INSPECTION & TEST PLAN |_ REV. PAGE
SIEMENS 1&TP# 1903-1
33 kV GIS
MEDIUM VOLTAGE SWITCHGEAR
00 10f8
GCC ELECTRICAL TESTING LABORATORY
FACTORY TEST PLAN
FOR
33kV 8DA10 GIS SWITCHGEAR
SIEMENS LTD
P.O. BOX 4621, JEDDAH 21412
SAUDI ARABIA
Page 1 of 8INSPECTION & TEST PLAN REV. PAGE
SIEMENS I&TP# 1903-1
00 20f8
33 KV GIS
MEDIUM VOLTAGE SWITCHGEAR
Project GCC ELECTRICAL TESTING
LABORATORY
Siemens Ref. No.
WBS 600P-01903.P
Name of Manufacture
SIEMENS Limited
Address
P.O. Box 4621
Jeddah - 21412
KSA
Place of inspection
Factory at the above address
Contact person
Mr. Nasir Iqbal (PM)
Mr. Ansari Qaiser (QC)
Contact No. / Email
Mob:0566773750
Email: [email protected]
Email: [email protected]
Page 2 of 8SIEMENS
INSPECTION & TEST PLAN.
I&TP# 1903-1
REV.
PAGE
33kV GIS MEDIUM VOLTAGE SWITCHGEAR
30f8
Project : GCC ELECTRICAL TESTING LABORATORY PROJECT
INSPECTION & TEST PLAN
WBS # G00P-01903
33KV SWITCHGEAR _: 8DA10
SI Test/inspection Brief Test Procedure ‘Acceptance Criter Applicable | Type oflnspection | Test | Remarks
No. Item Standards | Gustomer| Client] Type
|__| Inspection of Approval of engineering documents. RR RR
MECHANICAL OPERATION TEST I
1. [Mechanical ON/OFF | Operation ofthe ISOLATOR 5 _ | Smooth trouble free | 1EC 6277-200 | We Wwe R
of ISOLATOR times operation § 7.102
2. | Mechanical ON/OFF of | Operate earthing switch 5 times | Smooth & trouble free TEC 62271-200 | WC We R
Earthing switch operation §7.102
3. | Mechanical ON/OFF | Operation of the Circuit Breaker | Smooth trouble free TEC 62271-200 | WC We R
of Circuit Breaker 5 times operation § 7.102
4 | Mechanical interlock of |i) Try closing the Earthing Switch’ | Operation of earth switch? | TEC 6271-200 | WC We R
Earth switch / Isolato _ | Isolator Isolator shall not bepossible § 7.102
when the CB is in closed |
position |
il) Try closing of the CB when | Operation of CB shall be WC WC R
ES / Isolator is in closed possible
position
Ill | Measurement of the | Measurement with 100A DC Value shall be as per 1EC 62277-200 | WC we R
resistance of the
main circuit
carried out between the
cable connection terminals
from panel to panel
manufacturers standard
§73
Type of Inspection
WC — Witness Check
RR — Review of Records
ITP_39hv_@DA-SWGR_GCC LAB.GceINSPECTION & TEST PLAN. REV. PAGE
SIEMENS I&TP# 1903-1
33kV GIS MEDIUM VOLTAGE SWITCHGEAR o 8
Project : GCC ELECTRICAL TESTING LABORATORY PROJECT INSPECTION & TEST PLAN WBS # 600P-01903
Note: WC shall be on selected typical panels only.
‘SI_] Test/ Inspection Brief Test Procedure ‘Acceptance Applicable | Type of Inspection Test Remarks
No. Item Criteria ‘Standards Type
Customer | Client
WV _ | High Voltage Test
1 [Power frequency | S6KV, 60Hz AC voltage is applied between | Shall withstand TEC 62271- RR RR R__ | Test Report
Voltage Test: a phase and earth with the other two the voltage 200 of Frankfurt
phases earthed. This is conducted in turn | without any §7.1¢ Factory
for the remaining two phases. The duration | flashover Routine
for each test is 60 secs. Test
‘Shall withstand
2 | Dielectric test of With 1kV, 60HZ, 1 sec for Control Wiring the voltage IEC 62271- we we R On one
auxiliary circuits: (Wiring, aux. switches and contactors) without any: 200 panel only
* Electronic components are excluded. flashover §72
Shall withstand
V_ | Test of auxiliary _[Test of electrical devices at panel group. the voltage IEC 62271- we we R
devices fafication of correct wiring at pane! group without any 200
Varification of the iiashouer §7.104
correct wiring
Type of Inspection WC - Witness Check RR - Review of Records
Note: WC shall be on selected typical panels only.
ITP_S3iV_S0A.SWGR_6CC LAB dooINSPECTION & TEST PLAN. REV. PAGE
SIEMENS I&TP# 1903-1
33KV GIS MEDIUM VOLTAGE SWITCHGEAR . oe
Project : GCC ELECTRICAL TESTING LABORATORY PROJECT INSPECTION & TEST PLAN WBS # 600P-01903
SI Test/ Inspection Brief Test Procedure Acceptance Applicable ‘Type of Inspection Test Type | Remarks
No. Item Criteria ‘Standards EE
Customer | Client
VI | Design and visual | i) Check the breaker type, rating Shall be as per | IEC 62271- we WC R
checks plates & equipment serial no. the GA drawing. | 200 § 7.5.
ii) Check the arrangement of IEC 62271-200 WC we R
‘equipment. §75
i) Check the panel IEC 62271-200 ‘WC we R
dimensions/finish. §75
iv) Completeness of the equipment IEC 62271-200 WC wc R
§75.
v) Check for workmanship,
Materials, Surface defects, IEC 62271-200 wc we. R
Paint Specification etc. §75
Type of Inspection WC - Witness Check RR - Review of Records R - Routine Test
Note: WC shail be on selected typical panels only.
ITP_S3iV_S0ASWGR_6CC LAB dooINSPECTION & TEST PLAN.
SIEMENS T&TP# 1903-1
REV.
PAGE
33kV GIS MEDIUM VOLTAGE SWITCHGEAR
6of8
Project : GCC ELECTRICAL TESTING LABORATORY PROJECT _ INSPECTION & TEST PLAN
WBS # 600P-01903
SI] Test/ Inspection Brief Test Procedure ‘Acceptance Criteria | Applicable Type of Inspection Test | Remarks
No. Item Standards Type
Customer Client
Vila | Current
) | Transformer
14 | General Visual i) Check the Type & Rating | ShallbepertheGA | IEC61869-2| WC we R
Inspection of CT drawing
ii) Check arrangement of CT | Shall be per approved | IEC61869-2 | WC we R
drawing
Type of Inspection WC - Witness Check RR - Review of Records R - Routine Test
Note: WC shall be on selected typical panels only.
ITP_s94V_ADA-SWGR_GCC LAB.doc
Page 6018INSPECTION & TEST PLAN. REV.
PAGE
SIEMENS I&TP# 1903-1
33kV GIS MEDIUM VOLTAGE SWITCHGEAR 7 me
Project : GCC ELECTRICAL TESTING LABORATORY PROJECT INSPECTION & TEST PLAN WBS # 600P-01903
SI! | Test / Inspection Brief Test Procedure Acceptance Applicable Type of Inspection Test Remarks:
No. Item Criteria Standards Type
Customer |
2 | Verification of i) Power frequency with stand test
Test Certificate between sections and secondary Review of Test 1EC61869-2 RR RR R
winding Certificate
ii) Accuracy Test
Current error & phase
displacement test -do- 1EC61869-2 RR RR R
i) _Inter-turn voltage test Buge
Partial discharge i 1&C61869-2 RR | RR rR |
measurement test coer | |
Type of Inspection WC - Witness Check RR - Review of Records
Note: WC shail be on selected typical panels only.
Page Tot
ITP_ S8kV_AOA-SWNGR_GCC LAB doeINSPECTION & TEST PLAN. REV. PAGE
SIEMENS I&TP# 1903-1
33kV GIS MEDIUM VOLTAGE SWITCHGEAR : Bote
Project : GCC ELECTRICAL TESTING LABORATORY PROJECT _ INSPECTION & TEST PLAN WBS # 600P-01903
si Test / Inspection Brief Test Procedure Acceptance Criteria | Applicable Type of Inspection Test Remarks
No. Item ‘Standards Type
Customer | Client
Vil(b | Vortage
) | Transformer
Check the nampiate ratio and
General visual Shall be as per SLD.
inspection type of PT 1eC61869-3 we we R
i) Check for polarity 1EC61869-3 we we R
i) Measure Insulation resistance
(megger test) 16C61869-3 we we R
iv) Measure ratio lece1869-3, we we R
Inspection Release Notice (IRN)
Type of Inspection WC - Witness Check RR - Review of Records R- Routine Test
Note: WC shall be on selected typical panels only.
Page Oof8