67% found this document useful (3 votes)
843 views

2 Synchronous Generator Withans

This document contains questions about synchronous generators/alternators. Key points covered include: - Voltage drops that occur in an alternator and how they are affected by load current and power factor - How generated voltage and frequency depend on factors like pole number and rotor speed - Types of rotors suitable for high-speed turbo alternators - How power factor, regulation, and output are affected by changes in load or excitation - Parallel operation of alternators and how their load sharing is affected

Uploaded by

Incst Bhai
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
67% found this document useful (3 votes)
843 views

2 Synchronous Generator Withans

This document contains questions about synchronous generators/alternators. Key points covered include: - Voltage drops that occur in an alternator and how they are affected by load current and power factor - How generated voltage and frequency depend on factors like pole number and rotor speed - Types of rotors suitable for high-speed turbo alternators - How power factor, regulation, and output are affected by changes in load or excitation - Parallel operation of alternators and how their load sharing is affected

Uploaded by

Incst Bhai
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 19

Synchronous Generator

1. In an alternator, voltage drops occurs in


(A) armature resistance only
(B) armature resistance and leakage reactance
(C) armature resistance, leakage reactance and armature reaction
(D) armature resistance, leakage reactance, armature reaction and earth connections.
2. The magnitude of various voltage drops that occur in an alternator, depends on
(A) power factor of the load
(B) load current
(C) power factor x load current
(D) power factor x (load current)2
3. In an alternator, at lagging power factor, the generated voltage per phase, as compared to that at unity
power factor
(A) must be same as terminal voltage
(B) must be less than the terminal voltage
(C) must be more than the terminal voltage
(D) must be 1.41 time the terminal voltage.
4. The power factor of an alternator depends on
(A) Load
(B) Speed of rotor
(C) Core losses
(D) Armature losses.
5. Which kind of rotor is most suitable for turbo alternators which arc designed to run at high speed?
(A) Salient pole type
(B) Non-salient pole type
(C) Both (A) and (B) above
(D) None of the above.
6. Salient poles are generally used on
(A) high speed prime movers only
(B) medium speed prime movers only
(C) low speed prime movers only
(D) low and medium speed prime movers.
7. The frequency of voltage generated in an alternator depends on
(A) number of poles
(B) rotative speed
(C) number of poles and rotative speed
(D) number of poles, rotative speed and type of winding.
8. The frequency of voltage generated by an alternator having 8 poles and rotating at 250 rpm is
(A) 60 Hz
(B) 50 Hz
(C) 25 Hz
(D) 16 2/3 Hz.
9. An alternator is generating power at 210 V per phase while running at 1500 rpm. If the need of the
alternator drops to 1000 rpm, the generated voltage per phase will be
(A) 180 V
(B) 150 V
(C) 140 V
(D) 105 V.
10. A 10 pole AC generator rotates at 1200 rpm. The frequency of AC voltage in cycles per second will be
(A)120
(B) 110
(C) 100
(D) 50.
11. The number of electrical degrees passed through in one revolution of a six-pole synchronous
alternator is
(A)360
(B)720
(C) 1080
(D)2160
12. Fleming's left-hand rule may be applied to an electric generator to find out
(A) direction of rotor rotation
(B) polarity of induced emf
(C) direction of induced emf
(D) direction of magnetic field.
13. If the input to the prime mover of an alternator is kept constant but the excitation is changed, then the
(A) reactive component of the output is changed
(B) active component of the output is changed
(C) power factor of the load remains constant
(D) power factor of the load reduces.
14. An alternator is said to be over excited when it is operating at
(A) unity power factor
(B) leading power factor
(C) lagging power factor
(D) lagging to leading power factor.
15. When an alternator is running on no load the power supplied by the prime mover is mainly consumed
(A) to meet iron losses
(B) to meet copper losses
(C) to meet all no-load losses
(D) to produce induced emf in armature winding.
16. As the speed of an alternator increases
(A) the frequency increases
(B) the frequency decreases
(C) the frequency remains constant but power factor decreases
(D) none of the above.
17. For an alternator when the power factor of the load is unity
(A) the armature flux will have square waveform
(B) the armature flux will be demagnetising
(C) the armature flux will be cross-magnetising
(D) the armature flux will reduce to zero.
18. The driving power from the prime mover driving the alternator is lost but the alternator remains
connected to the supply network and the field supply also remains on. The alternator will
(A) get burnt
(B) behave as an induction motor but will rotate in the opposite direction
(C) behave as a synchronous motor and will rotate in the same direction
(D) behave as a synchronous motor but will rotate in a reverse direction to that corresponding to
generator action.
19. If the input of the prime mover of an alternator is kept constant but the excitation is changed, then
(A) the active component of the output is changed
(B) the reactive component of the output is changed
(C) power factor of the load remains constant
(D) power factor of the load changes from lagging to leading.
20. For 50 Hz system the maximum speed of an alternator can be
(A) approximately 3600 rpm
(B) approximately 3000 rpm
(C) 3600 rpm
(D) 3000 rpm.
21. Voltage characteristic of an alternator is shown in figure. Which curve represents the characteristics for
leading power factor?
Synchronous Generator MCQ No 21
(A) A
(B) B
(C) C
(D) D.
22. In the above figure, the characteristic for unity power factor is represented by the curve maked
(A) A
(B) B
(C)C
(D) D
Questions 23 to 26 refer to the following data:
In a 50 kVA, star connected 440 V, 4-phase 50 Hz alternator, the effective armature resistance is 0.25 ohm
per phase. The synchronous reactance is 3.2 ohm per phase and leakage reactance is 0.5 ohm per phase.
23. Full load output current at unity power factor will be
(A) 65.6 A
(B) 55.4 A
(C) 45.6 A
(D) 35.4 A.
24. Full load line voltage will be
(A) 500 V
(B) 471 V
(C) 450 V
(D) 435 V.
25. No load line voltage will be
(A) 600 V
(B) 599 V
(C)592V
(D) 580 V.
26. Percentage regulation of the alternator is approximately
(A) 55%
(B) 45%
(C) 35%
(D) 25%.
27. In order that two alternators be put in parallel, which of the following factors should be identical for
both?
(A) Voltage
(B) Frequency
(C) Phase sequence
(D) All of the above.
28. When two alternators are running in parallel, their RKVA load share is changed by changing
their ................ while their kW load share is changed by changing their ..............
(A) excitation, driving torque
(B) driving torque, excitation
(C) excitation, excitation
(D) driving torque, driving torque.
29. Two-alternators are running in parallel. If the driving force of both the alternators is changed, this will
result in change is
(A) frequency
(B) back emf
(C) generated voltage
(D) all of the above.
30. A three phase alternator has a phase sequence of RYB for its three output voltages. In case the field
current is reversed, the phase sequence will become
(A) RBY
(B) RYB
(C) YRB
(D) none of the above
31. The armature reaction of an alternator influences
(A) windage losses
(B) operating speed
(C) generated voltage per phase
(D) waveform of voltage generated.
32. For the same power rating, a lower voltage alternator will be
(A) more efficient
(B) larger in size
(C) operating at high rpm
(D) more costly
33. An alternator is supplying 10A to an inductive load at 220 V, while running at 1000 rpm. Now if the speed
of the alternator is reduced to 750 rpm but the field current remains unchanged, the load current will
become
(A) 18 A
(B) 13.3 A
(C) 10 A
(D) 7.5 A.
34. Dampers in a large generator
(A) increase stability
(B) reduce voltage fluctuations
(C) reduce frequency fluctuations.
35. An alternator is rated for 75 kW at 0.8 power factor. It means that
(A) alternator has 4 poles
(B) alternator can supply 75 kW at 0.8 power factor
(C) alternator can supply power only to loads having power factor 0.8 only
(D) the peak efficiency of alternator occurs only at 75 kW load having 0.8 lagging power factor.
36. The regulation of an alternator is
(A) the reduction in terminal voltage when alternator is loaded
(B) the variation of terminal voltage under the conditions of maximum and minimum excitation
(C) the increase in terminal voltage when load is thrown off
(D) the change in terminal voltage from lagging power factor to leading power factor.
37. A magnetization curve represents the relationship between
(A) reactive and non-reactive components of voltage
(B) exciting currents and terminal voltage
(C) power factor and terminal voltage
(D) magnetic flux and armature current.
38. In an alternator if the armature reaction produces demagnetisation of the main field, the power factor
should be
(A) Zero, lagging load
(B) Zero, leading load
(C) Unity.
39. In an alternator if the armature reaction produces magnetisation of the main field the power factor
should be
(A) Zero, lagging load
(B) Zero, leading load
(C) Unity
40. When an alternator is supplying unity power factor load, the armature reaction will produce
(A) magnetisation of the main field
(B) demagnetisation of the main field
(C) distortion of the main field.
41. An alternator has full load regulation of 4% when the power factor of the load is 0.8 lagging while
alternator runs at 1500 rpm. The full load regulation of 1400 rpm for 0.8 pf lagging load will be
(A) 15/14 x 4 percent
(B) 14/15 x 4 percent
(C) 4 percent
(D) Depends on other factors also.
42. The Poitier’s triangle separates the
(A) iron losses and copper losses
(B) field mmf and armature mmf
(C) stator voltage and rotor voltage
(D) armature leakage reactance and armature reaction mmf.
43. In the Poitier’s triangle, the Potier reactance drop per phase is 22 volts per phase at 88 amperes per
phase. The Potier's reactance per phase is
(A) 0.22
(B) 0.25
(C) 0.30
(D) 0.44.
44. Two alternators are running in parallel. The excitation of one of the alternator is increased. The result will
be
(A) machine with excess excitation will burn
(B) both machines will start vibrating
(C) power output will decrease
(D) wattless component will change.
45. The power output of an alternators is 100 kW. In order that the tangent of pf angle may be 0.8 lagging,
the KVAR rating must be
(A) 80 cosφ KVAR
(B) 80 sin φ KVAR
(C) 80 KVAR
(D) -80 KVAR
46. The power output of an alternator is 40 kW and KVAR component is - 25. What will be the value of tanφ
(φ being the power factor angle)?
(A) 0.625 lagging
(B) 0.625 leading
(C) 0.375 lagging
(D) 0.375 leading.
47. When short pitch coils of 160 are used in an alternator, which harmonic component will not be present in
the output emf?
(A) third
(B) fifth
(C) seventh
(D) ninth.
48. A 120 MW turbo alternator is supplying power to 80 MW load at p.f. lagging. Suddenly the steam supply
to the turbine is cut off and the alternator remains connected to the supply network and the field supply also
remains on. What will happen to the alternator?
(A) The stator winding of the alternator will get burnt
(B) The rotor winding of the alternator will get burnt
(C) The alternator will continue to run as a synchronous motor rotating in the same direction
(D) The alternator will continue to run as a synchronous motor rotating in the opposite direction.
49. The figure shows the characteristics of an alternator. Which curve represents synchronous impedance?
Synchronous Generator MCQ No 49
(A) curve A
(B) curve B
(C) curve C
(D) curve D.
50. In the above figure (Figure of Question 49) which curve represents short circuit?
(A) curve A
(B) curve B
(C) curve C
(D) curve D.
51. In the above figure which curve represents open circuit voltage?
(A) curve A
(B) curve B
(C) curve C
(D) curve D.
52. For a peripheral speed of 314 m/s, a 2-pole cylindrical machine will have maximum diameter of
(A) 255 cm
(B) 235 cm
(C) 200 cm
(D) 170 cm.
53. The rotor of the salient pole alternator has 24 poles. The number of cycles of emf in one revolution would
be
(A) 24
(B) 12
(C) 6
(D) 4.
54. Two alternators A and B are sharing an inductive load equally. If the excitation of alternator A is increased
(A) alternator B will deliver more current and alternator A will deliver less current
(B) alternator B will deliver less current and alternator A will deliver more current
(C) both will continue to share load equally
(D) both will deliver more current.
55. Desirable feature for the parallel operation of two alternators is
(A) both should have same resistance
(B) both should have same reactance
(C) both should have less of resistance as compared to synchronous reactance
(D) both should have more of resistance as compared to synchronous reactance.
56. Alternators used in aircraft systems usually have frequency of
(A) 25 Hz
(B) 50 Hz
(C) 100 Hz
(D) 400 Hz.
57. High frequency on aircraft alternators are selected in order to
(A) free the systems from external disturbance
(B) compensate for high speeds
(C) compensate for high altitudes
(D) reduce the bulk.
58. A 20 pole ac generator rotates at 600 rpm. The periodic time of current in seconds per cycle is
(A) 0.009
(B) 0.004
(C) 0.008
(D) 0.01.
59. What kind of rotor is most suitable for turbo alternators?
(A) salient pole type
(B) non-salient pole type
(C) both (A) and (B) above
(D) none of the above.
60. The synchronizing power developed in one of the alternators, when two alternators are running in
parallel, will load the same alternator in which it is developed and reduce its speed
(A) True
(B) False
61. If the input to the prime mover of an alternator is kept constant but the excitation is changed then the
(A) reactive component of the output is changed
(B) active component of the output is changed
(C) power factor of load remains constant.
62. If two machines are running in synchronism and the voltage of one machine is suddenly increased
(A) the machines will burn
(B) both machines will stop
(C) synchronizing torque will be produced to restore further synchronism.
63. In an alternator, at 0.8 lagging power factor, the generated voltage per phase is 240 V to give a rated
terminated voltage ' V '. If the power factor of load increases to unity, the generated voltage per phase must
be
(A) 260 V
(B) 250 V
(C) 240 V
(D) 225 V.
64. The advantage of salient poles in an alternator is
(A) reduce noise
(B) reduced windage loss
(C) adoptability to low and medium speed operation
(D) reduce bearing loads and noise.
65. Magnetisation curves for no load and full load unity power factor are shown in figure below. Which is the
magnetisation curve for full load 0.8 power factor?
(A) curve A
(B) curve B
(C) curve C
(D) curve D.
66. At a particular instant a turbo alternator is generating 80 MW at 0.8 power factor lagging. Now if the
steam supply valve to the steam turbine is further opened and the excitation is not changed
(A) the speed of the alternator will increase but kW delivered will remain unchanged
(B) the speed of the alternator will increase and kW delivered will also increase
(C) the speed of the alternator will remain unchanged but it can meet more kW demand
(D) the speed of the alternator will remain unchanged but it will deliver more kVA.
67. Two alternators A and B are sharing a resistive load (p.f. = 1) equally. Now if the excitation of alternator A
is increased
(A) alternator A will become lagging and alternator B will become leading
(B) alternator A will become leading and alternator B will become lagging
(C) both alternators will continue to operate on unity power factor
(D) both alternators will operate on lagging power factor
(E) both alternators will operate on leading power factor.
68. The advantage of providing damper winding in alternators is
(A) elimination of harmonic effects
(B) provide a low resistance path for the currents due to unbalancing of voltage
(C) oscillations are provided when two alternators operate in parallel
(D) all of the above.
69. When two alternators are running in exactly synchronism, the synchronizing power will be
(A) zero
(B) sum of the output of two
(C) unity
(D) 0.707.
Questions 70 to 72 refer to the figure given below:
70. Load characteristic curves for an alternator are shown. The curves are drawn for 0.8 pf lagging, 0.8 p.f.
leading, 0.7 p.f. leading and 0.9 p.f. lagging. Which curve represents the characteristics for 0.8 p.f. leading?
(A) curve A
(B) curve B
(C) curve C
(D) curve D.
71. Which curve represents the data for 0.8 p.f. lagging?
(A) curve A
(B) curve B
(C) curve C
(D) curve D.
72. Which curve represents the data for 0.9 p.f. lagging?
(A) curve A
(B) curve B
(C) curve C
(D) curve D.
73. The balanced short circuit current of a three-phase alternator is 25 amperes at 1500 rpm. For the same
field current, the balanced short current at 1400 rpm will be
(A)18 A
(B) 27 A
(C) 20 A
(D) 20*(2)1/2A
74. A three phase alternator has a phase sequence of RYB for its three output voltages, for clockwise rotation.
Now if the alternator is rotated anticlockwise, the phase sequence will be
(A) RYB
(B) RBY
(C) BYR
(D) none of the above.
75. In a synchronous machine, if the field flux axis is ahead of the armature field axis, in the direction of
rotation, the machine working as
(A) asynchronous motor
(B) asynchronous generator
(C) synchronous motor
(D) synchronous generator.
76. In synchronous alternator, which of the following coils will have emf closer to sine waveform?
(A) concentrated winding in full pitch coils
(B) concentrated winding in short pitch coils
(C) distributed winding in full pitch coils
(D) distributed winding in short pitch coils.
77. An alternator has rated field current of 4 A. The alternator develops 180 V while drawing a field current of
2 A at 750 rpm. If the field current is made 4 A at 750 rpm generated voltage could be
(A) 400 V
(B) 380 V
(C) 60V
(D) 330 V.
78. The armature reaction of an alternator will be completely magnetizing in case the load power factor is
(A) unity
(B) 0.707
(C) zero lagging
(D) zero loading.
79. Which of the following is not an integral part of synchronous generator system?
(A) prime mover
(B) distribution transformer
(C) excitation system
(D) protection system.
80. For turbo generators the range of excitation voltage is
(A) 10 to 20 V
(B) 30 to 100 V
(C) 100 to 800 V
(D) 1000 to 1800 V.
81. In case of low speed hydrogenators, the short circuit ratio is usually
(A) 0.1 to 0.5
(B) 0.5 to 0.6
(C) 0.6 to 1.0
(D) 1.0 to 1.5.
82. The permissible duration for which a generator of rated frequency 50 Hz can run at 46 Hz is
(A) zero
(B) one cycle
(C) one second
(D) one minute.
83. The permissible duration in supply. frequency is
(A) ± 2 %
(B) ± 5 %
(C) ± 10 %
(D) ± 25 %.
84. The regulation of an alternator is likely to be negative in case of
(A) high speed alternators
(B) slow speed alternators
(C) lagging power factor of the load
(D) leading power factor of the load.
Questions 85 to 88 refer to the data given below:
A phase, 50 Hz, 6600 V, alternator is rated at 6600 kW at 0.8 power factor and a full load efficiency of 90%.
85. kVA is rating of the alternator is
(A) 750 kVA
(B) 7500 kVA
(C) 75000 kVA
(D) 750000 kVA.
86. The current rating of the alternator is
(A) 65.63 A
(B) 656.3 A
(C) 6563 A
(D) 65630 A.
87. The input to the alternator is
(A) 666.6 kW
(B) 6666 kW
(C) 66660 kW
(D) 666,600 kW.
88. If the input. to an alternator remains unaltered, but excitation is changed then which of the following will
not change?
(A) kVA output
(B) kW output
(C) power factor
(D) all of the above.
89. Which of the following method is likely to give the voltage regulation more than the actual value?
(A) Synchronous reactance method
(B) MMF method
(C) Zero power factor method
(D) None of the above.
90. The effect of cross magnetization in an alternator field is to make the output
(A) true sinusoidal
(B) non-sinusoidal
(C) harmonic free
(D) none of the above.
91. In order to reduce the harmonics in the emf generated in an alternator
(A) slots are skewed
(B) salient pole tips are chamfered
(C) winding is well distributed
(D) all of the above.
92. The maximum power in a synchronous machine is obtained when the load angle is
(A) 0°
(B) 85°
(C) 120°
(D) 135°
93. The emf generated due to nth harmonic component of flux in an alternator will be
(A) n times the fundamental emf
(B) same as fundamental emf
(C) less than the value of fundamental emf.
94. Synchronizing torque comes into operation under all of the following cases EXCEPT
(A) phase difference between two voltages
(B) frequency difference between two voltages
(C) voltage difference between two voltages
(D) reduction in exciting current in one of the alternators.
95. Unbalanced 3-phase stator currents cause
(A) double frequency currents in the rotor
(B) healing of rotor
(C) vibrations
(D) all of the above.
96. In large generators protection provided against external faults is
(A) biased differential protection
(B) sensitive earth fault protection
(C) inter-turn fault protection
(D) all of the above.
97. Pitch factor is the ratio of the emfs of
(A) short pitch coil to full pitch coil
(B) full pitch winding to concentrated winding
(C) full pitch winding to short pitch winding
(D) distributed winding to full pitch winding.
98. In an alternator if the winding is short pitched by 50 electrical degrees, its pitch factor will be
(A) 1.0
(B) 0.866
(C) 0.75
(D) 0.50.
99. The Potier's triangle separates
(A) stator losses and rotor losses
(B) fixed losses and variable losses
(C) armature voltage and field voltage
(D) armature leakage reactance and armature reaction mmf.
100. If a single-phase alternator has 8 slots per pole uniformly speed, but the winding is arranged with the
middle two left empty, the breadth coefficient will be
(A) 0.99
(B) 0.88
(C) 0.67
(D) 0.53.
101. Two alternators are running in parallel. If the field of one of the alternator is adjusted, it will
(A) reduce its speed
(B) change its load
(C) change its power factor
(D) change its frequency.
102. A generator is operating by itself supplying the system loads. The reactive power supplied by the
generator will
(A) depend on prime mover rpm
(B) depend on type of insulation used
(C) depend on the amount demanded by the load
(D) depend on inter-coil inductance.
103. Which of the following part plays important role in over speed protection of a generator?
(A) Over current relay
(B) Alarm
(C) Differential protection
(D) Governor.
104. Which type of protection is provided on a generator to protect against stator insulation failure?
(A) Differential protection
(B) Thermocouple actuated alarm
(C) Over current relay
(D) Reverse power relay.
105. Which relays comes into operation in the event of the failure of prime mover connected to the
generator?
(A) Reverse power relay
(B) Differential relay
(C) Buchholz relay
(D) None of the above.
106. In alternators, the distribution factor is defined as the ratio of emfs of
(A) distributed winding to connected winding
(B) full pitch winding to distributed winding
(C) distributed winding to full pitch winding
(D) concentrated winding to distributed winding.
107. One of the advantages of distributing the winding in alternator is to
(A) reduce noise
(B) save on copper
(C) improve voltage waveform
(D) reduce harmonics.
108. In case of a uniformly distributed winding, the value of distribution factor is
(A) 0.995
(B) 0.80
(C) 0.75
(D) 0.50.
109. The advantage of a short pitch winding is
(A) low noise
(B) increased inductance
(C) suppression of harmonics
(D) reduced eddy currents.
110. Two alternators are connected in parallel. Their kVA and kW load share can be changed by changing
respectively their
(A) driving torque and excitation
(B) excitation and driving torque
(C) excitations only
(D) driving torques only.
111. In case of alternators, the dark and bright lamp method is used for
(A) phase sequence
(B) load balancing
(C) synchronizing
(D) load transfer.
112. The advantage of using short pitched windings in an alternator is that it
(A) suppresses the harmonics in generated emf
(B) reduces the total voltage around the armature coils
(C) saves copper used in windings
(D) improves cooling by better circulation of air.
113. For the same power rating, an alternator operating at lower voltage will be
(A) less noisy
(B) costlier
(C) larger in size
(D) more efficient.
114. Which of the following is the common synchronous speed in rpm between 60 Hz and 50 Hz alternators?
(A) 900
(B) 600
(C) 375
(D) 225.
115. All of the following losses for a synchronous machine are fixed EXCEPT
(A) Bearing friction loss
(B) Copper loss
(C) Windage loss
(D) Core loss.
116. Salient pole type rotors as compared to cylindrical pole type are
(A) smaller in diameter and larger in axial length
(B) larger in diameter and smaller in axial length
(C) larger in diameter as well as axial length
(D) small in diameter as well as axial length.
117. In a synchronous machine, the field flux axis is ahead of the armature field axis in the direction of
rotation, the machine is working as
(A) asynchronous alternator
(B) asynchronous motor
(C) synchronous motor
(D) synchronous alternator.
118. Which of the following is not a common synchronous speed in rpm between a 50 Hz and 25 Hz
alternator?
(A) 750
(B) 375
(C) 250
(D) 200.
119. The effective voltage in one phase of an alternator having 240 turns per phase, frequency of 60 Hz and
flux per pole of 2.08 x 106
lines will be
(A) 332.5 V
(B) 665 V
(C) 1330 V
(D) 2660 V.
120. The maximum current that can be supplied by an alternator depends on
(A) speed of the exciter
(B) number of poles
(C) exciter current
(D) strength of the magnetic field.
121. The windings for an alternator are
I. 36 slots, four poles, span 1 to 8
II. 72 slots, six poles, span 1 to 10
III. 96 slots, six poles, span 1 to 12.
The windings having pitch factors of more than 0.9 are
(A) I and II only
(B) II and III only
(C) I and II only
(D) I, II and III.
Questions 122 to 124 refer to data given below:
A 500 kVA ,2300-volt three phase star connected alternator has a full load armature-resistance drop per
phase of 50 volts and a combined armature reactance plus armature-reaction drop of 500 volts per phase
122. The percent regulation of the alternator at unity power factor is
(A) 1.05
(B) 10.5
(C) 21.5
(D) 27.5.
123. The percent regulation of the alternator at 0.866 power factor lagging is
(A) 26.3
(B) 20.1
(C) 16.6
(D) 10.5.
124. The percent regulation of the alternator at 0.8 power factor leading is
(A) 13.2
(B) 26.4
(C) - 26.4
(D) - 13.2.
125. The imaginary or fictitious part of synchronous reactance takes care of
(A) armature reaction
(B) voltage regulation
(C) inductive reactance
(D) none of the above.
126. In an alternator, the use of short pitch coils of 160° will indicate the absence of
(A) third harmonic
(B) fifth harmonic
(C) seventh harmonic
(D) ninth harmonic.
127. When a generator designed for operation at 60 Hz is operated at 50 Hz
(A) operating voltage must be derated to (50/60) of its original value
(B) operating voltage must be derated to (50/60)2 of its original value
(C) kVA rating can be upgraded to (60/50) of the rated value
(D) the generator will not take any load.
128. Overheating of generator's winding
(A) reduces generated voltage
(B) reduces power factor
(C) reduces life of the machine
(D) does not have any significant effect.
129. Rotor shaft of 500 MW alternator is supported in
(A) ball bearings
(B) roller bearings
(C) needle bearings
(D) journal bearings.
130. The voltage of field system for an alternator is usually
(A) less than 200 V
(B) between 200 V and 440 V
(C) 400 V
(D) more than 1 kV.
131. Maximum electric power output of a synchronous generator is
(A) Xs / VtEf
(B) V2t/ Xs
(C) E2f/ Xs
(D) VtEf/ Xs
132. The electrical angle between the field axis and axis of armature reaction of a loaded synchronous
generator with armature current lagging behind the excitation emf by ψ is
(A) ψ - 90
(B) ψ + 90
(C) 90 - ψ
(D) ψ + 180.
133. Two synchronous generators G1and G2 are equally sharing the KVAR of the load while operating in
parallel. Keeping the terminal voltage fixed in order to shift part of the KVAR load from G2 to G1
(A) The field current of G1 is lowered
(B) The field current of G2 is raised
(C) The field current of G1 is raised and of G2 lowered
(D) The field current of G1 is lowered and of G2 is raised.
134. A synchronous generator is operating with excitation adjusted for unity power factor current at constant
load. When on increasing the excitation the power factor
(A) will lag
(B) will lead
(C) will become zero
(D) none of the above.
135. On changing the speed of an alternator from 4000 rpm to 2000 rpm, the generated emf phase will
become
(A) 1/4
(B) 1/2
(C)1/3
(D)1/5
136. Zero power factor method of an alternator is used to find its
(A) field resistance
(B) armature resistance
(B) armature resistance
(C) efficiency
(D) voltage regulation.
137. The power factor of an alternator is obtained from its
(A) excitation
(B) speed
(C) load
(D) none of the above.
138. For parallel operation, alternators must have
(A) same speed
(B) same kVA rating
(C) same voltage rating
(D) none of the above.
139. For alternation having fractional pitch of 5/6 the coil span is
(A)90°
(B)120°
(C)150°
(D)180°
140. Fractional pitch to eliminate 7th harmonic from alternator emf is
(A) 7/6
(B) 6/7
(C) 6/5
(D) 3/5.
141. Consider the following statements about a three-phase synchronous generator synchronized to an
infinite bus when its mechanical input is increased gradually with field current held constant:
1. The power factor of the current supplied becomes more lagging.
2. The power factor of the current supplied improves.
3. The power factor remains unity.
4. The load angle is increased.
Of these statements
(A) 1 alone is correct
(B) 2 alone is correct
(C) 2 and 4 are correct
(D) 3 and 4 are correct.
142. A 3-phase synchronous generator, with its armature resistance and the leakage reactance being
neglected, is synchronized to an infinite bus and its field excitation is kept constant thereafter. Now the
machine is loaded by Supplying mechanical input to the shaft so that the load-angle δ reaches a value of 60°
Under this condition, the operating power-factor would be
(A) 0.866 leading
(B) 0.866 lagging
(C) 0.5 leading
(D) 0.5 lagging.
143. A round rotor synchronous generator has a leakage reactance of 10%, armature reaction reactance of
90% and negligible armature resistance. With the machine initially running at rated speed and terminal
voltage of 1.0 p.u., a 3-phase short-circuit is applied. The sustained armature current will be
(A) 1.25 p.u.
(B) 1.11 p.u.
(C) 1.0 p.u.
(D) 0.9 p.u.
144. Following a sudden short-circuit at the terminals of a 3-phase unloaded synchronous generator, the
initial effect of the pole-face damper windings, is to
(A) establish the armature flux through the direct-axis magnetic circuit of the machine
(B) allow only partial linkage of the armature flux with the main field winding
(C) confine the armature flux to completely link the damper winding
(D) repel the armature flux and confine it to the leakage flux path in the air-gap.
145. In a synchronous generator operating at zero pf lagging, the effect of armature reaction is
(A) magnetizing
(B) demagnetizing
(C) cross-magnetizing
(D) both magnetizing and cross-magnetizing.
146. Which of the following limit the reactive power output of a synchronous generator?
1. Armature current
2. Field current
3. Load angle
4. Prime mover input.
Select the correct answer using the codes given below: Codes
(A) land 2
(B) 2 and 3
(C) 3 and 4
(D) land 4.
147. The steady-state stability limit of a synchronous generator can be increased by
(A) an increase in its reactance
(B) an increase in the excitation of the machine
(C) a decrease in the moment of inertia of the machine
(D) an increase in the moment of intertia of the machine.

You might also like