)
20K views1 page

Kanto Seiki Support Manual

This document provides operating instructions and troubleshooting information for an OILMATIC temperature control system. It describes how to start and stop the system using control panel buttons or external signals. Settings like key lock and temperature control mode can be adjusted. Alarm codes and their causes are listed to help with issues, such as sensing a temperature outside the set range or filter clogging. Troubleshooting steps are suggested, such as checking sensor connections.

Uploaded by

sunhuynh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Support manual Service section TEL 027-251-2123

KANTO SEIKI FAX 027-290-1881


■Operating and stopping method :
(1)Operating method:Press ①"POW"key until ⑧"RUN" lamp lights up to operate OILMATIC. ⑦Parameter LED
(2)Stopping method:Press1①"POW"key until ⑧"RUN" lamp turns off to stop OILMATIC. ⑥DATA LED
(3)Operating and stopping by the external starting signal:When a No.14,19 terminals (for the exclusive use of external starting ) ⑧RUN lamp ⑤UP key
are received the external starting signal from the main machine,the OILMATIC operats and terminated OILMATIC stops.

■Setting and canceling key lock method : RUN

(1)Setting key lock method:Press ⑤"UP"and ④"DOWN"keys simultaneously until "LED" on lower right ⑥"LED" UP
area blinks to deactivate all key operation excluding ①"POW" key. PARA DATA
(2)Canceling key lock method:Press ⑤"UP"and ④"DOWN"keys simultaneously until "LED" on lower right ⑥"LED" DOWN
area turns off to activate all key operaions. POW TMR PARA ENT
④DOWN key
■Selecting temperature control method :
(1)Changing base temperature follow up mode or constant mode:Press both ②"PARA"and ③"ENT" keys and also
either ⑤"UP" key or ④"DOWN" key to make a change. ①POW key ②PARA key ③ENT key
The change of setting is completed upon release of the ②"PARA" and ③"ENT" keys.
The ⑥"LED",⑦"LED" corresponding under the diagram.
⑥Data LED ⑦Parameter LED Control mode
A E Base temperature follow up mode . Setting Canceling
C F Constant mode. key lock key lock
DOWN
※A standard model controls inlet temperature.If you change it into outlet temperature control mode.Please attach the connector remove from
UP
+
inlet temperature sensor to outlet temperature sensor in control box and change the system parameters at once.
■Indication on the control panel and how to cope : Simultaneous
Indication Cause Cope
AL1 RP(Reverse phase protective relay) or OL1(Pump moter protective device)is actuated
AL2 THP, ITS(Compressor temp. protective switch ) or GPS(Refrigeration pressure switch) is actuated.
AL30 The Connection failure between the inverter PCB and the main PCB.
AL31 The CPU mounting the inverter PCB unusual. Prease refer to an instruction manual 8-1.
AL32 Over current of HIC(Inverter power IC)or heated up. PARA + ENT + or DOWN
UP
AL33 Over current primary of inverter PCB.
Simultaneous
AL4 HTS1 or HTS2(Heater temp. protective switch) is actuated.
AL61 The inlet temperature sensor is not connects.(The preparation sensor is not connects in case of PID control.)  
AL62 The outlet temperature sensor is not connects. (The liquid control sensor is not connects in case of PID control) Please confirm conection of the sensor. Follow up
⑥"LED"indicates ↑↓
AL63 The base temperature sensor is not connects. ※In case of wire is broken,please liquid temperature Constant
AL64 The room temrerature sensor is not connects. exchange a new sensor.
H The control liquid temperature is higher than temperature the sum of the set
temperature and the maximum alarm.
L The control liquid temperature is lower than the set temperature minus Prease refer to an instruction manual 8-1. PARA + ENT
the minimum alarm temperature. Release
45 The control liquid temperature is higher than 45 degree.
5 The control liquid temperature is lower than 5 degree.
FIL Filter clogging. Prease refer to an instruction manual
and cleaning of air filter.
※About besides,please refer to "Service Manual"attached with Oilmatic.