Switches-Air, Low Voltage
Switches-Air, Low Voltage
5. Verify correct blade alignment, blade penetration, travel stops and mechanical operation.
6. Verify that fuse sizes and types are in accordance with the drawings, short-circuit studies, and
coordination study.
7. Verify that each fuse has adequate mechanical support and contact integrity.
8. Inspect bolted electrical connections for high resistance using one of the following methods:
2. Electrical Tests.
3. Perform insulation-resistance test on each pole, phase-to-phase and phase-to-ground with switch
closed and across each open pole for one minute. Test voltage shall be in accordance with
manufacturer’s published data or table 100.1.
7. Perform test on other protective devices in accordance with section 7.9 if applicable.
3. Test Values
2. Bolt-torque levels should be in accordance with table 100.12 unless otherwise specified by the
manufacturer.
3. Microhm or millivolt drop values shall not exceed the high levels of the normal range as indicated
in the manufacturer’s published data. If manufacturer’s published data is not available, investigate
any values in which deviate from adjacent poles or similar switches by more than 50 percent of the
lowest value.
4. Minimum insulation resistance shall be in accordance with manufacturer’s published data or table
100.1.
5. Investigate fuse-resistance values that deviate from each other by more than 15 percent.
ATS-2003.45